The Lovato HS1B6NT040D024 is a single-phase solid state relay with zero-crossing switching, a rated resistive current of 40 A and an operating voltage of 24 to 600 V AC. It is controlled with 3.5 to 32 V DC and has 4000 V isolation between input and output. Seven Star LLC supplies the HS1B6NT040D024 in Oman and the GCC as an independent supplier in Muscat.

The designation carries the main data: HS1B is the relay family, 6 the 600 V class, NT part of the type code, 040 the 40 A rating and D024 the DC control range around 24 V. The HS1B6NT040E230 is the version with a different control-voltage code and the HS1B6NT060D024 steps up to 60 A.

HS1B6NT040D024 technical specifications

Parameter Specification
Manufacturer / part number Lovato / HS1B6NT040D024
Type Single-phase solid state relay
Control voltage 3.5 to 32 V DC; pick-up 3.5 V; drop-out 2 V
Input current 10 to 13 mA
Output SCR; zero-crossing
Operating voltage 24 to 600 V AC; blocking voltage 1200 V
Frequency 45 to 65 Hz
Rated current AC-51 40 A at 40 °C; 35 A at 55 °C
Minimum load current 0.05 A
Surge current (10 ms) 500 A; I²t 1250 A²s
Voltage drop on state 1.5 V
Off-state leakage 1 mA
dv/dt 500 V/μs
Isolation 4000 V input to output and to base
Heatsink for rated current 0.9 K/W or less
Terminals Control M4, load M5; load 1.5 to 6 mm²; 2 to 3 Nm
Temperature -40 to +90 °C; storage -40 to +100 °C
Protection IP20; TVS output protection

Why the HS1B6NT040D024 needs a heatsink

The voltage drop of 1.5 V across the SCR output at 40 A gives a loss of about 60 W, all of which appears as heat in the relay. Without a heatsink the device would overheat within minutes. The data sheet states that a heatsink with thermal resistance of 0.9 K/W or better is required for the rated 40 A at 40 °C or 35 A at 55 °C, and a larger sink or forced air is needed in hot panels.

The thermal resistance from junction to case is 0.55 K/W, which helps the heat to flow into the base plate. Apply thermal paste between the relay base and the heatsink and tighten evenly, since poor contact is a leading cause of early failure.

Zero-crossing switching with the HS1B6NT040D024

The relay turns on only when the AC voltage passes near zero, and turns off when the current passes near zero. This minimises electrical noise and inrush for resistive loads such as heaters. It is unsuitable for phase-angle control, and for inductive loads like motors or transformers the surge rating and a suitable snubber should be checked, since the SCR can see high dv/dt and current peaks.

Applications and cautions for the HS1B6NT040D024

The relay is intended for heating elements, ovens, extruder zones, and other resistive loads switched frequently by a PLC or temperature controller. The DC control of 3.5 to 32 V allows direct connection to a PLC transistor output. Because a solid state relay leaks 1 mA when off, a lamp or sensitive load may glow or remain energised, and a series fuse or high-speed semiconductor fuse should protect the SCR against short circuit using the I2t value.

HS1B6NT040D024 selection checklist

  • Resistive load current below 40 A at temperature
  • Load voltage between 24 and 600 V AC
  • PLC or controller output between 3.5 and 32 V DC
  • Heatsink sized for the actual current and ambient
  • Semiconductor fuse chosen against I2t of 1250 A2s
  • Load type: resistive, not inductive
  • Wire size on M4 and M5 terminals

Installing the HS1B6NT040D024

Mount the relay on a flat heatsink with thermal compound and the specified torque. Connect control at the M4 terminals and the load at the M5 terminals, tightening to 2 to 3 Nm at the power terminals. Leave space above and below the heatsink for airflow.

Check heat in service: a heatsink that is too hot to hold indicates insufficient size. Inspect for dust build-up, as heavy deposits reduce cooling, a typical problem at sites near desert dust or workshops.

Typical HS1B6NT040D024 applications in Oman and the GCC

Heaters in packaging and plastic machines, oven control, tank heating, and trace heating are the main uses. In hot panels the derating to 35 A at 55 °C must be observed, and forced ventilation extends life.

HS1B relays in the catalogue

Part Current Control
HS1B6NT040D024 40 A 3.5-32 V DC
HS1B6NT040E230 40 A Different control-voltage code
HS1B6NT060D024 60 A 3.5-32 V DC
HS1B6NT090D024 90 A 3.5-32 V DC

Failure modes are worth knowing. A shorted SCR leaves the load permanently on, which is why a safety thermostat or a separate contactor in series is standard on heating systems. An open-circuit failure usually follows overheating or a surge beyond the rating. Both are avoided by correct heatsink sizing, thermal paste and a semiconductor fuse. If the panel is hot, measure the heatsink temperature at full load and compare it with the datasheet curve rather than trusting the nominal 40 A figure, since ambient rises and dust deposits reduce capacity during the year.

Information to send with an RFQ for the HS1B6NT040D024

  • Part number HS1B6NT040D024 and quantity
  • Load type, voltage and current
  • Control signal
  • Heatsink needs
  • Ambient temperature
  • Delivery location

Documents and quotation

The official Lovato Electric datasheet for the Lovato HS1B6NT040D024 single-phase hockey-puck solid state relay (English) is attached on this page as a PDF. It gives the 40 A load rating, the 3.5-32 V DC control input, the zero-crossing switching mode, the off-state leakage, the thermal resistance needed to size the heatsink, the screw terminal data and the dimensions. Check the load current, the line voltage and the heatsink arrangement for your panel, then send us the quantity and the delivery location for a quotation.

Seven Star LLC is an independent supplier in Muscat and is not an official channel of the manufacturer. Share the quantity, delivery location and project reference with the request and we will answer with a formal quotation.

Datasheets & Documents
  • PDF Datasheet Lovato HS1B6NT040D024 Datasheet (PDF) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.

Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.

Lovato Electric at a glance

Established 1922, Bergamo, Italy
Headquarters Gorle (Bergamo), Italy
Ownership Private, family-run for four generations
Product families Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs

Lovato products we list

Family Models Typical use
Contactors BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing Switching motors, heaters, lighting and capacitor banks
Motor protection and starters SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay Short-circuit and overload protection and direct starting of motors
Soft starters ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 Reducing starting current and mechanical shock on pumps, fans and compressors
Variable speed drives VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 Speed control of pumps, fans and conveyors to save energy
Power management and control DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC Power factor correction, mains/generator changeover and energy monitoring

Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.

Where Lovato products are used

In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.

Ordering Lovato products: what we need

Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.

Facts checked against Lovato Electric company profile brochures, October 2026.

FAQ

Questions about the Lovato HS1B6NT040D024 Solid State Relay 40 A,

Answers from our engineering team on installation, compatibility and integration.

01What current does the HS1B6NT040D024 switch?
40 A resistive (AC-51) at 40 degrees C and 35 A at 55 degrees C, with a suitable heatsink.
02What control voltage is needed?
3.5 to 32 V DC, with 10 to 13 mA input current.
03Is it zero-crossing?
Yes, the switching mode is zero crossing.
04What heatsink is required?
A heatsink of 0.9 K/W or lower for the rated current.
05What isolation does it provide?
4000 V between input and output and between output and metal base.