Brand: ABB
ABB MO165-80 Magnetic Manual Motor Starter 80 A
Description
ABB MO165-80 magnetic-only manual motor starter, 80 A
The ABB MO165-80 is a three-pole manual motor starter with magnetic release only, rated 80 A, with a fixed short-circuit setting of 1120 A and a catalogue rating of 45 kW at 400 V in category AC-3. It belongs to the MO165 frame, 55 mm wide, which the catalogue describes for motors up to 45 kW at 400 V. The order code for this type is 1SAM461000R1019.
The 80 A type is the top of the MO165 range at 45 kW at 400 V. It is a short-circuit and disconnect device for the largest motors that this frame covers, normally combined with a contactor and an electronic overload relay.
Reading the MO165-80 type code
MO stands for manual motor starter, magnetic only, 165 is the frame and 80 is the rated operational current in amperes. Unlike the MS165 range, the ABB MO165-80 has no thermal release and no adjustment dial, so it gives short-circuit protection and a manual disconnect function only. ABB notes that for overload protection of the motor an appropriate thermal or electronic overload relay must be used.
MO165-80 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | ABB / MO165-80 |
| Order code | 1SAM461000R1019 |
| Rated operational current Ie | 80 A |
| Rated power AC-3 at 400 V | 45 kW |
| Rated instantaneous short-circuit current setting Ii | 1120 A |
| Service short-circuit breaking capacity Ics at 400 V AC | 30 kA |
| Ultimate short-circuit breaking capacity Icu at 400 V AC | 30 kA |
| Back-up fuse at 400 V | not specified in the catalogue |
| Rated operational voltage Ue | 690 V AC / 250 V DC |
| Rated insulation voltage Ui | 1000 V |
| Rated impulse withstand voltage Uimp | 8 kV |
| Thermal release / phase-loss sensitivity | None / No |
| Number of poles | 3 |
| Width | 55 mm |
| Weight (1 piece) | 1.000 kg |
| Degree of protection | IP20 housing, IP10 main terminals |
| Ambient temperature, operation (open) | -25 to +60 °C |
| Storage temperature | -50 to +80 °C |
| Maximum operating altitude | 2000 m |
| Mounting | DIN rail EN 60715, or M4 screws on a mounting plate (2 Nm) |
| Mechanical durability | 50000 cycles |
| Electrical durability | 20000 cycles |
How the MO165-80 works
A magnetic release reacts to high current without delay. When the current exceeds the fixed setting of 1120 A the device opens all three poles, and a separate window indicates that it has tripped on a short circuit. The rotary handle gives a clear switch-position indication, can be locked against unauthorised changes, and provides a disconnect function in line with IEC/EN 60947-2. The trip-free mechanism means the contacts open even if the handle is held in the on position.
It has the highest fixed short-circuit setting of the range, 1120 A, and 30 kA breaking capacity at 400 V. As with the 73 A type, the AF combination tables in the catalogue stop at 65 A, so check the pairing in the full tables.
Selecting the MO165-80
Choose the MO165 when overload protection is provided elsewhere, typically by a thermal or electronic overload relay behind a contactor, or by a variable speed drive. If one device must protect against both overload and short circuit, the MS165 range with its adjustable thermal release is the alternative.
- Confirm that the motor nameplate current at the supply voltage is not above 80 A.
- Compare Ics of 30 kA at 400 V with the prospective short-circuit current at the board.
- Check the fixed 1120 A magnetic setting against the motor starting current.
- Select the contactor and overload relay for the same motor, using the catalogue combination tables.
- Choose accessories such as auxiliary contacts, signalling contacts, shunt trips or undervoltage releases.
UL and CSA ratings of the MO165-80
The catalogue gives three-phase motor ratings for North American use. At 220 to 240 V AC the MO165-80 is rated 30 hp at a full load of 80 A, and at 440 to 480 V AC it is rated 60 hp at 77 A. These figures help when machinery arrives in the Gulf with a UL-oriented control panel.
MO165 family and related ABB parts
Other types in the same frame are MO165-16, MO165-20, MO165-25, MO165-32, MO165-42, MO165-54, MO165-65, MO165-73. The adjustable counterparts with thermal protection are the MS165 types, for example MS165-80 where available. Auxiliary contacts, signalling contacts, undervoltage releases, shunt trips and power in-feed blocks are listed by the catalogue as accessories for the MO165.
| Type | Power AC-3 at 400 V | Rated current | Ics at 400 V | Short-circuit setting Ii |
|---|---|---|---|---|
| MO165-16 | 7.5 kW | 16 A | 100 kA | 240 A |
| MO165-20 | 7.5 kW | 20 A | 100 kA | 300 A |
| MO165-25 | 11 kW | 25 A | 100 kA | 375 A |
| MO165-32 | 15 kW | 32 A | 100 kA | 480 A |
| MO165-42 | 22 kW | 42 A | 50 kA | 630 A |
| MO165-54 | 22 kW | 54 A | 30 kA | 810 A |
| MO165-65 | 30 kW | 65 A | 30 kA | 975 A |
| MO165-73 | 37 kW | 73 A | 30 kA | 1022 A |
| MO165-80 | 45 kW | 80 A | 30 kA | 1120 A |
Installation and maintenance
- Snap onto a 35 mm DIN rail or fix with M4 screws at 2 Nm.
