Schneider Electric METSEPM5560 PowerLogic PM5560 Power Meter

Description

METSEPM5560 PowerLogic PM5560 power and energy meter with dual Ethernet

The METSEPM5560 is a Schneider Electric product listed in the datasheet as: power meter PowerLogic PM5560, 2 ethernet, up to 63th Harmonic, 1,1MB 4DI/2DO 52 alarms. The PM5560 is a panel-mounted power meter from the PowerLogic PM5000 series. It measures current, voltage, power and energy, analyses harmonics up to the 63rd, and provides two Ethernet ports plus serial communication so it can act as a gateway. Seven Star LLC supplies the METSEPM5560 in Oman and the GCC as an independent supplier based in Muscat.

Reading the reference: METSE marks the Schneider meter prefix, PM5560 the model in the PM5000 line. The datasheet title states 2 Ethernet ports, up to the 63rd harmonic, 4 digital inputs, 2 digital outputs and 52 alarms.

Technical specifications of the METSEPM5560

Parameter Specification
Manufacturer / part number Schneider Electric / METSEPM5560
Description power meter PowerLogic PM5560, 2 ethernet, up to 63th Harmonic, 1,1MB 4DI/2DO 52 alarms
Range PowerLogic
Product name PowerLogic PM5000
Product or Component Type Power meter
Device short name PM5560
Power quality analysis up to the 63rd harmonic
Metering type Measured neutral current; Calculated ground current
Device Application Gateway; WAGES metering; Power monitoring; Multi-tariff
Type of measurement Current; Voltage; Frequency; Power factor; Energy; Active and reactive power
[Us] rated supply voltage 100 to 300 V DC; 90 to 528 V AC 45 to 65 Hz
Network Frequency 60 Hz; 50 Hz
Line Rated Current 1A; 5A
type of network 3P + N; 3P; 1P + N
Maximum power consumption in 16 VA 480 V
Ride-through time 35 ms 120 V AC typical; 129 ms 230 V AC typical; 50 ms 125 V DC typical
Display Type Backlit LCD
Display Resolution 128 x 128 pixels
Sampling rate 128 samples/cycle
Measurement current 50 to 10000 mA
Analogue input type Voltage (impedance 5 MOhm); Current (impedance <= 0.3 mOhm)
Measurement voltage 20 to 400 V AC 45 to 65 Hz between phase and neutral; 20 to 828 V AC 45 to 65 Hz between phases
Frequency measurement range 45 to 65 Hz
Number of inputs 4 digital
Measurement accuracy Apparent power ± 0.5 %; Frequency ± 0.05 %; Active energy ± 0.2 %; Reactive energy ± 1 %; Active power ± 0.2 %; Voltage ± 0.1 %
Accuracy class Class 0.2S active energy IEC 62053-22
Number of Outputs 2 digital
Information displayed Tariff 8
Communication port protocol Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none – 2 wires 2500; V; JBUS; Modbus TCP/IP 10/100 Mbit/s 2500 V
Communication port support RS485; ETHERNET
Communication gateway Ethernet/serial
Data recording Event logs; Maintenance logs; Min/max of instantaneous values; Data logs; Alarm logs; Time stamping
Memory capacity 1.1 MB
Web services Alarm notification by e-mail; Diagnostic via predefined web pages; Web server; Real time viewing of data
Ethernet service SNTP client; SNMP-Traps
Connections – terminals Voltage circuit screw terminal block4; Control circuit screw terminal block2; Current transformer screw terminal block6
Mounting Mode Flush-mounted
Mounting support Framework
Standards EN 50470-3; IEC 61557-12:2015; IEC 62053-22:2020; IEC 62053-24; IEC 60529; EN 50470-1; UL 61010-1; ANSI C12.20; IEC 62053-23:2020
Product certifications CE conforming to IEC 61010-1; CULus conforming to UL 61010-1; BTL
Width 96 mm
Depth 72 mm

Measurement and power-quality functions

Power-quality analysis: up to the 63rd harmonic. Measured quantities: Current; Voltage; Frequency; Power factor; Energy; Active and reactive power. Accuracy class: Class 0.2S active energy IEC 62053-22. Accuracy: Apparent power ± 0.5 %; Frequency ± 0.05 %; Active energy ± 0.2 %; Reactive energy ± 1 %; Active power ± 0.2 %; Voltage ± 0.1 %. Sampling rate: 128 samples/cycle. Data recording: Event logs; Maintenance logs; Min/max of instantaneous values; Data logs; Alarm logs; Time stamping. Memory: 1.1 MB. Network types: 3P + N; 3P; 1P + N.

