Siemens 6EP1434-2BA20 SITOP PSU300S 24V/10A Power Supply
Description
6EP1434-2BA20: SITOP PSU300S 24 V / 10 A stabilized power supply, explained
The Siemens 6EP1434-2BA20 is the three-phase member of the SITOP smart line, taking 400 – 500 V three-phase mains. It is the 24 V DC, 10 A version in the catalog. Rated 10 A, this unit is 70 mm wide and weighs about 0.7 kg, with 91 % efficiency and a mains buffering time of 6 ms at 400 V. It is the typical choice for a three-phase cabinet with a mid-size PLC and field devices.
The article number is simply the catalog identifier for this rating of the SITOP PSU300S group; it does not describe the build in a way that can be decoded digit by digit without the manufacturer’s tables, so always quote the full number 6EP1434-2BA20 when ordering. Seven Star LLC supplies the 6EP1434-2BA20 in Oman and the GCC as an independent supplier in Muscat.
Technical specifications of the 6EP1434-2BA20
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Siemens / 6EP1434-2BA20 |
| Product line | SITOP PSU300S (SITOP smart line) |
| Rated output | 24 V DC, 10 A |
| Input | 3-phase AC, rated 400 – 500 V, range 340 – 550 V |
| Input current (per phase conductor) | 0.7 A at 400 V; 0.6 A at 500 V |
| Switch-on current limit (+25 °C) | max. 20 A |
| Mains buffering at rated load | min. 6 ms; at Vin = 400 V |
| Output voltage adjustment | 24 – 28 V via potentiometer |
| Output tolerance (static) | ±3 % |
| Residual ripple (peak-peak, max.) | 200 mV |
| Efficiency at rated load, approx. | 91 % |
| Power loss at rated load, approx. | 23 W |
| Start-up delay, max. | 1.5 s |
| Short-circuit / overload response | Constant-current characteristic (current limit about 13 A) |
| Parallel operation for more power | Yes |
| Signalling output | Relay contact (normally open, 60 V DC/0.3 A) for the output-voltage-OK message |
| Protection class | Class I |
| Approvals listed | cULus listed (UL 508, CSA C22.2 No. 107.1); CB |
| Hazardous-area listings | IECEx / ATEX category 3G (Ex nA) and cCSAus Class I Div. 2 listings appear in the catalog for this series; confirm the marking and temperature class on the exact unit |
| Ambient temperature (operation) | −25 – +70 °C, natural convection |
| Derating note (catalog) | 12 A up to +45 °C |
| Humidity class | Climate class 3K3, no condensation |
| EMC | Emissions EN 55022 Class B; noise immunity EN 61000-6-2 |
| Degree of protection | IP20 |
| Dimensions (W × H × D) | 70 × 125 × 120 mm |
| Weight, approx. | 0.7 kg |
| Mounting | Snap-on to DIN rail EN 60715 35 × 7.5/15; side-by-side mounting permitted |
Values are taken from the manufacturer’s SITOP catalog (KT 10.1, 2016) and apply at rated input voltage and +25 °C unless stated otherwise; check the current data sheet of the exact unit before design freeze.
How the 6EP1434-2BA20 regulates and protects its 24 V output
The 6EP1434-2BA20 operates from three-phase 400 – 500 V mains (tolerance 340 – 550 V), which spreads the load across all three phases and keeps the input current low: 0.7 A per conductor at 400 V. It regulates the 24 V output with a switch-mode converter and offers an adjustable output (24 – 28 V) plus a relay contact for the 24 V OK message.
Mains buffering is 6 ms at 400 V, and short circuits are handled by a constant-current characteristic (current limit about 13 A). The unit carries no built-in input fuse, so the feeder breaker is the protective device and must be a 3-pole miniature circuit breaker with characteristic C.
