- Automation & ControlView all 3,202 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Encoders
- Motor Soft Starters
- CCTV & Security
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Advantech
Advantech ADAM-4024 4-Channel Analog Output Module
Description
Overview
Advantech ADAM-4024 is a four-channel analog output module with Modbus that lets a controller, SCADA server or industrial PC drive 4 to 20 mA loops or voltage signals over RS-485. Each output channel can be set for current or for voltage, current channels can act as a source or as a sink, and the same box also carries four digital inputs that read dry or wet contacts. In one DIN-rail unit it therefore gives you setpoint outputs for drives, valve positioners or recorders and a few status inputs for feedback.
The model is a member of the ADAM-4000 remote I/O family, and its ordering code in the manufacturer datasheet is ADAM-4024-C. Plant engineers in Oman look for Advantech ADAM-4024 when a retrofit needs analog setpoints from a PC-based control system without a PLC analog card. Seven Star LLC is an independent supplier serving Oman and the GCC.
Highlights of Advantech ADAM-4024
- Four analog outputs, each one configurable as 0 to 20 mA, 4 to 20 mA, plus or minus 10 V, 0 to 10 V, plus or minus 5 V or 0 to 5 V.
- Sink or source type selectable for each current channel.
- Programmable output slope, 0.125 to 128 mA per second or 0.0625 to 64 V per second, to ramp setpoints smoothly.
- Four digital inputs, dry or wet contact selectable per channel.
- 3,000 VDC isolation on the analog outputs and on the digital inputs.
- Watchdog timer with 1.6 second system and communication monitoring.
Specification table for Advantech ADAM-4024
| Model | ADAM-4024 (ordering code ADAM-4024-C) |
|---|---|
| Function | 4-channel analog output module with Modbus |
| Analog output channels | 4 |
| Output impedance | 0.5 ohm |
| Current output ranges | 0 to 20 mA, 4 to 20 mA; sink or source per channel |
| Voltage output ranges | Plus or minus 10 V, 0 to 10 V, plus or minus 5 V, 0 to 5 V |
| Accuracy | Plus or minus 0.1 percent of full scale range, current and voltage |
| Maximum current load | 500 ohm |
| Minimum voltage load | 1 kilohm |
| Resolution | 12-bit and 16-bit |
| Programmable output slope | 0.125 to 128 mA per second; 0.0625 to 64 V per second |
| Span temperature coefficient | Plus or minus 25 ppm per degree Celsius |
| Zero drift | Voltage plus or minus 30 microvolt per degree Celsius; current plus or minus 0.2 microamp per degree Celsius |
| Digital input channels | 4, dry or wet contact selectable |
| Dry contact | Level 0 open, level 1 closed to GND |
| Wet contact | Level 0 1 V maximum, level 1 10 to 30 VDC |
| Isolation | 3,000 VDC |
| Power consumption | 3 W at 24 VDC |
| Power input | Unregulated 10 to 30 VDC |
| Connectors | 2 plug-in terminal blocks, 14 to 28 AWG |
| Protocols | ASCII command and Modbus RTU |
| Operating temperature | minus 10 to 70 degrees Celsius |
| Storage temperature | minus 25 to 85 degrees Celsius |
| Humidity | 5 to 95 percent RH |
Driving loads with ADAM-4024
Current output has a maximum load resistor of 500 ohm, which is enough for most positioners, current-to-pressure converters and chart recorders, but the total loop resistance including cable must stay under that figure. Voltage output needs a load of at least 1 kilohm. The output slope setting is an unusual extra: it makes the module ramp from one value to the next at a programmed rate, which protects valves and drives against abrupt setpoint steps and avoids mechanical shock in a process line.
Digital inputs on ADAM-4024
The four digital inputs accept either a dry contact, where logic 1 means the contact closes to ground, or a wet contact with a level of 10 to 30 VDC for logic 1 and 1 V or less for logic 0. This is helpful to read a limit switch, a running contact of a motor starter or a pushbutton without extra interposing relays, and it keeps the voltage level choice in configuration instead of hardware.
Applications in Oman and the GCC
Examples include speed setpoints to variable frequency drives on water pumps, damper and valve positioning in HVAC plants, dosing pump control at water treatment sites and analog setpoints in test benches. Because it speaks Modbus RTU, a SCADA server in a utility control room can talk to it through an RS-485 gateway.
Accuracy, resolution and drift
Both current and voltage outputs are specified at plus or minus 0.1 percent of full scale range, with a span temperature coefficient of plus or minus 25 ppm per degree Celsius. Zero drift is plus or minus 30 microvolt per degree Celsius on voltage output and plus or minus 0.2 microamp per degree Celsius on current output. For a 4 to 20 mA signal over a 50 degree temperature swing, those drift numbers remain small compared with the basic accuracy, so the module does not need frequent recalibration in a typical plant room. The datasheet lists 12-bit and 16-bit resolution, and the output impedance of 0.5 ohm keeps voltage outputs stiff against moderate loads.
