Brand: Carlo Gavazzi
Carlo Gavazzi EM340DINAV23XS1X Three-Phase Energy Meter RS485
Description
A 65 A direct-connection three-phase meter in three DIN modules
The Carlo Gavazzi EM340DINAV23XS1X is the standard (non-MID) RS485 version of the EM340 three-phase energy meter. It measures up to 65 A directly, without current transformers, on three-phase systems from 208 to 400 V line to line, and is only three DIN modules wide (54 mm). A backlit LCD with three rows of eight digits and an integrated touch keypad shows energy and electrical variables.
The meter is aimed at cost allocation, sub-metering of tenants or production lines, and monitoring of motor feeders, pumps and small distribution boards. Active energy is class 1 (EN 62053-21) and class B (EN 50470-3), reactive energy is class 2, and current and voltage accuracy is +/-0.5% of reading. The unit is self powered from the measured voltage, so no separate auxiliary supply is needed.
Technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / series | Carlo Gavazzi, EM340 |
| Model / ordering key | EM340-DIN AV2 3 X S1 X (EM340DINAV23XS1X) |
| Range code AV2 | 208 to 400 V AC line to line, 5(65) A, direct connection |
| System 3 | 3-phase, 3 or 4 wire; 2-phase 3 wire |
| Power supply X | Self powered: -20% +20% of rated measuring voltage, 45 to 65 Hz; consumption 1 W / 10 VA max. |
| Output S1 | RS485 Modbus RTU port (O1 pulse output and M1 M-bus versions also exist) |
| Active energy accuracy | Class 1 (EN 62053-21); class B (EN 50470-3) |
| Reactive energy accuracy | Class 2 (EN 62053-23) |
| Current / voltage accuracy | +/-0.5% of reading; phase-phase voltage +/-1% |
| Current range | Imin 0.25 A, Ib 5 A, Imax 65 A; continuous overload 65 A at 50 Hz |
| Measured values | kWh and kvarh imported/exported, kWh by two tariffs, kWh per phase; kW, kvar, kVA, VLL, VLN, A, PF, Hz, kW demand and demand peak |
| Display | Backlit LCD, 3 rows of 8 digits; touch keys (down, enter, up); energy 8 digits, variables 4 digits |
| Sampling rate | 4096 samples/s at 50 or 60 Hz |
| Digital input | 1 free-of-voltage contact for tariff management |
| Modbus RS485 | Modbus RTU slave; 9.6 to 115.2 kbaud; address 1 to 247; 50 words per read |
| Wiring checks | Wrong connection detection, phase sequence and current direction indication |
| Operating temperature (X option) | -25 to +65 C indoor, R.H. 0 to 90% non-condensing at 40 C |
| Storage temperature | -30 to +80 C |
| Insulation / overvoltage | 4000 Vac for 1 minute; overvoltage category III; utilisation category UC2 |
| Connection terminals | Measuring inputs 2.5 to 16 mm2 (2.8 Nm); other terminals 1.5 mm2 |
| Housing | Noryl UL 94 V-0, 54 x 90 x 63 mm (W x H x D), 3 DIN modules; IP51 front, IP20 terminals |
| Weight | Approx. 240 g (packing included) |
| Compliance | EN 62052-11, EN 62053-21, EN 50470-3; CE; MID only for PF-option versions |
Choosing between EM340 versions
The type code selects the communication and certification. The S1 output used here is an RS485 Modbus RTU port, O1 is an open-collector pulse output and M1 is an M-bus port. Versions with the PF option are certified to the MID directive (module B and D, class B, annex V MI003) and can be used for fiscal or legal metrology; the code on this page has the X option, so it is not MID certified and should not be used for legal metrology. Check the how-to-order table before quoting a different version.
The datasheet explains the A and B measurement modes for MID versions: A integrates power always, whether imported or exported, while B counts only positive energy. In standard X versions the measurement menu can be set to A or B, which determines whether energy from a wrongly connected current direction is added to the import total.
Installation and selection points
Because the meter measures up to 65 A directly, the load wires pass through the meter terminals, so confirm that the conductor size (2.5 to 16 mm2) and a suitable short-circuit protective device are in place. For loads above 65 A the EM340 direct-connection range stops, and a CT-operated analyzer is needed. The Modbus port supports up to 247 devices on one bus, with a data refresh time of 1 second, which suits energy management systems and SCADA gateways. Allow for the DIN rail space (3 modules) and ventilation in warm panels.
How the EM340DINAV23XS1X works
The meter measures the line voltage and the load current in each phase. It multiplies them to find power and adds the power over time to find energy. The results go to the display and to the RS485 port.
Where the EM340DINAV23XS1X is used
- Cost allocation
- Tenant sub-metering
- Production line metering
- Motor feeders
- Pumps and small distribution boards
Selection checklist for the EM340DINAV23XS1X
- System voltage
- Load current
- Direct or transformer connection
- Wire count
- Output type
- Tariff need
- Panel space
- Communication address plan
Installation, commissioning and maintenance notes for the EM340DINAV23XS1X
Clip the meter on the DIN rail and connect the phases and the neutral. Set the Modbus address and the baud rate. Check the wiring indication and the readings at regular intervals.
Requesting a quotation for the EM340DINAV23XS1X
Please send the system voltage, the load current and the output needed. Seven Star LLC serves industrial customers in Oman and the GCC and replies with a quotation based on the information provided.
