In the ACS880-01 range the ACS880-01-246A-3 is the type that ABB rates for 132 kW at 400 V. It is a frame R8 unit rated 132 kW and 246 A. Engineers specify this size for water-works main pumps and large fans and blowers. Because the choke and Safe Torque Off are already inside, the drive can be mounted on the wall without extra filter hardware.

Technical specifications

Parameter Specification
Type designation ACS880-01-246A-3
Series ACS880-01, wall-mounted single drive, ACS880 industrial drive platform
Supply voltage 3-phase 380 to 415 V (400 V table)
Nominal rating 132 kW, 246 A
Light overload use 132 kW, 234 A
Heavy-duty use 110 kW, 206 A
Peak current IMAX 350 A
Frame size R8
IP21 height, width, depth, weight 963 mm with cable box (681 mm without), 300 mm, 386 mm, 68 kg
IP55 size (H x W x D) 963 x 300 x 452 mm; 74 kg
Sound level 68 dB(A)
Heat dissipation 3026 W
Air flow 550 m3/h
Brake chopper availability A selectable internal option, order code +D150
Minimum brake resistance 2.3 ohm for 132 kW braking power
Sine filter type B84143V0230S229 (rated 209 A)

Sizing and installing the ACS880-01-246A-3

ABB gives 234 A (132 kW) for light overload use and 206 A (110 kW) for heavy duty, against a nominal 246 A and a peak of 350 A. Choose light overload for variable-torque loads such as pumps and fans, and heavy duty for constant-torque machines with high breakaway torque. Start from the motor nameplate current, then verify derating for temperature, altitude and switching frequency.

Wall space needed for IP21 is 300 mm by 963 mm (cable box included), 386 mm deep, with a weight of 68 kg. For harsher rooms ABB offers IP55 at 963 x 300 x 452 mm and 74 kg. Heat dissipation is 3026 W at 90% frequency and full motor current, with 550 m3/h of cooling air and 68 dB(A) of noise.

Braking, filters and options

For braking, the chopper is a selectable internal option, order code +D150. ABB lists the SAFUR200F500 resistor of 2.7 ohm and 5400 kJ at 132 kW, and a minimum resistance of 2.3 ohm. The EMC filter options are +E202 (C2), +E200 (C3) and +E201 (C3 on ungrounded supplies); the base drive is C4. For long cables, submersible pumps or noise reduction, ABB lists the B84143V0230S229 sine filter (209 A, 110 kW).

Standard I/O is 6 digital inputs, 2 DIO, 2 analog inputs, 2 analog outputs and 3 relay outputs, plus STO and the RS485 link. Fieldbus adapters, extra I/O, encoder interfaces and safety modules fit into the three option slots.

Related ABB products: ABB ACQ580-01-246A-4 Water Drive 132 kW 246 A, ABB ACQ580-01-206A-4 Water Drive 110 kW 206 A, ABB ACQ580-01-026A-4 Water Drive 11 kW 25 A, ABB ACQ580-01-046A-4 Water Drive 22 kW 45 A, ABB ACS580-01-026A-4 AC Drive 11 kW 25 A and ABB ACS580-01-046A-4 AC Drive 22 kW 45 A.

Source document and RFQ

This page follows ABB’s ACS880 single drives catalogue (3AUA0000098111, linked) plus the ABB product page for the ACS880-01-246A-3. Seven Star LLC supplies the ACS880-01-246A-3 on request from Muscat; availability and lead time are stated in the quotation. Before ordering, check the full type code with options, the motor rating, enclosure, filters, braking duty and site conditions. More sizes sit in AC drives, and the ABB ACS580 page covers the general purpose family.

Datasheets & Documents
  • PDF Catalog ABB ACS880 single drives catalog (3AUA0000098111) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.

ABB company profile

Formed 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50%
ASEA Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators
Brown, Boveri & Cie Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri
Headquarters Zurich, Switzerland; ABB Ltd became the group holding company in 1999
Ownership Public company listed on SIX Swiss Exchange and Nasdaq Stockholm
Brands in the group Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers
Product families Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots

Milestones

  • 1883: ASEA is founded in Västerås, Sweden.
  • 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
  • 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
  • 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
  • 2011 and 2017: Baldor Electric and B&R join ABB.
  • 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.

Choosing an ABB drive

ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.

Where ABB products are used

In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.

ABB products we list

Family Examples
AC drives ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module
Breakers, motor control and protection SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay
Flow measurement ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500
Pressure, temperature and level 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge
Analysers Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210
Control systems and actuators AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000

Ordering ABB products: what we need

Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.

Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.

FAQ

Questions about the ABB ACS880-01-246A-3 Wall-Mounted Drive 132 kW 246 A

Answers from our engineering team on installation, compatibility and integration.

01What are the duty ratings of the ACS880-01-246A-3?
ABB lists 246 A nominal (132 kW), 234 A (132 kW) for light overload, 206 A (110 kW) for heavy duty and 350 A maximum output current.
02What size and weight is the ACS880-01-246A-3 in IP21?
It is frame R8: 963 mm high with cable entry box, 300 mm wide, 386 mm deep and 68 kg; the IP55 version is 963 x 300 x 452 mm and 74 kg.
03Does the ACS880-01-246A-3 include a brake chopper?
The brake chopper is a selectable internal option, order code +D150; the catalogue lists SAFUR200F500 (2.7 ohm) and a minimum resistance of 2.3 ohm.
04How much heat and cooling air does the ACS880-01-246A-3 need?
The catalogue gives 3026 W of heat dissipation, 550 m3/h of air flow and 68 dB(A) noise.
05Which EMC filter options exist for the ACS880-01-246A-3?
The catalogue lists +E202 for C2, +E200 for C3 and +E201 for ungrounded networks; category C4 is standard on 380 to 500 V ACS880-01 drives.