Using the watchdog and safe states
An output module is only as good as its behaviour when communication fails. The system watchdog of 1.6 second and the communication watchdog let the module detect a stalled host and move to a pre-defined safe value. Choose safe values for each channel during commissioning: a pump speed setpoint normally falls back to a minimum, a damper setpoint to a safe position. Document those values in the loop folder so operators know what the outputs do when the network is lost.
How ADAM-4024 differs from ADAM-4021
The ADAM-4021 provides one analog output channel, source type only, with 0 to 20 mA, 4 to 20 mA and 0 to 10 V, at 1.4 W. The ADAM-4024 gives four channels, adds bipolar voltage ranges, allows sink or source on current channels, includes four digital inputs, and draws 3 W. Its terminals accept thinner wire, 14 to 28 AWG, than the 14 to 22 AWG of the single-channel module.
Installation and maintenance
Mount on a DIN rail, wire the 10 to 30 VDC supply and RS-485 pair, assign the address and baud rate, set each channel type and test with a milliamp meter. Check the loop resistance and the terminals at routine inspections and keep the watchdog setting enabled so outputs go to a defined state if communication is lost.
Ordering notes
Quote the quantity of Advantech ADAM-4024 and tell us whether current or voltage outputs will be used, so that the application can be checked against the load limits.
Related items you may also need: Advantech ADAM-6017 8-Channel Analog Input Ethernet I/O Module | Advantech ADAM-6050 12DI/6DO Ethernet Digital I/O Module | Advantech ADAM-4055 16-Channel Isolated Digital I/O Module with Modbus | All Advantech products.
Documents and quotation
The manufacturer datasheet attached to this page covers both the ADAM-4021 and ADAM-4024. Send an RFQ with the part number Advantech ADAM-4024 and the quantity to receive a quotation.
Datasheets & Documents
- Datasheet Advantech ADAM-4024 4-Channel Analog Output Module Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Advantech is the Taiwanese maker of industrial computers and IoT hardware: ADAM remote I/O modules, EKI industrial Ethernet switches and serial device servers, industrial PCs, panel PCs and embedded boards. It was founded in Taipei in 1983 by K.C. Liu and partners, and today Advantech Co., Ltd. is headquartered in Taipei and listed on the Taiwan Stock Exchange.
Seven Star LLC supplies Advantech automation products to system integrators and plant teams in Oman, and this page lists items such as an ADAM-6000 Ethernet I/O module, an ADAM-4000 serial converter and an IPC rackmount chassis.
Advantech company profile
| Founded | 1983, Taipei, Taiwan |
|---|---|
| Founder | K.C. Liu and partners |
| Headquarters | Taipei, Taiwan |
| Ownership | Advantech Co., Ltd., public company listed on the Taiwan Stock Exchange |
| Product families | ADAM-4000 and ADAM-6000 remote I/O, EKI managed and unmanaged switches and serial device servers, industrial PCs and rackmount computers, panel PCs, embedded boards and edge gateways |
Advantech ADAM and IPC products listed here
The ADAM-6017 is an 8-channel analog input module from the ADAM-6000 Ethernet I/O family. It brings voltage and current signals onto a network and is read by SCADA or PLC software over Modbus TCP. The ADAM-4520 belongs to the ADAM-4000 serial family and converts RS-232 to isolated RS-422 or RS-485, a common fix for linking a PC or panel to field devices. The IPC-623 is a 4U, 20-slot rackmount chassis that houses a backplane, CPU card and expansion cards for control room computers.
Advantech products we list
Ordering Advantech hardware: what we need
Send the full part number with its suffix. Advantech adds letters after the model, as in ADAM-6017-D, to mark the hardware revision, and existing configurations sometimes depend on it. For an IPC chassis, state the backplane, power supply and drive bay arrangement, since these are ordered as specific versions. We supply across the GCC and check part numbers against Advantech documentation.
Facts checked against Advantech's published corporate profile, October 2026.
Browse Advantech products by category: Industrial Computer, PLC & I/O Cards, Industrial Communications.
FAQ
Questions about the Advantech ADAM-4024 4-Channel Analog Output Module
Answers from our engineering team on installation, compatibility and integration.
01How many analog outputs does the Advantech ADAM-4024 have?
It has four analog output channels, each configurable for current or voltage output, plus four digital inputs on the same module.
02What is the maximum current loop load of the ADAM-4024?
The datasheet gives a maximum current load resistor of 500 ohm; voltage outputs need at least 1 kilohm load.
03Can the ADAM-4024 sink and source current?
Yes. Sink or source type is selectable for each current output channel.
04What digital input types does the ADAM-4024 accept?
Four channels, each selectable as dry contact or wet contact; a wet contact reads 10 to 30 VDC as logic 1.
05What does the ADAM-4024 output slope setting do?
It lets the module ramp outputs at a programmed rate, 0.125 to 128 mA per second or 0.0625 to 64 V per second.


















Reviews