Brand:

Danfoss 148F3211 SFA 15 Safety Relief Valve, G 3/4, 11 bar

Description

SFA 15: a spring-loaded relief valve factory set to 11 bar for refrigeration vessels

Danfoss 148F3211 is an SFA 15 safety relief valve with a G 3/4 internal inlet and a G 1 outlet to ISO 228-1, factory set to 11 bar (160 psig). The flow area is 133 mm2 (0.206 in2), the flow diameter is 13 mm and the lift is 4.8 mm; the certified coefficient of discharge is 0.73. Net weight is 1.813 kg.

The page lists a temperature range of -50 to 100 C and approvals CE, EAC, TS and UA. A Danfoss pressure certificate is included with the valve, which records the set pressure. The valve is an angleway design.

Technical specifications

Parameter Specification
Danfoss code number 148F3211
Type SFA 15
Approvals as listed CE; EAC; TS; UA
Certified Coef of Disc 0.73 kg
Connection Internal/External External
Connection size 1/2 in / 15 mm
Connection standard ISO 228-1
Connection type G
Flow area 133 mm2
Flow diameter 0.512 in / 13 mm
Inlet connection size 3/4
Lift 4.8 mm
Nominal diameter DN below 15
Outlet connection size 1
Pressure certificate Danfoss certificate included
Pressure setting 11 bar
Refrigerants R134a; R170; R22; R401A; R402A; R404A; R407A; R407B; R407C; R407F; and others listed in the data sheet
Temperature range -50 C to 100 C
Net weight 1.813 kg
EAN 5702428194150

Relief valves on refrigeration vessels

Safety relief valves protect receivers, heat exchangers, oil separators and sections of pipe that can be isolated between valves against pressure above the design limit. The set pressure of 11 bar suits a vessel designed to a maximum allowable pressure of at least that value; other settings from the same family have separate code numbers.

The SFA 15 sits above the SFA 10 in flow capacity. In the same data sheet family are SFA 10, SFA 10H and SFA 15-50 (the same body in a larger version), and DSV dual-valve combinations. The certified coefficient and the flow area are the figures that the pressure-equipment calculation uses.

Installation, sizing and ordering

Sizing of a relief valve belongs to the pressure-vessel calculation. Use the certified discharge coefficient, the vessel external fire and compressor-capacity cases and the relevant standard. The valve must discharge to a safe place; avoid back-pressure above what the installation guide permits.

Confirm the set pressure, the thread type and the certificate you need. The valve must not be re-set by the user; a changed setting voids the certificate. Install vertically with the outlet pipe supported, and test or replace valves per your inspection regime.

Other types and sizes from the same Danfoss family that appear in the Danfoss store listing include SFA 15-50 (148F4000), SFA 10 (148F4210), SFA 10H (148F4228), SFA 10/DSV (148F6313), SFA 10H/DSV (148F6328). These are listed for orientation only; each has its own datasheet values, so check size, connection and version before ordering.

Related Danfoss products: Danfoss 148B0084 SNV-ST Gauge Stop Needle Valve, G 1/2 A, Danfoss 148B5200 SVA-S 15 Shut-off Valve, 15 mm Butt Weld, Danfoss 032U7115 EV220B 15 Solenoid Valve G 1/2 NC EPDM, Danfoss 032U5254 EV250B 18 Solenoid Valve G 3/4 NC 0 bar, Danfoss 148B4823 SVA-DH 250 Shut-off Valve, 250 mm Butt Weld and Danfoss 032U3806 EV225B 20 Steam Solenoid Valve G 3/4 NC.

Documents and quotation

Attached for download: Danfoss Safety relief valve, SFA 10 / SFA 10H / SFA 15 / SFA 15-50 AI564618139338en-000101 (manufacturer, unaltered), the manufacturer’s unaltered PDF. Browse comparable products in safety relief valves. To order, send us 148F3211 and the required quantity; Seven Star LLC is an independent supplier based in Muscat.

Datasheets & Documents
  • PDF Datasheet Danfoss Safety relief valve, SFA 10 / SFA 10H / SFA 15 / SFA 15-50 AI564618139338en-000101 (manufacturer, unaltered) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Danfoss is the Danish engineering group that makes refrigeration and air-conditioning controls, heating components, variable speed drives and mobile hydraulics. Mads Clausen founded it on 1 September 1933 at his parents' farm in Nordborg on the island of Als, after making his first refrigeration expansion valve in 1932. Nordborg is still the group's headquarters, and Danfoss remains controlled by the Clausen family through the Bitten & Mads Clausen Foundation.

