Brand: Yokogawa
Yokogawa EJX510A-EAS7N-012NL Absolute, 8 to 200 kPa
Description
Low-absolute-pressure specialist: EJX510A-EAS7N-012NL
Down at 8 kPa absolute the physics gets delicate. Yokogawa EJX510A-EAS7N-012NL uses the A capsule, whose minimum span of 8 kPa is smaller than the 10 kPa of the EJA-E version, and whose maximum is 200 kPa abs. Output is 4 to 20 mA with HART 5 (code E, which is HART 5 only). The process connection is a 1/2 NPT male thread that screws into a female coupling, and a 316 SST two-inch pipe bracket is included.
Understanding EJX510A-EAS7N-012NL by position
| Code position | Meaning |
|---|---|
| -E | 4 to 20 mA DC with HART 5 digital communication |
| A | Capsule: span 8 to 200 kPa |
| S | 316L SST process connector, Hastelloy C-276 diaphragm, 316L SST or F316L SST other wetted parts |
| 7 | Process connection: 1/2 NPT male |
| 1 | Amplifier housing: cast aluminum alloy |
| 2 | Electrical: 1/2 NPT female, two electrical connections, no blind plugs |
| N | Integral indicator: none |
| L | Mounting bracket: 316 SST 2-inch pipe mounting bracket |
Accuracy and limits of the A capsule
The reference accuracy for A is plus or minus 0.04 percent of span down to a span of 20 kPa; below that, the datasheet gives the formula of 0.004 times URL over span percent, which for the 8 kPa minimum span with URL 200 kPa works out to about 0.1 percent. Over-pressure limit is 4 MPa abs and maximum working pressure is 200 kPa abs. The datasheet also gives a minimum working pressure curve for silicone oil that depends on process temperature, so check it for vacuum duty at the hot end of the range. Stability is plus or minus 0.2 percent of URL for fifteen years.
Materials of EJX510A-EAS7N-012NL and process compatibility
Wetted material S means a 316L stainless process connector, a Hastelloy C-276 diaphragm and 316L or F316L stainless for the other wetted parts, all noted by Yokogawa as conforming to NACE MR0175 and ISO 15156 recommendations and also to MR0103. The capsule is filled with silicone oil as standard; fluorinated oil is an option. The datasheet reminds users that the selection of wetted material is the responsibility of the buyer and that highly corrosive fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite or steam at 150 degrees C and above need manufacturer review. For EJX510A-EAS7N-012NL the process temperature range is minus 40 to 120 degrees C.
EJX510A-EAS7N-012NL data summary
| Item | Value |
|---|---|
| Capsule A | 8 to 200 kPa abs span; URL 200 kPa abs |
| Output code E | 4 to 20 mA with HART 5 protocol |
| Accuracy | 0.04 percent of span for spans of 20 kPa or more |
| Max working pressure | 200 kPa abs (29 psia) |
| Over-pressure | 4 MPa abs |
| Burst | 30 MPa |
| Process thread | 1/2 NPT male |
| Bracket | 316 SST 2-inch pipe |
| Indicator | None |
| Update | 45 ms |
| Response | 90 ms |
Typical uses
Vacuum drying, deaerators, flash vessels, vacuum pump suction, condenser back-pressure and vapor recovery units all need absolute pressure in the tens of kPa. In the Gulf these show up in desalination ejector systems and refinery vacuum units. Lower-capsule transmitters also monitor nitrogen blanketing with absolute reference.
Why code E and not J
Code E gives HART 5 only. Code J lets you choose HART 5 or 7 at ordering. Plants that standardize on HART 5 for asset management compatibility can order E. The advanced diagnostics option DG6 is applicable to E, J and F output codes.
Installation notes
Mount high or with a drip leg so condensate does not sit in the male port. Keep the process line short for vacuum applications to minimize outgassing effects, and verify tightness of the 1/2 NPT male thread with a leak test since air in-leakage would offset a vacuum reading. The bracket accepts a 2 inch pipe.
Zero trim should be done with proper vacuum reference. If a cover is opened, check the O-ring and re-seat it.