Class 0.2S for active energy is suitable for revenue-grade billing and tight verification. Harmonic analysis to the 63rd order helps find drive and rectifier distortion. Event, alarm, maintenance and min/max logs allow a post-incident look at disturbances.

Communications, web services and the place of the METSEPM5560 in a monitoring system

The meter has two Ethernet ports (as a daisy-chain or separate networks) and an RS485 serial port, with an Ethernet-to-serial gateway function. The datasheet lists web services such as e-mail alarm notification and web pages for diagnostics.

It integrates with supervisory systems by Modbus and other protocols as the datasheet lists. Related meters: PM5110 for basic monitoring, PM2110 for simpler needs.

Selection checklist for the METSEPM5560

  • Accuracy class and standard needed for billing.
  • Harmonic order required.
  • Ethernet and serial communication needs.
  • Digital inputs/outputs and alarm counts.
  • Panel cut-out and depth.
  • Current transformers and ratio planning.

Wiring, setup and commissioning of the METSEPM5560

Mount flush in a 96 x 96 mm cut-out, connect voltage inputs through fuses, wire the CT secondaries with shorting blocks, and set the CT and VT ratios and system type. Configure the network address and time sync.

Verify readings against a reference instrument, check phase sequence and CT polarity (negative power usually means a reversed CT), and set alarm thresholds.

Typical applications of the METSEPM5560 in Oman and the GCC

Main incomers, large motor feeders, generators, and data-centre or plant substations in the region. In hot switchrooms check the temperature limit of the display.

Dimensions, environment and approvals of the METSEPM5560

For the METSEPM5560, plan the mounting space from the datasheet: 96 mm (W) x 96 mm (H) x 72 mm (D). The METSEPM5560 weighs 450 g. Mounting, derating and enclosure choices follow the environmental data below, which should be compared with the actual panel temperature and the dust and humidity of the site in Oman and the GCC.

Ambient temperature limits in the datasheet: -25 to 70 °C. Relative humidity: 5 to 95 % 50 °C non-condensing. Ingress protection: IP54 display: conforming to IEC 60529; IP30 rear: conforming to IEC 60529. Operating altitude: <= 3000 m. Standards listed: EN 50470-3; IEC 61557-12:2015; IEC 62053-22:2020; IEC 62053-24; IEC 60529; EN 50470-1; UL 61010-1; ANSI C12.20; IEC 62053-23:2020. Certifications listed for this reference: CE conforming to IEC 61010-1; CULus conforming to UL 61010-1; BTL.

Information to send with an RFQ for the METSEPM5560

  • Full reference and quantity required
  • Existing equipment, panel or rack it must fit
  • Supply voltage, load or signal details of the application
  • Required delivery location and timing
  • Whether a spare, a replacement or a new installation

Documents and quotation

A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and does not represent itself as an official channel of the manufacturer.

Datasheets & Documents
  • PDF Datasheet Schneider Electric METSEPM5560 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric METSEPM5560 PowerLogic PM5560

Answers from our engineering team on installation, compatibility and integration.

01What accuracy class has the METSEPM5560?
The datasheet states Class 0.2S active energy IEC 62053-22.
02What harmonics does it analyse?
Datasheet: up to the 63rd harmonic.
03What communication ports does the METSEPM5560 have?
Listed: RS485; ETHERNET.
04What memory has the METSEPM5560?
Listed: 1.1 MB.
05What supply does it need?
The supply range is 100 to 300 V DC; 90 to 528 V AC 45 to 65 Hz.