Brand: Lovato Electric
Lovato VLB30015A480 Variable Speed Drive 1.5 kW 400-480 V
Description
Lovato VLB30015A480 variable speed drive, 1.5 kW, 400-480 V
The Lovato VLB30015A480 is a three-phase variable speed drive from the VLB3 series, rated 1.5 kW (2 HP heavy load) with a rated output current of 3.9 A and a supply of 400 to 480 V AC. It has a built-in category C2 EMC filter, a brake chopper and an RS485 Modbus-RTU port. Seven Star LLC supplies the VLB30015A480 in Oman and the GCC as an independent supplier in Muscat.
The code reads as VLB3 for the three-phase drive series, 0015 for 1.5 kW, A for the standard version and 480 for the 400 to 480 V class. In the same family the VLB30004A480 and VLB30007A480 sit below it, the VLB30022A480 above it, and larger models continue up the range.
VLB30015A480 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Lovato / VLB30015A480 |
| Supply | Three-phase 400 to 480 V AC (340 to 528 V); 50/60 Hz |
| Output | Three-phase 0 to 480 V; 0 to 599 Hz |
| Rated output current / power | 3.9 A / 1.5 kW (2 HP heavy load) |
| Overload | 150 percent for 60 s; 200 percent for 3 s |
| Mains current | 5.4 A without choke; 3.7 A with choke |
| EMC filter | Built-in, category C2 |
| Brake chopper | Yes |
| Switching frequency | 2 to 16 kHz |
| Control modes | V/f linear and quadratic, sensorless vector, ECO, multipoint V/f, torque, closed loop with encoder |
| I/O | 5 digital inputs; relay and digital output; 2 analogue inputs; 1 analogue output |
| Communication | RS485 Modbus-RTU |
| Safety | STO optional; PTC input |
| Temperature | -10 to +55 °C; derating above 45 °C at 2.5 percent per degree (4 kHz) |
| Humidity and altitude | 5 to 95 percent; 4000 m (derate 5 percent per 1000 m over 1000 m) |
| Size and weight | 60 x 278 x 130 mm; 1.38 kg; IP20 |
How the VLB30015A480 controls a motor
The drive rectifies the mains supply to a DC bus and then creates a three-phase output of variable voltage and frequency with a power inverter. By changing frequency from 0 to 599 Hz, it changes motor speed; by shaping the voltage it controls torque. Control modes range from simple V/f for fans and pumps to sensorless vector and encoder feedback for demanding loads.
Pump and fan applications benefit from the PID function with sleep and rinse, and from multi-pump control in which one pump is frequency regulated and up to two auxiliary pumps start directly when more flow is needed. A sequencer provides programmable cycles, and 15 preset speeds can be selected from the digital inputs.
Protections and EMC of the VLB30015A480
Protections include output short circuit and earth fault, overcurrent, overvoltage and undervoltage, phase loss, motor overload by an I2t model, overspeed and speed reversal. A PTC probe input monitors motor temperature. The built-in C2 filter reduces radio-frequency emissions, with maximum shielded motor cable lengths of 20 m for category C2, 35 m for C3, and 50 or 100 m without a stated category depending on conditions.
Power and mains choke considerations for the VLB30015A480
The mains current is 5.4 A without a mains choke and 3.7 A with one, so a choke reduces harmonics and the required supply capacity. Heat loss is 48 W at 4 kHz under heavy load. For a motor of 1.5 kW the fuse and cable should be selected from the manual, using the higher current if no choke is fitted.
VLB30015A480 selection checklist
- Motor nameplate current below 3.9 A and 400 V class
- Heavy or normal duty and overload requirement
- Cable length and EMC category required
- Fitting of mains choke and brake resistor
- Control signals: analogue, digital, Modbus
- Safe torque off requirement
- Ambient temperature and derating
Installing and commissioning the VLB30015A480
Mount vertically in a panel with free space for air flow, wire power with shielded motor cable, connect the screen at both ends and keep it away from signal cables. Set motor nameplate parameters, follow the commissioning steps in the manual (the data sheet lists autotuning as not available) and test direction of rotation without load.
Record parameters after commissioning. If the drive trips on overvoltage during stopping, extend the deceleration time or add a brake resistor to the chopper output.
