Brand: Schneider Electric
Schneider Electric RXM2LB1BD Harmony RXM Relay 24 V DC
Description
RXM2LB1BD: RXM2 miniature relay, 24 V DC coil
The RXM2LB1BD is an RXM-series miniature plug-in relay with 2 changeover contacts rated 5 A, a 24 V DC coil, no status LED and no test button. It belongs to the Schneider Electric Harmony electromechanical relay range and is built for panel and marshalling-cabinet duty, where it plugs into a socket instead of being wired directly. Seven Star LLC supplies the RXM2LB1BD in Oman and the GCC as an independent supplier based in Muscat.
Reading the reference as our own pattern across the RXM2L group, and not as a published ordering table: RXM2 gives the contact count, LB the 5 A body, the digit 1 (without an LED) and the closing code BD the coil, here 24 V DC.
RXM2LB1BD technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / RXM2LB1BD |
| Range / series | Harmony Electromechanical Relays / RXM series |
| Relay type | Miniature plug-in relay |
| Contacts | 2 C/O |
| Control circuit voltage [Uc] | 24 V DC |
| Operating voltage limits | 19.2–26.4 V DC |
| Drop-out threshold | ≥ 0.1 Uc DC |
| Average coil resistance | 640 Ohm at 23 °C ± 10 % |
| Average coil consumption | 0.9 W, DC |
| Status LED | Without |
| Control / test | No lockable test button |
| Load current | 5 A at 250 V AC; 5 A at 28 V DC |
| Maximum switching capacity | 1250 VA AC; 140 W DC |
| Contact material | Silver alloy (Ag/Ni) |
| Mechanical durability | 20000000 cycles |
| Electrical durability | 200000 cycles resistive load 23 °C; 100000 cycles resistive load at 55 °C |
| Storage temperature | -40–85 |
| Net weight | 0.032 kg |
| Standards | CE, IEC 61810-1 (iss. 2), UL 508 |
All figures above come from the Schneider Electric product datasheet for the RXM2LB1BD, which carries the print date 8 Nov 2026. The sheet shows no discontinuation notice for this reference.
Typical applications in Oman and the GCC
A 5 A relay without a test button is intended for repeat, signalling and logic duty where the contacts only carry modest currents and a hand-operated override is not wanted. Panels in Oman and the wider Gulf see high ambient temperatures, dust and humidity, so relays should be installed in ventilated, sealed cabinets and the temperature limits (storage -40–85 °C, no operating range listed) kept in mind when panels sit in the sun. Seven Star LLC supplies the RXM2LB1BD for panel builders, maintenance teams and projects in oil and gas, power, desalination and general industry.
Installation, commissioning and maintenance
Seat the relay squarely so that all flat pins engage the socket. Since it has no test button, plan a way to prove the circuit from the controller or by temporarily bridging the coil, and keep spares of the same coil voltage on the shelf. The storage temperature range is -40–85 °C.
During commissioning, prove the output by energising the coil from the control system and checking the contact state with a meter. A relay is a wear item: keep spare relays of the same coil voltage and replace them on a schedule defined by the duty, not only after a failure.
Coil data and operating range of the RXM2LB1BD
24 V DC is the everyday control voltage of PLC and DCS output cards, so this coil is the natural interposing choice between a controller output and a heavier field load, a solenoid or a motor starter coil.
The datasheet gives operating voltage limits of 19.2–26.4 V DC, with a drop-out threshold of ≥ 0.1 Uc DC. The average coil resistance is 640 Ohm at 23 °C ± 10 % and the average consumption is 0.9 W, DC. Those numbers matter more than the nominal voltage: a supply that sags under load, or that sits at the top of its tolerance, should still fall inside the stated window for RXM2LB1BD to pick up and release cleanly.
A DC coil has no inrush surge to speak of, but it stores energy: when the coil is switched off it can throw a voltage spike back into the driving output. That is why a protection module or free-wheeling diode is often added across a DC coil driven by a transistor output. Check polarity at the socket if you add one.
Selection checklist for this relay
- Coil voltage and type: 24 V DC. Match both the voltage and AC or DC to the supply that actually feeds the coil.
- Contact count and load: 2 changeover contacts, 5 A at 250 V AC; 5 A at 28 V DC; confirm the NC contact rating if the load is on the NC side.
- Indication: no LED, so status must be read from the controller or by a lamp elsewhere in the circuit.
- Test facility: no test button.