Quick facts: EM340DINAV23XS1X
| Device type | It is a three-phase energy meter. |
|---|---|
| Series | It belongs to the EM340 series. |
| Output | It has an RS485 Modbus RTU port. |
| Direct connection | It measures up to 65 A without current transformers. |
| Voltage | It works on systems from 208 to 400 V line to line. |
| Systems | It serves three-phase systems with three or four wires. |
| Width | It is only three DIN modules wide, which is 54 mm. |
| Display | A backlit LCD shows three rows of eight digits. |
| Keypad | An integrated touch keypad sets the meter. |
| Power supply | The meter is self powered from the measured voltage. |
| Energy values | It measures kWh and kvarh, imported and exported. |
| Tariffs | It stores kWh in two tariffs. |
| Tariff input | One digital input switches the tariff. |
| Other values | It also shows power, voltage, current, power factor and frequency. |
| Demand | It calculates kW demand and the demand peak. |
| Sampling | The sampling rate is 4096 samples per second. |
| Baud rate | The baud rate is 9.6 to 115.2 kbaud. |
| Address range | Modbus addresses run from 1 to 247. |
| Wiring check | It detects a wrong connection and shows the phase sequence. |
| Temperature | Operating temperature is minus 25 to plus 65 degrees C. |
| Meter records for the EM340DINAV23XS1X | Record the Modbus address, the meter readings and the date of each check. |
| Choosing the right EM340DINAV23XS1X version | Choose the output version from the data system in use. |
Documents and quotation
The attached EM340 datasheet gives the full ordering key, accuracy tables, Modbus and M-bus specifications, display pages and dimensions. When requesting a price for the EM340DINAV23XS1X, send the quantity, the system voltage, the maximum current per feeder and the communication needed. See also Automation Accessories and the Carlo Gavazzi EM540 three-phase energy analyzer, which is used with current transformers.
Datasheets & Documents
- Datasheet Carlo Gavazzi EM340 datasheet (EN) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Carlo Gavazzi is an international group making electronic components for industrial and building automation, founded in 1931 in Milan, Italy. The group's holding company, Carlo Gavazzi Holding AG, is based in Steinhausen, Switzerland, and has been listed on the SIX Swiss Exchange since 1996. Its sensors, relays and energy meters are used in machinery, HVAC, solar and building systems.
Seven Star LLC is an independent supplier in Muscat. We list Carlo Gavazzi components for panel builders and building services contractors in Oman and the GCC.
Carlo Gavazzi company profile
| Founded | 1931, Milan, Italy |
|---|---|
| Headquarters | Steinhausen, Switzerland (Carlo Gavazzi Holding AG) |
| Listing | SIX Swiss Exchange, since 1996 |
| Markets | Industrial automation and building automation |
| Product families | RG and RM solid-state relays, CA capacitive and ICB inductive proximity sensors, DPA and DPB monitoring relays, EM24 and EM340 energy meters, Dupline field bus, timers and soft starters |
Milestones
- 1931: Carlo Gavazzi is founded in Milan.
- 1996: Carlo Gavazzi Holding lists on the Swiss exchange.
Carlo Gavazzi product series
Energy meters include the EM340DINAV23XS1X three-phase meter with RS-485, the EM540DINAV23XS1PFA three-phase MID energy analyzer, the EM111DINAV81XS1X single-phase analyzer and the WM50AV53HBC multichannel power analyzer.
Switching and control includes the RM1A48D50 50 A solid state relay, the RGC1A60D25KKE 25 A solid state contactor, the RSGT4025E0V10C 25 A three-phase soft starter and the DPB01CM44 three-phase voltage monitoring relay. The ICB12S30N04NO is an M12 inductive proximity sensor.
Solid state relays and contactors switch heaters and other resistive loads silently and with long life, while soft starters reduce starting current and mechanical shock on pumps and fans. Carlo Gavazzi energy meters and analyzers are available with MID approval for billing and with Modbus RTU, Modbus TCP or M-Bus for building management systems.
Where Carlo Gavazzi products are used
Energy sub-metering in buildings, heating and process control with solid state switching, pump and fan soft starting, phase and voltage supervision of motors, and object detection on machines.
Carlo Gavazzi products we list
Ordering Carlo Gavazzi products: what we need
Send the full ordering code, which defines input, supply, outputs and communication, or give the voltage, current, load type and interface needed.
Facts checked against Carlo Gavazzi Holding company profiles, October 2026.
Browse Carlo Gavazzi products by category: Automation Accessories, Contactors & Overload Relays, Inductive Proximity Sensors.
FAQ
Questions about the Carlo Gavazzi EM340DINAV23XS1X Three-Phase Energy
Answers from our engineering team on installation, compatibility and integration.
01Is this version MID certified?
No. The X option is not MID certified; only versions with the PF option are.
02What is the maximum direct current?
65 A per phase, with a 5 A base current and 0.25 A minimum.
03What communication does it have?
An RS485 port with Modbus RTU slave, addresses 1 to 247 and 9.6 to 115.2 kbaud.
04How is it powered?
It is self powered from the measured voltage of 208 to 400 V line to line, -20% to +20%.
05How wide is it?
Three DIN modules, 54 mm, with a 90 mm height and 63 mm depth.


















Reviews