- Keep 150 mm vertical clearance to other units of the same type; side-by-side mounting needs 0 mm up to 400 V.
- Open mounting is rated -25 to +60 °C; there is no ambient compensation because there is no thermal element.
- Operate the handle periodically and check terminal tightness after the first weeks of service.
- Vibration resistance is 5 g from 3 to 150 Hz and shock resistance is 25 g for 11 ms.
Heat, dust and humidity are the main stresses for panels in Oman and the GCC, so mount the starter in a ventilated enclosure and keep the upper limit of 60 °C in view when sizing the panel.
Typical applications in Oman and the GCC
Magnetic-only starters of this size are used in motor feeders for desalination and water-treatment pumps, district cooling fans, compressors and conveyors, and in oil and gas and petrochemical auxiliaries where the contactor and overload relay are separate and the manual device provides local isolation and short-circuit protection. Combined with a drive or soft starter, it also serves as a local disconnect with fault protection.
Information to send with an RFQ
- Motor nameplate power, current and supply voltage.
- Prospective short-circuit current at the board and supply frequency.
- Overload relay or drive type used downstream.
- Required accessories and contactor pairing.
- Quantity and delivery location in Oman or the GCC.
Documents and quotation
A catalogue extract with the MO165 technical data is attached on this page. Send the part number MO165-80 and the motor data and we will confirm availability and delivery.
Seven Star LLC supplies industrial electrical products in Oman and the GCC and can quote MO165-80 together with matching accessories.
Other Models in the Abb Mo165 Manual Motor Starter Range
Seven Star LLC supplies models from the Abb Mo165 Manual Motor Starter range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| ABB MO165-16 Magnetic Manual Motor Starter 16 A | Contactors & Overload Relays | View details |
| ABB MO165-20 Magnetic Manual Motor Starter 20 A | Contactors & Overload Relays | View details |
| ABB MO165-25 Magnetic Manual Motor Starter 25 A | Contactors & Overload Relays | View details |
| ABB MO165-32 Magnetic Manual Motor Starter 32 A | Contactors & Overload Relays | View details |
| ABB MO165-42 Magnetic Manual Motor Starter 42 A | Contactors & Overload Relays | View details |
| ABB MO165-54 Magnetic Manual Motor Starter 54 A | Contactors & Overload Relays | View details |
| ABB MO165-65 Magnetic Manual Motor Starter 65 A | Contactors & Overload Relays | View details |
| ABB MO165-73 Magnetic Manual Motor Starter 73 A | Contactors & Overload Relays | View details |
| ABB MO165-80 Magnetic Manual Motor Starter 80 A | Contactors & Overload Relays | You are viewing this model |
Datasheets & Documents
- Catalog ABB MO165-80 Catalogue Extract Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.
ABB company profile
| Formed | 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50% |
|---|---|
| ASEA | Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators |
| Brown, Boveri & Cie | Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri |
| Headquarters | Zurich, Switzerland; ABB Ltd became the group holding company in 1999 |
| Ownership | Public company listed on SIX Swiss Exchange and Nasdaq Stockholm |
| Brands in the group | Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers |
| Product families | Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots |
Milestones
- 1883: ASEA is founded in Västerås, Sweden.
- 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
- 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
- 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
- 2011 and 2017: Baldor Electric and B&R join ABB.
- 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.
Choosing an ABB drive
ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.
Where ABB products are used
In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.
ABB products we list
| Family | Examples |
|---|---|
| AC drives | ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module |
| Breakers, motor control and protection | SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay |
| Flow measurement | ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500 |
| Pressure, temperature and level | 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge |
| Analysers | Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210 |
| Control systems and actuators | AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000 |
Ordering ABB products: what we need
Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.
Frequently requested ABB models: ABB FENA-21 Two-Port Ethernet Adapter Module, ABB AHM550.
Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.
FAQ
Questions about the ABB MO165-80 Magnetic Manual Motor Starter 80 A
Answers from our engineering team on installation, compatibility and integration.
01What is the MO165-80 used for?
The MO165-80 is a magnetic-only manual motor starter that gives short-circuit protection and a manual disconnect for a motor up to 80 A. Overload protection must come from a separate relay.
02What is the difference between MO165 and MS165?
The MO165 has only a magnetic release, while the MS165 adds an adjustable thermal release and phase-loss sensitivity. The MO165 therefore needs a separate overload device.
03What is the breaking capacity of the MO165-80?
At 400 V AC the catalogue lists Ics 30 kA and Icu 30 kA for this type. Compare these with the prospective fault level at the installation.
04What is the short-circuit trip setting of the MO165-80?
The magnetic release is fixed at 1120 A. Check it against the motor starting current when commissioning high-inertia loads.
05Which motor power does the MO165-80 match?
The catalogue lists 45 kW at 400 V in category AC-3. The nameplate current of the motor must not exceed 80 A.