Lovato PSL1M06024 Power Supply 24 V DC 2.5 A 60 W

Description

Lovato PSL1M06024 DIN rail power supply, 24 V DC 2.5 A 60 W

The Lovato PSL1M06024 is a single-phase switching power supply for DIN rail mounting that converts a 100 to 240 V AC mains into a 24 V DC output at 2.5 A, equal to 60 W. The output is trimmable from 24 to 28 V DC, the unit works down to -40 °C, and it occupies four DIN modules. Seven Star LLC supplies the PSL1M06024 in Oman and the GCC as an independent supplier in Muscat.

Read the code as PSL1M (family of modular supplies), 060 (60 W) and 24 (24 V output). The larger sibling PSL1M10024 delivers 4.2 A and 100 W, so the code number tells you the power rating directly.

PSL1M06024 technical specifications

Parameter Specification
Manufacturer / part number Lovato / PSL1M06024
Input Single-phase, 100 to 240 V AC (90 to 264 V); DC 120 to 375 V
Frequency 47 to 63 Hz
Input current 1.5 A maximum
Internal fuse T2A 250 V AC
Output 24 V DC, 2.5 A, 60 W
Voltage trimming 24 to 28 V DC by potentiometer
Efficiency 86%
Line / load regulation ±1% / ±1%
Ripple and noise 50 mV
Overload protection 110 to 150%
Short-circuit protection Fold forward
PFC No
Parallel connection Not allowed
Isolation input/output 3000 V AC; 4242 V DC
Operating temperature -40 to +71 °C; derating 2.5%/°C above 56 °C
Indication Power-on LED; low-voltage LED
Housing Plastic, 4 modules, IP20; 71 x 96 x 56.2 mm; 311 g

Why the derating curve matters for the PSL1M06024

The unit is specified to +71 °C but it can deliver full power only up to 56 °C; above that the available output falls by 2.5 percent per degree. At 71 °C the supply can therefore deliver only about 62 percent of its rated power, or roughly 37 W. In an unventilated panel in the Gulf, where interior temperatures of 55 to 65 °C occur in summer, that derating is often the real limit, not the nameplate figure.

The efficiency of 86 percent means around 10 W is lost as heat at full load, and the supply sits in a closed cabinet with other equipment. Leave free space above and below the housing, as in the installation instructions, and mount it vertically on the DIN rail.

Features and protections of the PSL1M06024

A fold-forward short-circuit protection means the supply keeps working with a reduced output rather than latching off; overload is limited between 110 and 150 percent of rated current. The output trim lets you compensate for voltage drop in long 24 V cable runs by raising the output towards 28 V. Two LEDs show that the output is present and when it falls too low. Parallel connection is not permitted, so redundancy needs separate supplies with decoupling diodes in a redundancy module, not direct paralleling.

Where the PSL1M06024 fits

Typical loads are PLC logic, small relays, sensors and indicator lamps: the Lovato micro PLCs LRD12RD024 and LRK12RD024 draw only a few hundred milliamperes at 24 V DC, so one 60 W unit can feed a small control panel with margin. For larger loads, the PSL1M10024 offers 100 W in five modules and further PSL ranges extend upward.

PSL1M06024 selection and ordering checklist

  • Total 24 V DC load current, plus 20 to 30 percent margin
  • Highest panel temperature, then apply derating above 56 °C
  • Input voltage range at site, including the DC input option 120 to 375 V
  • Need for redundancy; parallel connection is not available
  • Voltage drop in the 24 V wiring and the need for trimming
  • Four DIN modules of space and a vertical mounting position

Installation and maintenance of the PSL1M06024

Connect the mains through a 2 A class protective device or breaker upstream, and take the 24 V output to a distribution terminal. Set the trimmer with a multimeter at the load, not at the supply, to include cable drop. In maintenance, check the hot spots with a thermal camera, since heat is what ends the life of switch-mode supplies, and replace units that run hot in panels with filtered ventilation.

Typical PSL1M06024 applications in Oman and the GCC

The supply feeds control cabinets for pumping stations, water treatment skids, HVAC controls, small packaged plants and telemetry. Where the mains supply is unstable, a brief dip will not be covered by the PSL1M06024 because there is no holdup guarantee quoted in the sheet, so critical loads should be buffered with a UPS or battery module.

Sizing the 24 V load for the PSL1M06024

A worked example shows how quickly 60 W is used. A small PLC with expansion may draw 6 W, ten 24 V proximity sensors 3 W, a dozen interposing relay coils 12 W and a few indicator lamps 2 W, giving about 23 W. That leaves a comfortable margin, and even a hot panel at 65 °C, where about 45 W is available after derating, remains safe. The same panel with a 24 V solenoid valve manifold would exceed the limit, which is the point to move up to the 100 W model or add a second supply for the field devices.

Keep 24 V wiring short and sized for the current. At 2.5 A, a long run of 0.75 mm² cable can lose more than a volt, which is where the output trimmer is useful.

PSL1M family comparison

Part Output Power Efficiency Modules
PSL1M06024 24 V, 2.5 A 60 W 86% 4
PSL1M10024 24 V, 4.2 A 100 W 89% 5

Information to send with an RFQ for the PSL1M06024

  • Part number PSL1M06024 and quantity
  • Load current and voltage
  • Input supply voltage and frequency
  • Maximum panel temperature
  • Mounting and space constraints
  • Delivery location

Documents and quotation

Send the part number PSL1M06024 and we will confirm the documents available for it, such as the technical data sheet, wiring diagram and instruction sheet, together with availability and lead time.

Seven Star LLC is an independent supplier in Muscat and is not an official channel of the manufacturer. Share the quantity, delivery location and project reference with the request and we will answer with a formal quotation.

Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.

Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.

Lovato Electric at a glance

Established 1922, Bergamo, Italy
Headquarters Gorle (Bergamo), Italy
Ownership Private, family-run for four generations
Product families Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs

Lovato products we list

Family Models Typical use
Contactors BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing Switching motors, heaters, lighting and capacitor banks
Motor protection and starters SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay Short-circuit and overload protection and direct starting of motors
Soft starters ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 Reducing starting current and mechanical shock on pumps, fans and compressors
Variable speed drives VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 Speed control of pumps, fans and conveyors to save energy
Power management and control DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC Power factor correction, mains/generator changeover and energy monitoring

Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.

Where Lovato products are used

In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.

Ordering Lovato products: what we need

Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.

Facts checked against Lovato Electric company profile brochures, October 2026.

FAQ

Questions about the Lovato PSL1M06024 Power Supply 24 V DC 2.5 A 60 W

Answers from our engineering team on installation, compatibility and integration.

01What output does the PSL1M06024 provide?
24 V DC at 2.5 A, 60 W, adjustable from 24 to 28 V DC.
02What input voltage range does it accept?
100 to 240 V AC single-phase, operating from 90 to 264 V AC, and also 120 to 375 V DC.
03Can PSL1M06024 units be paralleled?
No, parallel connection is not allowed.
04At what temperature does it derate?
Above 56 °C the output derates by 2.5% per degree, up to the 71 °C maximum.
05What protections does it have?
Overload limiting between 110 and 150%, fold-forward short-circuit protection and an input fuse.