Where the 6EP1434-2BA20 fits in the control system
In a typical cabinet the 6EP1434-2BA20 sits right behind the incoming breaker and feeds a 24 V distribution rail. Other members of the SITOP PSU300S group in the catalog are 6EP1433-2BA20, 6EP1436-2BA10, 6EP1437-2BA20; they share the same operating concept but differ in rated current, width and weight, so they are not interchangeable in a fixed layout without checking space and breaker coordination.
For this series the catalog lists the SITOP PSE201U buffer module 6EP1961-3BA01, the PSE202U redundancy modules (6EP1961-3BA21, 6EP1962-2BA00, 6EP1964-2BA00), the PSE200U selectivity modules in 3 A and 10 A versions and device labeling plates 3RT1900-1SB20.
As an independent supplier, Seven Star LLC can help you match the supply to the rest of the bill of materials, for example by checking that the redundancy or buffer module suits the output current, but the final electrical design remains with your engineering team.
Selection and ordering checklist for the 6EP1434-2BA20
- Load current: add the continuous demand of all 24 V consumers and compare it with the 10 A rating of the 6EP1434-2BA20, leaving margin for inrush and future additions.
- Mains: confirm that the site supply matches the input data (3-phase AC, rated 400 – 500 V, range 340 – 550 V) and check the input current figures given in the specification table.
- Cabinet temperature: the operating range is -25 – +70 °C and derating applies at the upper end; compare it with the worst-case temperature inside the enclosure.
- Space: allow 70 mm width on the rail plus 125 mm of height and 120 mm of depth; vertical clearance for convection is required.
- Protection: the catalog requires a 3-pole connected miniature circuit breaker of 3 – 16 A, characteristic C, on the three-phase input.
- Signalling: decide whether the relay contact will be wired to your monitoring system.
- Add-ons: decide early whether a redundancy, buffer or selectivity module is needed; the catalog lists compatible modules for the series.
- Use it for loads up to 10 A; the catalog quotes 12 A up to +45 °C and a current limit near 13 A with a constant-current characteristic.
Installation, commissioning and maintenance
Mount the 6EP1434-2BA20 on a 35 mm DIN rail with free vertical clearance. Wire L1, L2, L3 and PE with the screw terminals, then the output and the signalling contact; protect the feeder with the required 3-pole breaker, as the unit has no built-in fuse.
On commissioning, confirm phase presence and that the 24 V OK relay closes. Because the unit dissipates about 23 W at full load, check the cabinet temperature under real load and confirm that natural convection is sufficient.
Protect the three-phase feeder with a 3-pole breaker as stated in the catalog (3 – 16 A, characteristic C), and keep the rated clearances above and below.
- Inspect terminals for tightness and discolouration at each shutdown.
- Clean dust from the vents with dry compressed air; do not block the convection path.
- Compare the output voltage with the value recorded at commissioning.
- Keep one spare of the same article number for critical cabinets, since lead times for individual SITOP models can vary.
Typical applications in Oman and the GCC
In Oman and the GCC, the 6EP1434-2BA20 suits three-phase panels in pumping stations, compressor houses, desalination plants and industrial workshops, where a 400 V three-phase feeder is already present. The operating range (-25 – +70 °C) covers hot cabinets, but check ventilation in direct sun.
It fits MCC-adjacent control panels, dosing skids and mid-sized process cabinets.
SITOP PSU300S group at a glance
The table lists the SITOP PSU300S versions found in the catalog so you can compare ratings and size before selecting the 6EP1434-2BA20.
| Article number | Output | Width | Weight | Efficiency |
|---|---|---|---|---|
| 6EP1433-2BA20 | 24 V / 5 A | 50 mm | 0.5 kg | 89 % |
| 6EP1434-2BA20 | 24 V / 10 A | 70 mm | 0.7 kg | 91 % |
| 6EP1436-2BA10 | 24 V / 20 A | 90 mm | 1.6 kg | 91 % |
| 6EP1437-2BA20 | 24 V / 40 A | 150 mm | 3.7 kg | 91.5 % |
Information to send with an RFQ for the 6EP1434-2BA20
- Exact article number (6EP1434-2BA20) and quantity, including whether you need identical replacement or an equivalent.