Danfoss company profile

Founded 1 September 1933, Nordborg, Denmark, by Mads Clausen (1905–1966)
First product Thermostatic expansion valve for refrigeration
Headquarters Nordborg, Denmark
Ownership Private; majority controlled by the Bitten & Mads Clausen Foundation and the Clausen family
Size About 42,000 employees (2023)
Business segments Danfoss Climate Solutions (refrigeration, air conditioning and heating), Danfoss Drives (VLT and VACON frequency converters, soft starters), Danfoss Power Solutions (mobile and industrial hydraulics)
Brands in the group VLT, VACON, Eaton Hydraulics (bought 2021), Ikusi radio remote controls

Milestones

  • 1932–1933: First expansion valve; the company is founded in Nordborg.
  • 1939: 26 employees. By the 10th anniversary in 1943 the company has 179.
  • 1950s: Rapid growth turns Nordborg into a Danfoss town with housing and schools for its workforce.
  • 1968: Danfoss launches its VLT frequency converter, one of the first mass-produced AC drives.
  • 2014: Acquisition of the Finnish drives maker Vacon, now the VACON brand.
  • 2021: Acquisition of Eaton's hydraulics business.

Choosing Danfoss products

For solenoid valves, check the operating principle. A direct-operated valve such as EV210B opens even at 0 bar differential pressure. A servo-operated valve such as EV220B needs a minimum differential (typically about 0.3 bar) to open, while an assisted-lift valve such as EV250B works from 0 bar. Coils are ordered separately, so the voltage on the coil (for example 230 V AC or 24 V DC) must match the control circuit. For drives, the VLT family is split by application: FC 51 Micro Drive for small machines, FC 102 HVAC Drive for fans and pumps in buildings, FC 202 AQUA Drive for water, and FC 302 AutomationDrive for demanding industrial duty.

Where Danfoss products are used

In Oman and the GCC, Danfoss drives run pumps, fans and compressors in district cooling plants, water and wastewater stations, desalination and building HVAC. Danfoss pressure switches, transmitters and solenoid valves are built into chillers, refrigeration plants, boilers and hydraulic systems, and AB-QM valves balance chilled-water circuits in large buildings.

Danfoss products we list

Family Examples
Variable speed drives and soft starters VLT Micro Drive FC 51, VLT HVAC Drive FC 102, VLT AQUA Drive FC 202, VLT AutomationDrive FC 302, FC 280, iC2-Micro, VACON NXP, MCD 600 soft starter
Solenoid valves and coils EV220B, EV210B, EV250B, EV225B steam, EVR 25, AM230C coil
Pressure switches and thermostats KP 37, KP 44, RT 200, CS, MBC 5000, KPS 77, RT 101
Pressure transmitters MBS 3000, MBS 5100, MBS 3250, MBS 4251 Ex, AKS 33, DST P92S SIL 2
HVAC and refrigeration valves AB-QM PICV, NovoCon S, AB-PM, AVTA, ICV, TE 5 element

Ordering Danfoss products: what we need

Send the Danfoss code number from the label (for example 032U7115 or 131B0149) or the full drive type code (FC-302P3K0T5...). For drives, add the motor power, supply voltage and any fieldbus option. For valves, add the size, connection, medium and coil voltage. For pressure switches and transmitters, add the range, output and pressure connection.

Facts checked against Danfoss's company history pages and published company data, October 2026.

FAQ

Questions about the Danfoss 148F3211 SFA 15 Safety Relief Valve, G 3/4,

Answers from our engineering team on installation, compatibility and integration.

01What is Danfoss 148F3211?
An SFA 15 safety relief valve set to 11 bar (160 psig) with G 3/4 inlet and G 1 outlet.
02What is the discharge coefficient?
A certified coefficient of discharge of 0.73 is listed.
03Does it come with a certificate?
Yes, a Danfoss pressure certificate is included.
04What is the temperature range?
-50 to 100 C.
05Which document is attached?
The Danfoss SFA 10 / SFA 10H / SFA 15 / SFA 15-50 data sheet AI564618139338en-000101.