Brand: Schneider Electric
Schneider Electric BMXCPS3020 Modicon X80 24-48 V DC Power
Description
BMXCPS3020 DC-powered rack power supply module
The BMXCPS3020 is a Schneider Electric product listed in the datasheet as: power supply module, Modicon X80, 24 to 48V DC, 31.2W. The BMXCPS3020 is a rack power supply module for Modicon X80 and M340 platforms, with a 24 to 48 V DC input and 31.2 W output power. It suits sites with DC distribution such as battery-backed supplies. Seven Star LLC supplies the BMXCPS3020 in Oman and the GCC as an independent supplier based in Muscat.
Reading the reference: CPS is the rack power supply, 30 the DC input class and 20 the variant. The datasheet gives 24 to 48 V DC.
Technical specifications of the BMXCPS3020
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / BMXCPS3020 |
| Description | power supply module, Modicon X80, 24 to 48V DC, 31.2W |
| Range of Product | Modicon X80 |
| Product or Component Type | Power supply module |
| backplane compatibility | Not compatible with BMEXBP..02 |
| Primary Voltage | 24 to 48 V isolated |
| Supply circuit type | DC |
| Secondary power | 15 W 3.3 V DC I/O module logic power supply; 31.2 W 24 V DC I/O module power supply and processor |
| Primary voltage limit | 18 to 62.4 V |
| Input current | 0.83 A 48 V; 1.65 A 24 V |
| Inrush current | 30 A 24 V; 60 A 48 V |
| I²t on activation | 1 A².s 24 V; 3 A².s 48 V |
| It on activation | 0.2 A.s 24 V; 0.3 A.s 48 V |
| MTBF reliability | 4600000 H |
| Protection type | Internal fuse not accessible primary circuit; Overload protection secondary circuit, 24 V sensor power supply |
| Current at secondary voltage | 1.3 A 24 V DC I/O module power supply and processor; 4.5 A 3.3 V DC I/O module logic power supply |
| Maximum power dissipation in W | 8.5 W |
| Status LED | 1 LED (Green) rack voltage OK |
| Control Type | RESET push-button cold restart |
| Electrical connection | 1 connector 2 alarm relay; 1 connector 5 line supply, protective earth |
| Maximum cable distance between | 10 m power supply cable copper 1.5 mm² |
| devices | 15 m power supply cable copper 2.5 mm² |
| Insulation resistance | >= 10 MOhm primary/ground; >= 10 MOhm primary/secondary |
| Net Weight | 0.34 kg |
| Immunity to microbreaks | 1 ms |
| Dielectric strength | 1500 V primary/ground; 1500 V primary/secondary |
| Vibration resistance | 3 gn |
| Shock resistance | 30 gn |
| IP Degree of Protection | IP20 |
| Ambient air temperature (operation or storage, as listed) | 0 to 60 °C |
| Relative humidity | 5 to 95 % 55 °C without condensation |
| Operating altitude | 0 to 2000 m; 2000 to 5000 m with derating factor |
Input and output data of the BMXCPS3020
The module feeds the rack bus. The datasheet lists the power it can deliver, and the power budget of all modules in the rack must fit within it.
Power budgeting with the BMXCPS3020
Add the consumption of the processor and all I/O modules and keep a margin. The AC supply modules, such as BMXCPS2000, are used in mains-fed racks.
Use of a DC supply simplifies backup.
Selection checklist for the BMXCPS3020
- DC input range.
- Rack budget.
- Alarm relay.
- Fuse.
- Cable.
- Space.
Wiring and check of the BMXCPS3020
Wire the DC input with correct polarity, check the output LED, and test the alarm relay.
Include in the spare plan.
Typical applications of the BMXCPS3020 in Oman and the GCC
In Oman and the GCC it suits substations and remote sites with DC supplies.
Dimensions, environment and approvals of the BMXCPS3020
The BMXCPS3020 weighs 0.34 kg. Mounting, derating and enclosure choices follow the environmental data below, which should be compared with the actual panel temperature and the dust and humidity of the site in Oman and the GCC.
Ambient temperature limits in the datasheet: 0 to 60 °C. Relative humidity: 5 to 95 % 55 °C without condensation. Ingress protection: IP20. Operating altitude: 0 to 2000 m; 2000 to 5000 m with derating factor. Vibration resistance: 3 gn. Shock resistance: 30 gn.
For a rack powered from a DC bus, the BMXCPS3020 is attractive because the processor can ride through a loss of mains if batteries are present. Calculate the power budget with the consumption of every module: the processor, communication modules, and I/O modules each draw from the rack, and the total must stay within the 31.2 W output with margin for future modules. The alarm relay of the supply can be wired to an input to signal a supply failure. Take care with polarity and with the supply range: 24 to 48 V DC covers common battery voltages, but ripple on charger outputs can exceed the allowed limit. Fuse the supply input according to the manual. When replacing the module, switch off the DC source and wait for discharge, then check that the new unit has the same variant. Keep a spare in stock, as a power supply is the module most likely to fail in a rack after years of operation.
Information to send with an RFQ for the BMXCPS3020
- Full reference and quantity required
- Existing equipment, panel or rack it must fit
- Supply voltage, load or signal details of the application
- Required delivery location and timing
- Whether a spare, a replacement or a new installation
Site conditions in Oman for the BMXCPS3020
Electrical rooms and outdoor panels in the Gulf often operate well above the 25 °C reference temperature used in many catalogues. Before you finalise the BMXCPS3020, compare the expected panel temperature with the operating range and any output derating stated in the manufacturer documentation, and leave the recommended clearance above and below the device for convection. Supply quality also varies between sites, so confirm the input voltage range, frequency and any requirements for protection on the supply side.
Where the device feeds or monitors critical loads, plan how faults will be signalled to the control system and how a replacement can be installed quickly. Keeping one spare BMXCPS3020 per site and recording its settings helps maintenance teams in Oman restore service with minimum downtime.
Documents and quotation
A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above.
Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and does not represent itself as an official channel of the manufacturer.
Other Models in the Se X80 Range
Seven Star LLC supplies models from the Se X80 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric BMXDAI1602 Modicon X80 16-Input AC/DC Module | PLC & I/O Cards | View details |
| Schneider Electric BMXCRA31200 Modicon X80 EtherNet/IP Remote | PLC & I/O Cards | View details |
| Schneider Electric BMXCPS3020 Modicon X80 24-48 V DC Power | Power Modules | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric BMXCPS3020 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric BMXCPS3020 Modicon X80 24-48 V
Answers from our engineering team on installation, compatibility and integration.
01What input voltage limits does the BMXCPS3020 list?
The datasheet gives 18 to 62.4 V.
02What input current does the BMXCPS3020 draw?
Stated as 0.83 A 48 V; 1.65 A 24 V.
03What is the net weight of the BMXCPS3020?
The datasheet gives 0.34 kg.
04What ingress protection does the BMXCPS3020 list?
Stated as IP20.
05Which product range does the BMXCPS3020 belong to?
The datasheet lists the range as Modicon X80.