- Supply system at site: voltage, frequency and number of phases, plus whether a DC feed is possible.
- Output requirement: voltage, continuous current, peak or inrush loads and the number of parallel units if redundancy is planned.
- Ambient conditions inside the cabinet: maximum temperature, dust, humidity and any hazardous-area classification.
- Required accessories, for example redundancy, buffer or selectivity modules, terminals or labeling plates.
- Delivery location (Muscat or elsewhere in Oman or the GCC) and required delivery time.
- Any document requirement such as a datasheet or manual in English.
Documents and quotation
Send us the part number 6EP1434-2BA20 and we will confirm which manufacturer documents are available for it. The figures on this page come from the manufacturer’s SITOP catalog and should be checked against the data sheet of the exact unit before design freeze.
Seven Star LLC is an independent supplier based in Muscat and is not affiliated with the manufacturer. To request a quotation for the 6EP1434-2BA20, send the information listed above through the request-for-quotation form or by email; we will reply with availability and lead time.
Other Models in the Siemens Sitop Psu300s Range
Seven Star LLC supplies models from the Siemens Sitop Psu300s range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Siemens 6EP1433-2BA20 SITOP PSU300S 24V/5A Power Supply | Power Modules | View details |
| Siemens 6EP1434-2BA20 SITOP PSU300S 24V/10A Power Supply | Power Modules | You are viewing this model |
Reviews (0)
How would you rate this product? Cancel reply
About brand
Siemens is the German technology group whose industrial products include SIMATIC controllers and HMIs, SINAMICS drives, SIRIUS and SENTRON switching and protection devices, SIPROTEC protection relays, SITRANS process instruments, SCALANCE networks and process analysers. It was founded in Berlin on 12 October 1847 by Werner von Siemens and the precision mechanic Johann Georg Halske as Telegraphen-Bauanstalt von Siemens & Halske, to build Siemens's newly designed pointer telegraph. Siemens AG is headquartered in Munich and listed on the Frankfurt Stock Exchange; its energy business was spun off as Siemens Energy in 2020.
Siemens company profile
| Founded | 12 October 1847, Berlin, Germany, as Telegraphen-Bauanstalt von Siemens & Halske, with 10 employees |
|---|---|
| Founders | Werner von Siemens (1816–1892) and Johann Georg Halske (1814–1890) |
| First product | The pointer telegraph designed by Werner von Siemens |
| Headquarters | Munich, Germany (Siemens AG) |
| Ownership | Public company listed in Frankfurt; Siemens Energy (2020) and Siemens Healthineers are separately listed companies |
| Businesses acquired that appear in our range | Moore Products (bought in 2000; APACS and QUADLOG control systems), Applied Automation (Maxum process gas chromatographs); small industrial gas turbines such as the SGT-300 came with Alstom's industrial turbine business in 2003 |
| Product families | SIMATIC S7 PLCs, ET 200 distributed I/O and HMI panels, TIA Portal software, SINAMICS drives, SIMOTICS motors, SIRIUS and SENTRON low voltage devices, SIVACON switchboards, SIPROTEC relays, SITRANS instruments, SCALANCE network components, building technology valves and sensors |
Milestones
- 1847: Siemens & Halske starts work in Berlin with 10 employees.
- 1848: The company wins the contract for Europe's first long-distance telegraph line, Berlin to Frankfurt am Main.
- 1856: 330 employees, two-thirds of them working on telegraph networks in Russia.
- 1866: Werner von Siemens describes the dynamo-electric principle, the basis of the electric generator.
- 1958 onwards: The SIMATIC name is used for Siemens industrial automation; S7 PLCs follow in the 1990s and S7-1500 in 2012.
- 2020: Siemens Energy is spun off and listed separately.