Typical VLB30015A480 applications in Oman and the GCC
Small drives of this class run fans in HVAC units, dosing and circulation pumps, conveyors, and mixers. Since the drive derates above 45 °C, panels in warm rooms should be ventilated, and altitude derating can be ignored at coastal sites.
VLB3 drives in the catalogue
| Part | Power | Note |
|---|---|---|
| VLB30004A480 | Smaller | Lower power |
| VLB30007A480 | Smaller | Lower power |
| VLB30015A480 | 1.5 kW | This part |
| VLB30022A480 | Larger | Higher power |
Plan the supporting equipment together with the drive. A line fuse or breaker, a mains choke if harmonics are a concern, a brake resistor on applications with fast stops or overhauling loads, and a shielded cable with proper glands make up a complete installation. Keep the drive away from heat sources and out of direct dust, and clean filters in the panel regularly. For pumps, enable the sleep function so that the drive stops when demand is very low, saving energy and avoiding unnecessary wear on the motor and seals.
Information to send with an RFQ for the VLB30015A480
- Part number VLB30015A480 and quantity
- Motor data
- Load type and speed range
- Control interface
- Options such as choke and brake resistor
- Delivery location
Site conditions in Oman for the VLB30015A480
Electrical rooms and outdoor panels in the Gulf often operate well above the 25 °C reference temperature used in many catalogues. Before you finalise the VLB30015A480, compare the expected panel temperature with the operating range and any output derating stated in the manufacturer documentation, and leave the recommended clearance above and below the device for convection. Supply quality also varies between sites, so confirm the input voltage range, frequency and any requirements for protection on the supply side.
Where the device feeds or monitors critical loads, plan how faults will be signalled to the control system and how a replacement can be installed quickly. Keeping one spare VLB30015A480 per site and recording its settings helps maintenance teams in Oman restore service with minimum downtime.
Documents and quotation
Send the part number VLB30015A480 and we will confirm the documents available for it, such as the technical data sheet, wiring diagram and instruction sheet, together with availability and lead time.
Seven Star LLC is an independent supplier in Muscat and is not an official channel of the manufacturer. Share the quantity, delivery location and project reference with the request and we will answer with a formal quotation.
Other Models in the Lovato Vlb3 Drive Range
Seven Star LLC supplies models from the Lovato Vlb3 Drive range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Lovato VLB30040A480 AC Drive 4 kW, 400-480 V, C2 EMC Filter | AC Drives | View details |
| Lovato VLB30015A480 Variable Speed Drive 1.5 kW 400-480 V | Power Modules | You are viewing this model |
Datasheets & Documents
- Datasheet Lovato VLB30015A480 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.
Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.
Lovato Electric at a glance
| Established | 1922, Bergamo, Italy |
|---|---|
| Headquarters | Gorle (Bergamo), Italy |
| Ownership | Private, family-run for four generations |
| Product families | Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs |
Lovato products we list
| Family | Models | Typical use |
|---|---|---|
| Contactors | BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing | Switching motors, heaters, lighting and capacitor banks |
| Motor protection and starters | SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay | Short-circuit and overload protection and direct starting of motors |
| Soft starters | ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 | Reducing starting current and mechanical shock on pumps, fans and compressors |
| Variable speed drives | VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 | Speed control of pumps, fans and conveyors to save energy |
| Power management and control | DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC | Power factor correction, mains/generator changeover and energy monitoring |
Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.
Where Lovato products are used
In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.
Ordering Lovato products: what we need
Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.
Facts checked against Lovato Electric company profile brochures, October 2026.
Browse Lovato Electric products by category: Motor Soft Starters, Automation Accessories, Controllers & Data Acquisition, PLC & I/O Cards, Circuit Breakers, Diesel Generator Spare Parts.
FAQ
Questions about the Lovato VLB30015A480 Variable Speed Drive 1.5 kW
Answers from our engineering team on installation, compatibility and integration.
01What is the power rating of the VLB30015A480?
1.5 kW with a rated output current of 3.9 A, equal to 2 HP at heavy load.
02What supply does it use?
Three-phase 400 to 480 V AC, 50 or 60 Hz, operating range 340 to 528 V.
03Does it have an EMC filter?
Yes, a built-in category C2 filter.
04What communication does it provide?
An RS485 port with Modbus-RTU.
05What overload can it deliver?
150 percent for 60 seconds and 200 percent for 3 seconds.