Brand:

Hochiki CHQ-MRC2/DIN(SCI) Fail Safe Mains Relay Controller

Description

Overview

Fire alarm systems do more than ring bells: they release door magnets, shut down air handlers, close dampers and drop plant supplies. The Hochiki CHQ-MRC2/DIN(SCI) is the loop-powered relay module that gives an ESP addressable panel a single mains-rated contact for those jobs, in a DIN rail housing for cabinet installation. Seven Star LLC is an independent supplier serving Oman and the GCC. It adds a monitored auxiliary input, an integral short-circuit isolator and fail safe relay control where the panel allows it.

What the Hochiki CHQ-MRC2/DIN(SCI) provides

The relay contact is rated 250 V AC at 5 A resistive and 48 V DC at 2 A resistive. For mains switching, the datasheet notes that the control panel must comply with the Low Voltage Directive for SELV circuits. The monitored input suits local power supply fault monitoring or use as a general input, with a 10 kilohm end-of-line resistor and thresholds of 470 ohms for ON, below 50 ohms for a short and above 100 kilohms for an open circuit. Addressing is through DIL switches. No fuse is fitted, so the relay circuit must be protected by a suitable over-current device.

Hochiki CHQ-MRC2/DIN(SCI) specification table

Item Datasheet value
Ordering codes CHQ-MRC2(SCI) module; CHQ-MRC2/DIN(SCI) DIN module
Operating voltage 17 to 41 V DC
Low power mode 100 microamps at 0.75 s
Quiescent current 300 microamps typical
Polling current 22 mA plus or minus 20 percent
Current in short circuit 8 mA; maximum 1 A
Relay rating 250 V AC 5 A resistive; 48 V DC 2 A resistive
Input end-of-line 10 kilohms, 5 percent, 0.25 W
Operating and storage temperature minus 10 to plus 50; minus 30 to plus 60 degrees C
Humidity 95 percent RH non-condensing at 40 degrees C
DIN module weight and size 145 g; 119 by 108 by 24 mm
Material Green ABS for the DIN module

How the Hochiki CHQ-MRC2/DIN(SCI) differs from the enclosed CHQ-MRC2(SCI)

The wiring and ratings are common, but the housing is not. The enclosed module weighs 360 g and measures 157 by 127 by 35 mm with lid, and can be fitted in the CHQ-BACKBOX to comply with BS 7671, reaching 79 mm in depth and 235 g more. The DIN module weighs 145 g and measures 119 by 108 by 24 mm, and has no lid. Because it carries mains-rated terminals, the DIN version belongs in a cabinet that keeps live parts away from accidental touch.

Typical duties in Oman and the GCC

Common uses are shutting down air handling units and extract fans on fire, releasing electromagnetic door holders, dropping non-essential supplies and signalling a building management system. In regional plants with large HVAC systems, an interface relay close to the motor starter keeps the control cable short. Check relay loads against the resistive ratings; inductive loads such as contactor coils or motors should be switched through a suitable interposing contactor with surge suppression.

Installation and commissioning

Install the module in a cabinet with proper separation between mains and loop wiring. Connect the loop terminals, wire the relay contact and input, set the address on the DIL switches, and add the over-current protection the datasheet calls for. During commissioning, confirm the fail safe behaviour and the relay state with the panel, remembering that fail safe operation depends on panel compatibility. Check the monitored input with and without the supply that it supervises.

Using the monitored input

The auxiliary input is easy to overlook, yet it gives the panel supervised information from the field. A common use is to watch the supply of the controlled equipment, such as the control voltage of a door magnet power unit, so that the panel raises a fault when the supply fails and the relay can no longer be trusted. It can also read the status of a contact on the damper or fan starter to confirm that the commanded action took place. With the 10 kilohm end-of-line resistor in place, the panel can tell a normal open state from a cut cable or a short, which are reported as faults.

Maintenance

Periodically operate the relay through the panel, verify that the controlled equipment responds, and inspect contact terminals for heat discolouration. Replace modules whose relay contacts have been used beyond the rated load.

Fail safe operation and why it matters

A normal relay output energises to act. A fail safe output acts when power or the loop is lost, so a damper closes or a fan stops even if the cable is cut. This is attractive for life safety shutdowns, but it needs support from the panel, and the datasheet therefore asks users to check compatibility. Decide for each controlled device which state is safe, document it and test it on site.

Protecting the contact and the controlled equipment

The relay is a dry contact without fuse, so the designer decides what protects it. Fit a fuse or breaker upstream of the contact that is sized for the load and for the contact rating of 5 A on mains. Where the controlled device is a coil or motor, add suppression across the load to limit the arc on opening, and consider an interposing contactor so that the module relay only switches the coil current. Keep mains and extra low voltage wiring separated inside the cabinet with barriers or spacing in line with the wiring rules applied on the project, and label the terminals clearly for the service crew. In Gulf climates, check that the cabinet temperature does not push the module above its operating limit of 50 degrees C when the cabinet carries other heat sources such as power supplies.