To stay within the same family but change the function, remember the single-position rule. Replacing the A with B or C increases the spans to 0.02 to 2 MPa abs or 0.1 to 10 MPa abs. Replacing the 7 with 4 turns the connection into 1/2 NPT female, and 8 or 9 give DIN G1/2 or M20 x 1.5 male. Replacing E with J allows HART 7. Adding D or E for the indicator adds an LCD and changes the ambient low limit to minus 30 degrees C. The datasheet lists approvals under separate slash codes (FM FF1 and FS1, ATEX KF22 and KS21, CSA CF1 and CS1, IECEx SF22 and SU22), all of which belong to a different quotation than the base code of EJX510A-EAS7N-012NL.
If you need the exact nameplate match, send us the full tag and the calibrated range, since a transmitter shipped with a calibration option (such as psi or bar units through /D1 and /D3) needs that option to be quoted.
Quick answers about EJX510A-EAS7N-012NL
- What is the lowest span of EJX510A-EAS7N-012NL? The A capsule has a minimum span of 8 kPa absolute, with a maximum of 200 kPa absolute.
- What does E in the first suffix position mean? 4 to 20 mA DC output with HART 5 digital communication.
- Is a mounting bracket included? Yes, L is a 316 SST bracket for 2-inch pipe mounting.
- What is the thread? 1/2 NPT male, code 7 in the process connection position.
- What is the burst pressure? The datasheet gives 30 MPa burst pressure for the A, B and C capsules, while over-pressure is 4 MPa for the A capsule.
Documents and quotation
For low-pressure absolute applications it helps to tell us the operating range and any vacuum conditions.
The Yokogawa general specification GS 01C25F01-01EN, which covers the EJX510A and EJX530A, is supplied as the datasheet PDF with this listing. To request a quotation, send the part number EJX510A-EAS7N-012NL, the quantity, tag numbers, process fluid and the approval you need if the area is classified. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Availability and lead time are confirmed per RFQ.
Other Models in the EJX510A Range
Seven Star LLC supplies models from the EJX510A range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Yokogawa EJX510A-JCS4N-012DN Absolute Pressure Transmitter | Pressure Transmitters | View details |
| Yokogawa EJX510A-EAS7N-012NL Absolute, 8 to 200 kPa | Pressure Transmitters | You are viewing this model |
Datasheets & Documents
- Datasheet Yokogawa EJX510A-EAS7N-012NL Absolute, 8 to 200 kPa Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.
Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.
Yokogawa at a glance
| Established | 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki |
|---|---|
| Milestones | Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986 |
| Headquarters | Tokyo, Japan |
| Product families | Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers |
Yokogawa products we list
| Family | Models | Typical use |
|---|---|---|
| Pressure and DP transmitters | EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable | Pressure, level and DP flow measurement in process plants |
| Temperature transmitters | YTA610, YTA710 | RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus |
| Flowmeters | ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 | Water and conductive liquids, mass flow of hydrocarbons, steam and gas |
| Analysers | TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover | Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen |
| Controllers and recorders | UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 | Single-loop control, furnace programs and data recording |
| Control and safety systems | CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 | Spares and expansions for CENTUM DCS, safety systems and STARDOM |
| Battery packs | S9129FA, S9185FA, S9548FA | Memory backup batteries for DCS and controller modules |
The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.
Where Yokogawa products are used
In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.
Ordering Yokogawa products: what we need
Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.
Facts checked against Yokogawa's corporate history, October 2026.
Browse Yokogawa products by category: PLC & I/O Cards, Flowmeters, Pressure Instrumentation, Automation Accessories, Temperature Instrumentation.
FAQ
Questions about the Yokogawa EJX510A-EAS7N-012NL Absolute, 8 to 200 kPa
Answers from our engineering team on installation, compatibility and integration.
01What is the lowest span of EJX510A-EAS7N-012NL?
The A capsule has a minimum span of 8 kPa absolute, with a maximum of 200 kPa absolute.
02What does E in the first suffix position mean?
4 to 20 mA DC output with HART 5 digital communication.
03Is a mounting bracket included?
Yes, L is a 316 SST bracket for 2-inch pipe mounting.
04What is the thread?
1/2 NPT male, code 7 in the process connection position.
05What is the burst pressure?
The datasheet gives 30 MPa burst pressure for the A, B and C capsules, while over-pressure is 4 MPa for the A capsule.