Choosing Siemens automation products
A Siemens order number (MLFB) identifies the exact product: 6ES7 is SIMATIC automation, 6AV is HMI, 6GK is industrial communication, 6SL is SINAMICS drives, 3R is SIRIUS control and 5SY is SENTRON miniature circuit breakers. For PLCs, S7-1200 is the compact controller for small machines, S7-1500 is the current mid-to-high range controller, and S7-300 and S7-400 are older platforms still running in many plants; S7-300 is being phased out, so spares and migration to S7-1500 are common requests. When replacing a CPU or module, the full order number including the version digits matters, because firmware and hardware versions affect compatibility with the existing project.
Where Siemens products are used
In Oman and the GCC, Siemens automation runs in oil and gas, power and desalination plants, water networks, cement and process industries. Maxum gas chromatographs analyse gas composition in gas plants and refineries, SIPROTEC relays protect substations, SGT-300 turbines drive generators and compressors, and Siemens building valves are used in HVAC systems.
Siemens products we list
| Family | Examples |
|---|---|
| SIMATIC controllers and I/O | S7-1500, CPU 1515-2 PN, S7-1200, CPU 1214C, S7-300, S7-400H CPU 412-5H, ET 200SP, IM 153-2 |
| HMI and networking | KTP700 Basic, TP700 Comfort, TP1200 Comfort, SCALANCE XC208, SCALANCE WAM766, PROFIBUS OLM |
| Drives, motors and power distribution | SINAMICS G120C, SINAMICS G120X, 1LA7 motor, SIVACON S8, SIPROTEC 7SJ85, 5SY4510-7 MCB |
| Process instruments | SITRANS P320, MAG 5100W, SITRANS TH320, SITRANS TS500, SITRANS TR200 |
| Maxum II analyser spares | FID 302A detector, FPD II assembly, filament detector, Model 50 valve, SYSCON kit, air bath heater |
| APACS and QUADLOG spares | QLCCM24AAN, QLSAMBAN, QLSDM024DCCBN, 39SAMCAN, 16137-151 M-BUS cable |
| Building technology | VPI46 PICV, VPF44, QFM1660 sensor |
Ordering Siemens products: what we need
Send the full order number from the label (for example 6ES7214-1AG40-0XB0) and, for PLC and HMI parts, the hardware and firmware version (FS and V numbers). For Maxum II and APACS spares, send the Siemens part number such as 2021651-002. For drives, add the motor power and supply voltage.
Frequently requested Siemens models: Siemens IM 155-6 PN ST ET 200SP Interface Module 6ES7155-6AU02-0BN0, Siemens SGT-300 Industrial Gas Turbine.
Facts checked against Siemens's published history timeline, October 2026.
FAQ
Questions about the Siemens 6EP1434-2BA20 SITOP PSU300S 24V/10A Power
Answers from our engineering team on installation, compatibility and integration.
01Does the 6EP1434-2BA20 need a fuse or breaker on the input?
The unit has no built-in fuse, so the catalog requires a 3-pole connected miniature circuit breaker with characteristic C on the three-phase input; see the checklist above for the range that applies to this rating.
02What ambient temperature range does the 6EP1434-2BA20 support?
The catalog gives an operating range of -25 – +70 °C with natural convection. Derating applies at the upper end, so verify the cabinet temperature under full load rather than the room temperature.
03What are the dimensions and weight of the 6EP1434-2BA20?
The enclosure measures 70 mm wide, 125 mm high and 120 mm deep and weighs about 0.7 kg. It snaps onto a 35 mm DIN rail and can be mounted side by side, but vertical clearance for convection must be kept.
04How efficient is the 6EP1434-2BA20 and how much heat does it release?
The catalog lists an efficiency of about 91 % at rated load, which corresponds to a power loss of 23 W. Include this loss in the cabinet heat balance, especially in hot desert climates.
05What input voltage does the 6EP1434-2BA20 accept?
According to the catalog it accepts 3-phase AC, rated 400 – 500 V, range 340 – 550 V. Check this against the site supply and the selector or jumper setting where the series has one, since a mismatch is the most common cause of a dead unit at commissioning.


















Reviews