Brand: Schneider Electric
Schneider Electric ABL8RED24400 40 A Redundancy Module
Description
ABL8RED24400: 40 A redundancy module for 24 V DC supplies
The ABL8RED24400 is not a power supply itself but a redundancy module from the Schneider Electric Phaseo range. It combines the outputs of two 24 V DC power supplies onto one load rail, so that the failure of one supply does not interrupt the load. The datasheet lists a maximum output current of 40 A, an input voltage of 24–28.8 V DC and an output of (Uin − 0.2) V DC, meaning the unit drops only about 0.2 V. Seven Star LLC supplies the ABL8RED24400 in Oman and the GCC as an independent supplier based in Muscat.
In the reference, ABL8 is the Phaseo prefix, RED stands for the redundancy function in our reading, and 24400 corresponds to 24 V and 40 A. The datasheet remains the reference for ordering.
Pairing the ABL8RED24400 with Phaseo supplies
The datasheets of the ABL8RPS, ABL8RPM and ABL8WPS supplies name this module as the way to improve availability by connecting supplies in parallel. The Phaseo references that fit the 24 V input window are ABL8RPS24030 (3 A), ABL8RPS24050 (5 A), ABL8RPM24200 (20 A) and ABL8WPS24400 (40 A); the redundant current you can count on is that of one supply, up to the 40 A limit of the module. Use two identical supplies, keep each module input inside the 22–30 V limit, and fit the same cable length to each so they behave alike.
Where redundancy matters in Oman and the GCC
A redundant 24 V rail is typical for plants where a lost control supply means a lost process: desalination and water-treatment plants, oil and gas skids, compressor stations and power substation automation. In such installations the two supplies are often fed from independent sources, for example a UPS and a mains feeder, so that a single failure does not take down the controller. The ABL8RED24400 is the small, passive component that makes this practical, and it should be fitted next to the supplies it serves so that cable drop is minimal. Regional heat means the module and the supplies need ventilated enclosures; check the module rating of −25–60 °C against real cabinet temperatures.
Selecting the ABL8RED24400: checklist
- Confirm that both supplies output 24–28.8 V DC and that the module input limit of 22–30 V is respected.
- Size each supply for the full load so one unit can carry it alone, up to the module limit of 40 A.
- Decide whether the status relay should be wired to a PLC alarm input.
- Allow for the 0.2 V drop across the module when the load is voltage-sensitive.
- Plan equal cable lengths from each supply and enough terminal capacity for the currents involved.
Standards and test levels listed for the ABL8RED24400
The datasheet quotes electrostatic discharge to IEC 61000-4-2, emission to IEC 61000-6-3, induced electromagnetic field to IEC 61000-4-6 level 3, radiated field to IEC 61000-4-3 level 3, fast transients to IEC 61000-4-4 level 3, surge to IEC 61000-4-5 level 2 and conducted and radiated emissions to EN 55022 class B. Safety references are IEC 60950-1 and EN/IEC 61204, with CSA C22.2 No 60950-1 and UL 508 listed under standards and EAC and RCM under certifications. Vibration resistance is 3.5 mm between 3 and 11.9 Hz and 2 gn between 11.9 and 150 Hz to IEC 61131-2, dielectric strength is 500 V between input and ground and between output and ground, and the reliability figure is an MTBF of 2488391 hours at 24 V DC by the UTE C80-810 method.
Wiring, mounting and monitoring of the ABL8RED24400
The module clips onto a 35 mm DIN rail and can be mounted horizontally or vertically. Terminals are screw type: 4 × 0.5–4 × 10 mm² (20–8 AWG) for the inputs, 2 × 0.5–2 × 10 mm² for the output, and a removable terminal block for the diagnostic relay (1 × 2.5 mm², 14 AWG). A green LED per input shows that each supply is present, and the relay gives a remote contact for supply status, so a PLC can raise an alarm when one source drops out. The weight is 0.7 kg, protection is IP20 conforming to IEC 60529, and the unit is rated for operation at −25–60 °C and storage at −40–85 °C. Use short, equal-length, correctly sized cables between the supplies and the module; with 40 A flowing, voltage drop and loose screws are the usual cause of trouble.
ABL8RED24400 technical data
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / ABL8RED24400 |
| Range | Phaseo |
| Type | Redundancy module |
| Input voltage | 24–28.8 V DC |
| Input voltage limits | 22–30 V |
| Output voltage | (Uin-0.2) V DC |
| Maximum output current | 40 A |
| Input current | 20 A |
| Output channels | 1 |
| Output coupling | Parallel |
| Output protection | External, provided by the power supplies |
| Fixing | 35 mm DIN rail, horizontal or vertical |
| Signalling | 1 green LED per input; 1 status relay |
| Net weight | 0.7 kg |
| Protection degree | IP20 conforming to IEC 60529 |
| Operating temperature | −25–60 °C |
| Storage temperature | −40–85 °C |
| Relative humidity | 0–90 % during operation, 0–95 % during storage |
| Operating altitude | 2000 m |
| MTBF | 2488391 H at 24 V DC with UTE C80-810 calculation method |
How the ABL8RED24400 combines two supplies
The housing marks two inputs, Uin 1 and Uin 2, and the datasheet lists one output channel with parallel coupling and an output voltage of (Uin − 0.2) V DC. In general terms, a redundancy module of this kind isolates the two sources from each other so that a failed or switched-off supply does not pull down the rail; the datasheet’s internal wiring diagram shows the exact arrangement.
The datasheet lists an input current of 20 A and a maximum output current of 40 A. The practical rule for redundancy is that each supply must be able to carry the full load alone, so size every supply for the whole current, not half of it. This unit does not protect the output itself: the datasheet states that overload and short-circuit protection is external, supplied by the power supplies feeding it.
Information to send with an RFQ for the ABL8RED24400
- Reference ABL8RED24400 and quantity.
- Models and ratings of the two 24 V supplies it will join.
- Total load current and the acceptable voltage drop.
- Whether the diagnostic relay will be wired to an alarm.
- Delivery location and required date.
Documents and quotation
The manufacturer datasheet for the ABL8RED24400 is attached on this page and carries the complete specification set, including the dimension drawings and the derating information. Compare the datasheet revision with your project documents before you freeze a bill of materials.
Send us the reference ABL8RED24400, the quantity and the delivery location, and Seven Star LLC will reply to your request for quotation. We work as an independent supplier based in Muscat and serve customers across Oman and the GCC.
Datasheets & Documents
- Datasheet Schneider Electric ABL8RED24400 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric ABL8RED24400 40 A Redundancy
Answers from our engineering team on installation, compatibility and integration.
01What does the ABL8RED24400 do?
It joins the outputs of two 24 V DC power supplies onto one rail so that the failure of one does not interrupt the load. The output voltage is the input voltage minus 0.2 V.
02What current can the ABL8RED24400 handle?
The datasheet lists a maximum output current of 40 A, with an input current of 20 A. The module relies on the supplies for overload and short-circuit protection.
03What input voltage does the ABL8RED24400 accept?
Nominal input is 24–28.8 V DC with limits of 22–30 V.
04How does the ABL8RED24400 signal a failed supply?
A green LED per input shows supply status and a relay provides a status contact. The relay terminal block takes up to 1 × 2.5 mm² wire.
05How is the ABL8RED24400 mounted?
It clips onto a 35 mm DIN rail horizontally or vertically. It weighs 0.7 kg and has IP20 protection.