Brand: Schneider Electric
Schneider Electric GVAD0110 TeSys GV2/GV3 1 NO + 1 NC Contact
Description
GVAD0110: 1 NO plus 1 NC block with a normally closed fault contact
The GVAD0110 is a Schneider Electric auxiliary contact for the TeSys GV2 and GV3 motor circuit-breakers, with one normally open and one normally closed contact and a fault signal on a normally closed contact. It clips onto the left side of the breaker and carries state information to the control system. Seven Star LLC supplies the GVAD0110 in Oman and the GCC as an independent supplier based in Muscat.
The four GVAD references on the market differ in which contact is the fault contact and whether it is NO or NC. For the GVAD0110 the datasheet says auxiliary contacts operation is a fault signal on 1 NC, and the pole composition is 1 NO + 1 NC. The pairing is typical for a fail-safe control circuit that monitors a healthy loop.
Technical specifications of the GVAD0110
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / GVAD0110 |
| Description | Product datasheet TeSys GV2 & GV3 – auxiliary contact – 1 NO + 1 NC (fault) |
| Range | TeSys; TeSys Deca |
| Device short name | GVAD |
| Product or component type | Auxiliary contact block |
| Product compatibility | GV2ME; GV2L; GV3P; GV2P; GV3L; GV2LE; GV2RT |
| Mounting location | Left side |
| Auxiliary contacts operation | Fault signal 1 NC |
| Pole contact composition | 1 NO + 1 NC |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-1; 300 V conforming to UL 508; 300 V conforming to CSA C22.2 No 14 |
| [Ue] rated operational voltage | 48 to 690 V AC; 24 to 240 V DC |
| [Ith] conventional free air thermal | 6A |
| Mechanical durability | 100000 cycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Protection type | GB2CB– circuit breaker; GG fuse 10 A |
| Rated operational power in VA | 300 VA at 48 V AC-15 – electrical durability: 100000 cycles; 414 VA at 690 V AC-15 – electrical durability: 100000 cycles |
| Rated operational power in W | 120 W at 240 V DC-13 – electrical durability: 100000 cycles; 140 W at 110 V DC-13 – electrical durability: 100000 cycles |
| Height | 89 mm |
| Width | 9.3 mm |
| Depth | 66 mm |
| Net weight | 0.055 kg |
| Environmental characteristic | Normal environment |
| Product certifications | UKCA |
Compatibility and ratings of the GVAD0110
The compatibility list in the datasheet is GV2ME, GV2P, GV2L, GV2LE, GV2RT, GV3L and GV3P. The block fits the left side, which means no other left-hand accessory can be used at the same position.
It is rated for 48 to 690 V AC and 24 to 240 V DC, with a thermal current of 6 A and 2.5 A on the fault contact. For logic-level signals the minimum is 5 mA and 17 V, so very small PLC inputs need a check against that threshold.
The block mounts on the left side of the breaker and is 9.3 mm wide, 89 mm high and 66 mm deep, with a net weight of 0.055 kg. The datasheet lists a rated operational voltage of 48 to 690 V AC and 24 to 240 V DC, a conventional thermal current of 6 A, and 2.5 A for the fault-signalling contact. Rated operational power at AC-15 is 720 VA at 230 to 240 V and 850 VA at 380 to 415 V, each with an electrical durability of 100000 cycles; the DC-13 figures include 120 W at 240 V DC.
How the fault contact of the GVAD0110 is used
A normally closed fault contact is a monitored loop: as long as the breaker is healthy the loop is closed, and an open circuit, whether from a trip or a broken wire, is read as an alarm. That is why safety-minded designs ask for the NC type.
The second contact, normally open, gives a plain run or closed indication. With both in one block, a single accessory feeds a motor-status lamp and an alarm input of a PLC from the same breaker.
GVAD family: the GVAD0110 against its siblings
The four references below share the same left-side mounting and ratings and differ only in contact pattern and lifecycle status.
| Reference | Contacts | Fault signal contact | Status in datasheet |
|---|---|---|---|
| GVAD0101 | 2 NC | Fault signal 1 NC | Discontinued (17 Jul 2023) |
| GVAD0110 | 1 NO + 1 NC | Fault signal 1 NC | Listed |
| GVAD1001 | 1 NO + 1 NC | Fault signal 1 NO | Listed |
| GVAD1010 | 2 NO | Fault signal 1 NO | Listed |
Specifying the GVAD0110 correctly
- Contacts: 1 NO + 1 NC, fault signal on the NC.
- Breaker: one of the listed GV2 or GV3 families.
- Control circuit: voltage within 24 to 240 V DC or 48 to 690 V AC, current within 6 A.
- Alternatives: GVAD1001 puts the fault signal on a NO contact, and GVAD1010 gives two NO contacts.
- Document the contact meaning in your wiring schedule, because the datasheet label and the physical block carry only the code.
Wiring and verification of the GVAD0110
After isolating the breaker, push the block into the side seat, wire the terminals and verify continuity in the closed and tripped positions with a meter before restoring power. The block has a net weight of 0.055 kg.
Record the result in the commissioning sheet. A normally closed fault loop should read closed with the breaker on and open when tripped; if the readings are reversed, the wrong variant has been installed.
GVAD0110 uses in Oman and the GCC
Motor feeders for pumps, fans and conveyors in utilities and process plants use GV2 breakers with contact blocks to report status to a PLC or a DCS. The normally closed fault loop is common in oil and gas skids where wire breaks must raise an alarm.
Heat inside the starter panel is the main environmental stress in the region; the datasheet lists a normal environment rating, so keep the cabinet ventilated.
Information to send with an RFQ for the GVAD0110
- Full reference and quantity required
- Breaker model (GV2 or GV3 type) the block must fit
- Contact logic needed (NO or NC fault signal)
- Signal voltage and the input card that reads it
- Delivery location and timing
Documents and quotation
A datasheet for the GVAD0110 is attached on this page. It carries the electrical, mechanical and environmental data summarised above, so the figures can be checked against your drawings.
Send the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.
Other Models in the Se Tesys Gvad Range
Seven Star LLC supplies models from the Se Tesys Gvad range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric GVAD0101 TeSys GV2/GV3 2 NC Contact Block | Contactors & Overload Relays | View details |
| Schneider Electric GVAD0110 TeSys GV2/GV3 1 NO + 1 NC Contact | Contactors & Overload Relays | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric GVAD0110 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric GVAD0110 TeSys GV2/GV3 1 NO + 1
Answers from our engineering team on installation, compatibility and integration.
01What contacts does the GVAD0110 have?
One normally open and one normally closed contact; the fault signal is on the normally closed contact.
02Which breakers fit the GVAD0110?
GV2ME, GV2P, GV2L, GV2LE, GV2RT, GV3L and GV3P, per the datasheet.
03What voltage range does the GVAD0110 cover?
48 to 690 V AC and 24 to 240 V DC. See the datasheet linked on this page for the full figures.
04What current can the GVAD0110 fault contact carry?
The datasheet lists 2.5 A for fault signalling and 6 A conventional thermal current.
05Where does the GVAD0110 mount?
On the left side of the GV2 or GV3 breaker.