Dräger Flame 2700 (Multi-IR) Flame Detector
Overview
The Dräger Flame 2700, designated Multi-IR, is a multichannel infrared flame detector that recognises both hydrocarbon fires and hydrogen fires. Hydrogen burns with an almost invisible flame and gives off little of the carbon dioxide emission that ordinary hydrocarbon IR detectors rely on, so a detector that explicitly lists hydrogen sensitivity is valuable for electrolyser, refuelling and chemical sites. Dräger quotes a response of about 5 seconds, with gasoline fires detected out to 65 metres and hydrogen flames out to 38 metres in the sensitivity table, measured on a 0.1 square metre pan fire or a defined plume fire.
Across Oman and the wider GCC, Seven Star LLC supplies the Dräger Flame 2700 on request, backed by engineers based in Muscat. We help refineries, petrochemical plants, gas processing sites and emerging hydrogen projects choose detector variants, accessories and mounting hardware that fit their layout.
Multichannel IR Detection in the Dräger Flame 2700
Instead of looking at one narrow infrared band, the Dräger Flame 2700 evaluates several channels between 2 and 5 micrometres. This wider spectral window is what lets the detector respond to hydrogen as well as hydrocarbon flames, and cross-checking the channels is how multi-IR detectors in general separate genuine fires from interference. Dräger reports that the 2700 ignores nuisance sources like arc welding and hot CO2 plumes, and its sensitive optics avoid reacting to fires beyond the monitored zone.
Coverage angle depends on the fuel: 80 degrees horizontally and 80 degrees vertically for gasoline, and 70 degrees horizontally with 80 degrees vertically for hydrogen. The sensitivity table also lists ammonia at 18 metres and silane at 2 metres for a smaller plume fire, so engineers working with unusual fuels can check coverage directly in the data sheet.
Construction and Diagnostics
The body is cast in SS316L stainless steel and weighs 2.8 kg. Ingress protection reaches IP66 and IP67 (NEMA 250 6P), and wiring enters through a pair of NPT or metric threaded ports. On the Dräger Flame 2700, a heated window protects the optics against icing and fogging, which matters for cold or humid installations and for sites with large day and night temperature swings.
The detector runs a Built-in-Test routine on its electronics and optics without operator action, and a manual test can be started too. A three-colour LED on the front face reports the state: green means healthy, yellow means a fault, and red means fire. To connect to a plant system, the detector offers HART, an RS-485 Modbus link, stepped current output and relays, powered from 24 V DC.
Key Features
The Dräger Flame 2700 provides these core capabilities:
- Multi-IR sensing of hydrocarbon and hydrogen-based fires in the 2 to 5 micrometre range.
- Response in around 5 seconds, with gasoline fires detected to 65 metres.
- Hydrogen flame detection to 38 metres for a plume fire under the stated test conditions.
- SIL 2 capability confirmed by a TUEV certificate.
- Rejection of welding arcs, hot CO2 plumes and similar nuisance sources.
- A heated viewing window and a self-test that can run automatically or on demand.
- HART and Modbus over RS-485, a stepped current loop and three relays.
- Service in ambient temperatures from -55 °C up to +75 °C.
Industrial Applications
Where a plant handles both oil-derived fuels and hydrogen, a single detector family such as the Dräger Flame 2700 reduces design complexity. The Dräger Flame 2700 suits hydrogen production and compression, ammonia and chemical processing, refinery hydrotreating units, gas turbine halls and fuel storage, alongside classic hydrocarbon hazards such as diesel, jet fuel, alcohols, methane and LPG, all of which appear in the published sensitivity data.
Contractors and plant owners from Muscat to the Sohar and Salalah economic zones can rely on Seven Star LLC for layout review, accessory selection and spare parts planning. Because Oman is developing green hydrogen and ammonia projects, the hydrogen capability of the Dräger Flame 2700 is a practical reason to specify it for new facilities, while the same body style serves established oil and gas sites.
