- Automation & ControlView all 1,923 products
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- Isolator & Barrier
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- HMI Displays
- Industrial Computers
- Motor Soft Starters
- Servo Drives
- Pneumatic Cylinders
- Machine Vision
- Automation Software
- Robotics
Brand: ABB
ABB MS132-25 Manual Motor Starter 20-25 A
Description
MS132-25 manual motor starter for 11 kW motors
MS132-25 sets between 20 and 25 A, the range that matches 11 kW motors at 400 V (about 22 A). It is the only MS132 below 32 A where ABB changes the short-circuit rating: Icu and Ics are 50 kA at 230 V and 400 V, not 100 kA, and a 100 A gG back-up fuse is listed.
The thermal setting is adjustable, trip class is 10, and the magnetic trip is fixed at 300 to 450 A. A lockable handle and ON/OFF/TRIP indication are standard.
For a quotation, send the order code 1SAM350000R1014 together with the motor nameplate current and the supply voltage. Seven Star LLC supplies this motor starter as an independent supplier in Muscat, and stock and delivery time are confirmed in the written quotation.
Technical specifications
| Parameter | Specification |
|---|---|
| Type designation / order code | MS132-25 / 1SAM350000R1014 |
| Device type | Manual motor starter (motor protection circuit breaker), 3-pole, thermal + magnetic release |
| Setting range (thermal overload) | 20…25 A |
| Trip class | 10 (IEC/EN 60947-4-1) |
| Rated instantaneous short-circuit setting Ii | 300…450 A |
| Rated operational voltage Ue | 690 V AC; 250 V DC (3 poles in series); Ui 690 V; Uimp 6 kV |
| Short-circuit breaking capacity (Ics / Icu) | 230 V: 50/50 kA, back-up gG 100 A; 400 V: 50/50 kA, back-up gG 100 A; 690 V: 3/3 kA |
| Resistance / power loss per phase | 0.0045 Ohm; 1.8 W (20 A) / 2.8 W (25 A) |
| Connection capacity | Solid 1/2 x 2.5…6 mm2; flexible with ferrule 1/2 x 1…6 mm2 |
| Tightening torque / stripping | 2 Nm; stripping 10 mm; M4 Pozidriv 2 |
| Weight | 310 g (data sheet packing weight) |
| Mounting | 35 mm DIN rail (EN 60715), any position 1-6; 0 mm side-by-side, 150 mm vertical spacing between same-type units |
| Ambient temperature | Operation -25…+60 C compensated (to +70 C open); storage -50…+80 C; altitude up to 2000 m |
| Durability / protection | Mechanical 100 000 operations; electrical 50 000 (data sheet: 10^5 / 5 x 10^4); IP20 enclosure and terminals; utilization category A |
| Standards | IEC/EN 60947-1, 60947-2, 60947-4-1; UL 508; CSA C22.2 No. 14 |
| Approvals (as printed) | cULus, ABS, GL, GOST-R, CE |
Short-circuit data and what it means for the panel
If prospective fault current in your panel is below 50 kA, the MS132-25 stands alone. Above that, ABB specifies a 100 A gG fuse upstream, which then covers up to 100 kA according to the table note. At 690 V the rating is only 3 kA, so use it at 400 V class systems.
Power loss is 1.8 W per phase at 20 A and 2.8 W at 25 A. Terminals accept 2.5 to 6 mm2 solid and 1 to 6 mm2 flexible with ferrule, tightened to 2 Nm.
Selecting around the 25 A frame
The MS132-20 covers 16 to 20 A and the MS132-32 25 to 32 A. For a starter, combine the MS132-25 with an AF contactor so the motor can be switched remotely, while the starter provides protection and a visible isolation point.
Confirm that the motor current at your voltage lies inside 20 to 25 A, not at the extreme end.
Documents and quotation
The linked file is ABB MS132 manual motor starter data sheet 2CDC131021D0201. Seven Star LLC supplies the MS132-25 on request from Muscat; availability and lead time are stated in the quotation. For other protection devices see the Circuit Breakers category, for example the ABB Tmax XT moulded case circuit breakers.
Confirm before ordering: motor full-load current inside the setting range, the available fault level at the panel, whether the HKF1 auxiliary contact is needed, and the terminal type.
Datasheets & Documents
- Datasheet ABB MS132 manual motor starter data sheet 2CDC131021D0201 Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.
ABB company profile
| Formed | 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50% |
|---|---|
| ASEA | Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators |
| Brown, Boveri & Cie | Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri |
| Headquarters | Zurich, Switzerland; ABB Ltd became the group holding company in 1999 |
| Ownership | Public company listed on SIX Swiss Exchange and Nasdaq Stockholm |
| Brands in the group | Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers |
| Product families | Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots |
Milestones
- 1883: ASEA is founded in Västerås, Sweden.
- 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
- 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
- 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
- 2011 and 2017: Baldor Electric and B&R join ABB.
- 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.
Choosing an ABB drive
ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.
Where ABB products are used
In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.
ABB products we list
| Family | Examples |
|---|---|
| AC drives | ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module |
| Breakers, motor control and protection | SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay |
| Flow measurement | ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500 |
| Pressure, temperature and level | 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge |
| Analysers | Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210 |
| Control systems and actuators | AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000 |
Ordering ABB products: what we need
Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.
Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.
FAQ
Questions about the ABB MS132-25 Manual Motor Starter 20-25 A
Answers from our engineering team on installation, compatibility and integration.
01What is the setting range of the MS132-25?
20 to 25 A with trip class 10 and a 300 to 450 A magnetic release.
02What is the short-circuit capacity at 400 V?
50 kA Ics and Icu at 230 and 400 V, with a 100 A gG back-up fuse listed.
03What is its order code?
1SAM350000R1014 per the ABB ordering table.
04What conductor sizes does it accept?
Solid 2.5 to 6 mm2 and flexible with ferrule 1 to 6 mm2, 2 Nm torque.
05Which motor does it suit?
Roughly 11 kW at 400 V, if the motor current falls inside the 20-25 A scale.


















Reviews