- Socket: the relay has Flat (faston type) pins, so choose a matching socket from the same Harmony range and confirm its reference with your supplier.
- Environment: storage temperature -40–85 °C (no operating range is listed on the datasheet); as a plug-in relay it belongs inside a panel, not on an open plant floor.
Comparing this relay with related references
The table below lists the RXM2LB1BD next to the closest references from the same group, ordered by coil voltage, so that you can check that you are specifying the right coil and indicator combination.
| Part number | Coil voltage | Indicator LED | Test button | Coil resistance |
|---|---|---|---|---|
| RXM2LB1B7 | 24 V AC | Without | No | 180 Ω |
| RXM2LB1P7 | 230 V AC | Without | No | 16500 Ω |
| RXM2LB2P7 | 230 V AC | With | No | 16500 Ω |
| RXM2LB1BD (this page) | 24 V DC | Without | No | 640 Ω |
Contact ratings of the RXM2LB1BD 5 A relay
The two changeover contacts are rated for 5 A at 250 V AC; 5 A at 28 V DC with a maximum switching capacity of 1250 VA AC; 140 W DC. The contact material is Silver alloy (Ag/Ni). The datasheet separates the normally open contact, which carries 5 A, from the normally closed contact, which is listed at 2.5 A for IEC duty, so loads that sit on the NC side need to be checked against that lower figure.
Mechanical durability is 20000000 cycles and electrical durability is 200000 cycles resistive load 23 °C; 100000 cycles resistive load at 55 °C. Minimum switching values are listed as 5 mA and 5 V, subject to switching frequency, environment and the reliability level expected; dry-circuit signals below that should not be left to a standard AgNi contact.
The relay has no lockable test button, and this reference is sold in indivisible quantities of 10, which is relevant when you size an order for a few relays.
Information to send with an RFQ
- The exact part number RXM2LB1BD and the quantity, remembering the pack quantity of the reference.
- The coil voltage on site, 24 V DC here, and the supply tolerance.
- The socket reference or the existing relay being replaced.
- The load type and current on each contact.
- The delivery location and whether the relays are for a project or maintenance stock.
Documents and quotation
The Schneider Electric datasheet for the RXM2LB1BD is attached on this page, and the figures above come from it. Always check the latest revision before final design.
To obtain a quotation, send us the part number RXM2LB1BD with the quantity and delivery location, and we will respond with availability and lead time. Seven Star LLC is an independent supplier and does not claim any official status with the manufacturer.
Other Models in the Se Rxm L2 Range
Seven Star LLC supplies models from the Se Rxm L2 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric RXM2LB1B7 Harmony RXM Relay 24 V AC | Contactors & Overload Relays | View details |
| Schneider Electric RXM2LB1BD Harmony RXM Relay 24 V DC | Contactors & Overload Relays | You are viewing this model |
| Schneider Electric RXM2LB1P7 Harmony RXM Relay 230 V AC | Contactors & Overload Relays | View details |
| Schneider Electric RXM2LB2P7 Harmony RXM Relay 230 V AC | Contactors & Overload Relays | View details |
Datasheets & Documents
- Datasheet Schneider Electric RXM2LB1BD Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric RXM2LB1BD Harmony RXM Relay 24 V
Answers from our engineering team on installation, compatibility and integration.
01What coil voltage does the RXM2LB1BD use?
The RXM2LB1BD has a 24 V DC control coil. The datasheet gives operating limits of 19.2–26.4 V DC and a drop-out threshold of ≥ 0.1 Uc DC, and an average coil resistance of 640 Ohm at 23 °C ± 10 %.
02How many contacts and what current does the RXM2LB1BD switch?
It has 2 changeover contacts with a load current of 5 A at 250 V AC; 5 A at 28 V DC and a maximum switching capacity of 1250 VA AC; 140 W DC. The contact material is Silver alloy (Ag/Ni).
03Does the RXM2LB1BD have an LED or a test button?
It has no status LED and no lockable test button, according to the datasheet.
04What temperature range applies to the RXM2LB1BD?
The datasheet lists storage at -40–85 °C and gives no operating temperature range for this reference, so confirm the operating limits with the manufacturer if the panel runs hot.
05Can I request a quotation for the RXM2LB1BD in Oman?
Yes. Send the part number RXM2LB1BD, the quantity and the delivery location, and Seven Star LLC will confirm availability and lead time as an independent supplier in Muscat.