Technical Specifications
The figures below for the Dräger Flame 2700 come from Dräger’s published data sheet:
| Parameter | Specification |
|---|---|
| Model | Dräger Flame 2700 (Multi-IR) |
| Type | Flameproof multi-band IR detector, hydrocarbon and hydrogen fires |
| Spectral response | Multi IR bands, 2 to 5 µm |
| Field of view | Gasoline 80 ° x 80 °; hydrogen 70 ° horizontal, 80 ° vertical |
| Response time | About 5 seconds (typical) |
| Detection range | n-heptane/gasoline 65 m; diesel 45 m; ethanol 40 m; methanol 35 m; hydrogen 38 m; methane/LPG 45 m; ammonia 18 m; silane 2 m |
| Current levels | Stepped loop with HART: 0 mA fault, 4 mA normal, 16 mA warning, 20 mA alarm |
| Relays and serial link | Three SPST volt-free relays (alarm, fault, auxiliary) rated 2 A at 30 V DC; Modbus on RS-485 |
| Power supply | 24 V DC nominal (18 to 32 V DC); standby max 90 mA, alarm max 130 mA (110/160 mA with heated window) |
| Ambient range | Operating down to -55 °C and up to +75 °C; option and storage to +85 °C |
| Enclosure and entries | SS316L stainless steel; two threaded entries, NPT or metric |
| Mass and size | 2.8 kg; roughly 102 x 117 x 157 mm |
| Ingress rating | IP66 / IP67 (NEMA 250 type 6P) |
| Approvals and certificates | ATEX / IECEx Ex db eb op is IIC T4 Gb variants; FM, FMC and CSA Class I Div 1; TUEV SIL 2; VdS EN 54-10; FM 3260 performance |
Ordering Codes and Accessories
Dräger lists seven order numbers for the Dräger Flame 2700: 6813916 (M-111SC), 6813917 (M-211SC), 6813918 (M-311SC), 6813956 (M-112SF), 6813957 (M-212SF), 6813958 (M-222SF) and 6813959 (M-312SF). The accessory list covers the FS-1400 (M) flame simulator (6813976), a simulator battery pack (6813889), the USB RS-485 kit (6813994), mounting hardware (duct mount 6813978, tilt mount 6813979, pole mounts 6813322 and 6813323), weather covers in stainless steel (6813189) or ABS (6813190) and a laser pointer for aiming (6813890). Contact us with your required Dräger Flame 2700 variant and we will confirm it against the data sheet.
Related Dräger Flame Detection
For hydrocarbon-only coverage next to the Dräger Flame 2700, compare the Dräger Flame 1500 (IR3) flame detector, view the full Dräger range or see our fire and gas detector category.
The triple IR sibling model is the Dräger Flame 2500 IR3 flame detector.
Request a Quote for Dräger Flame 2700
Ready to specify the Dräger Flame 2700? Send an RFQ to the Seven Star LLC instrumentation team for pricing, stock status and the data sheet. Our engineers in Muscat will help with detector quantities, accessories and outputs, as a trusted Dräger supplier for Oman and the GCC.
- Datasheet Dräger Flame 2700 (Multi-IR) Product Information and Data Sheet Download
Dräger gas detection product families listed here
Fixed detection is covered by the Polytron line: the Polytron 8100 EC for toxic gases and oxygen with electrochemical sensors, the Polytron 8200 CAT for flammable gases with a catalytic sensor, the Polytron 7000 and the PIR 7000 point infrared detector for hydrocarbons. Dräger flame detectors on this page are the Flame 1500 and Flame 2500 (triple infrared) and the Flame 2700 (multi-infrared). Portable instruments include the Pac 8000 single-gas detector, the X-am 2500 for one to four gases and the X-am 8000 for up to seven. Short-term colorimetric tubes such as Hydrogen Sulfide 100/a (CH29101) are listed with the analyzer accessories.Where Dräger detectors are used
Polytron transmitters and PIR 7000 heads are found on wellhead and gathering facilities, gas plants, refineries, tank farms, LNG and petrochemical units, and in water treatment chlorine rooms. Portable Dräger gas detectors serve confined space entry, hot work permits and personal H2S monitoring, which is routine on sour fields in the GCC. Detector tubes remain a simple spot check where an electronic sensor is not available for the gas.Ordering Dräger equipment: what we need
Dräger identifies most items by a seven-digit part number, such as 8101211, and that number is the most direct route to the right quotation. For a fixed transmitter, add the target gas, measuring range, output (4-20 mA, HART or relays), housing material, cable entry thread and the required hazardous-area approval. For portables, list the sensor configuration, pump or diffusion mode and the charger or calibration accessories needed. For tubes, give the gas and the range printed on the box.Browse Dräger products by category: Fire & Gas Detector, Gas Analyzer Accessories.

Reviews
There are no reviews yet.