After installation, record the load connected to each module in the loop schedule so that future changes do not overload the contact.

Ordering notes for Hochiki CHQ-MRC2/DIN(SCI)

Quote the DIN code exactly. The enclosed module, the CHQ-BACKBOX and the white lid are separate items.

Related items you may also need: Hochiki CDX FIREbeam Conex Conventional Beam Smoke Detector | Hochiki CDX FIREbeam Xtra Conventional Beam Smoke Detector | Hochiki ACD-EN Intelligent Multi Sensor | All Hochiki products.

Documents and quotation

The manufacturer datasheet covering the Hochiki CHQ-MRC2/DIN(SCI) is attached to this page. Send your RFQ with the part number, quantity and delivery location in Oman or the GCC.

Other Models in the CHQ Modules Range

Seven Star LLC supplies models from the CHQ Modules range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Hochiki CHQ-DIM2/DIN(SCI) Dual Input Module, DIN RailFire & Gas DetectorsView details
Hochiki CHQ-SZM2/DIN(SCI) Addressable Single Zone ModuleFire & Gas DetectorsView details
Hochiki CHQ-MRC2/DIN(SCI) Fail Safe Mains Relay ControllerFire & Gas DetectorsYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Hochiki CHQ-MRC2/DIN(SCI) Fail Safe Mains Relay Controller Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Hochiki is a Japanese fire detection company, established in Tokyo in 1918 as Japan's first fire alarm manufacturer, with leading insurance companies among its founders. It makes smoke and heat detectors, beam detectors, addressable fire alarm systems and emergency lighting. Hochiki America has operated in the US since 1972.

Seven Star LLC is an independent supplier in Muscat. We list Hochiki detectors for fire alarm contractors in Oman and the GCC.

Hochiki company profile

Founded 1918, Tokyo, Japan
Founders Members of Japan's insurance industry
US operations Since 1972
Systems Conventional and addressable fire detection
Product families ESP intelligent detectors and multi-sensors, FIREbeam beam detectors, CDX conventional detectors, control panels

Milestones

  • 1918: Hochiki is founded in Tokyo.
  • 1972: Hochiki America begins US operations.

Hochiki product series

The ACD-EN is an intelligent multi sensor detector for Hochiki addressable systems.

Beam smoke detectors include the CDX FIREbeam Conex and CDX FIREbeam Xtra conventional detectors and the ESP FIREbeam Xtra addressable detector.

Multi sensor detectors combine smoke and heat sensing to detect different fire types and reduce false alarms. Beam detectors send an infrared beam across an open space and alarm when smoke reduces the signal, covering large areas with fewer devices.

Detectors must match the panel protocol and be installed and tested to the local fire code.

Where Hochiki detectors are used

Offices, hotels, schools and hospitals, and large open spaces such as warehouses, atriums and halls where beam detectors cover long distances.

Hochiki products we list

Family Examples
Fire & Gas Detectors ACD-EN Intelligent Multi Sensor, CDX FIREbeam Conex Conventional Beam Smo…, ESP FIREbeam Xtra Addressable Beam Smoke…

Ordering Hochiki detectors: what we need

Send the part number, protocol (conventional or ESP addressable), the beam range and the panel in use.

Facts checked against IFSEC Global centenary coverage and Hochiki company profiles, October 2026.

FAQ

Questions about the Hochiki CHQ-MRC2/DIN(SCI) Fail Safe Mains Relay

Answers from our engineering team on installation, compatibility and integration.

01What relay rating does the Hochiki CHQ-MRC2/DIN(SCI) have?
The relay contact is rated 250 V AC at 5 A resistive and 48 V DC at 2 A resistive, and no fuse is fitted so over-current protection is required.
02Does the Hochiki CHQ-MRC2/DIN(SCI) have a monitored input?
Yes. It has an auxiliary monitored input using a 10 kilohm end-of-line resistor, with an ON threshold of 470 ohms.
03Is the Hochiki CHQ-MRC2/DIN(SCI) loop powered?
Yes. It operates on 17 to 41 V DC from the loop, draws 300 microamps typical quiescent, and has an integral short-circuit isolator.
04How big is the Hochiki CHQ-MRC2/DIN(SCI)?
The DIN module weighs 145 g and measures 119 by 108 by 24 mm in green ABS.
05Does the Hochiki CHQ-MRC2/DIN(SCI) support fail safe control?
It provides fail safe relay control, but the datasheet asks users to check control panel compatibility for fail safe operation.