Yokogawa FW1012-4-2-H-D 12-Channel Paperless Recorder
Description
FW1012-4-2-H-D: what you receive
The Yokogawa FW1012-4-2-H-D is a twelve-channel paperless recorder from the FW1000 series. Its code reads as a recipe: FW1012 for twelve channels, -4 for a CompactFlash slot including a 512 MB card, -2 for the multi-language interface with degF and daylight-saving rules, -H for 1000 VAC isolation between measuring inputs and -D for a UL/CSA power cord. The recording unit stores trend data in a 400 MB internal file area and copies it to the card, and the datasheet photo shows a compact case with a carrying handle on top. Information below is from Yokogawa GS 04L24B01-01EN (May 2026 revision).
Scan and measurement
On the twelve-channel FW1012-4-2-H-D the scan interval is 1 s, 2 s or 5 s. A/D integration may be AUTO (the recorder follows mains frequency), 50 Hz, 60 Hz or 100 ms; selecting 100 ms restricts the scan to 2 s or 5 s. The FW1012-4-2-H-D accepts DC voltage ranges of 20 mV, 60 mV, 200 mV, 1 V, 2 V, 6 V, 20 V and 50 V, a 1 to 5 V range, thermocouples R, S, B, K, E, J, T, N, W, L, U and WRe, Pt100 and JPt100 RTDs, level or contact ON/OFF inputs and, with a shunt, DC current. Burnout detection on the FW1012-4-2-H-D (detection current about 10 microamps) can be chosen upscale or downscale per channel, and scaling spans minus 30000 to 30000.
Technical data for FW1012-4-2-H-D
| Channels | 12 |
|---|---|
| Scan interval | 1 s, 2 s, 5 s |
| Display | 5.7-inch TFT color LCD, 240 x 320 dots |
| Internal memory | 400 MB file storage |
| External medium | CF card slot with 512 MB card (suffix -4) |
| Case | Metal plate; bezel and cover polycarbonate |
| Size | 144 W x 189.3 H x 184 D mm |
| Weight | 2.3 kg without options |
| Supply | 100 to 240 VAC rated, 90 to 264 VAC allowed, 50/60 Hz |
| Consumption at 100 VAC | 10 VA backlight off, 15 VA normal, 35 VA maximum |
| Consumption at 240 VAC | 15 VA, 20 VA and 45 VA |
| Operating ambient | 0 to 50 C; 20 to 80 percent RH |
| Operating altitude | 2000 m or less; indoor use |
| Mounting position | Left and right horizontal |
| Warm-up | At least 30 minutes |
| Clock accuracy | 50 ppm from 0 to 50 C |
| Messages | 100 stored in the message summary |
How FW1012-4-2-H-D differs from other FW1000 models
The FW1002, FW1004, FW1006 and the FW1012 base of FW1012-4-2-H-D share an identical case of 2.3 kg. The first two scan at 125 ms or 250 ms and the other two at 1 s to 5 s, with the 100 ms integration option reserved for the six and twelve channel types. The /N2 three-leg isolated RTD option cannot be added to the FW1002 or FW1004. In the order string, FW1012-4-2-H-D differs from a -0 version in that it includes the CF slot, from a -7 version in that it uses CF media (512 MB) rather than an SD card (1 GB), and from a -L version in that its input withstand level is 1000 VAC rather than 400 VAC.
Alarm, display and data handling
Alarms on the FW1012-4-2-H-D support high, low and rate-of-change limits with delay from 1 to 3600 s, hysteresis of 0.0 to 5.0 percent of span, and an AND/OR internal switch that can drive the optional relay or status output. Display options include trend, digital, bar graph and report screens, a message summary, an alarm summary and historical trend recall of display or event data; the trend can be changed in time axis and the background switched among white, cream, black or light gray. If data must leave the recorder, the datasheet states the unit needs /C2, /C7 or /USB1 for loading; the FW1012-4-2-H-D itself can also be read from the CF card in a PC.
Where a twelve-channel paperless recorder helps
Practical uses for the FW1012-4-2-H-D in the Gulf include heat treatment and kiln logging, chiller and cooling tower monitoring, environmental chambers, and pump or tank farm records that must be kept for audits. The 1000 VAC input isolation of the -H code is the reason to choose this string over the -L code when channels share a plant with higher common-mode voltages. The compact 144 mm front also lets a FW1012-4-2-H-D replace chart recorders in standard cut-outs.
Options and constraints
- /C2 RS-232, /C7 Ethernet and /USB1 USB (one port) cover communication.
- /M1 adds mathematical and report functions; /PM1 adds three pulse inputs and five remote control points, and cannot be combined with /M1, /R1 or /PWR5.
- /R1 gives eight remote control points; /PWR5 is a power monitor option that excludes /F1, /R1, /PM1 and /M1.
- /N3F extended inputs without Pt1000, /CC1 calibration correction and /LG1 log scale (vacuum gauges need /LG1 together with /CC1).
- /F1 is a fail and status relay output, energized in normal operation and de-energized on a system error, with a status output for conditions such as low memory, memory failure or a media error.
- /N2 serves three-leg RTD wiring and, being barred on the FW1002 and FW1004, is available to the twelve-channel FW1012-4-2-H-D family. Check every slash code against the conflicts above before you send an RFQ for a FW1012-4-2-H-D with options.
Installation and servicing of FW1012-4-2-H-D
Mount the FW1012-4-2-H-D indoors at 2000 m or lower, give it 30 minutes of warm-up before accuracy checks, and keep ambient within 0 to 50 C. The recorder complies with UL 61010-1 and CSA C22.2 No. 61010-1 (overvoltage category II, pollution degree 2, measurement category II) as stated in the datasheet. For service, keep a saved setup, retain the manual set supplied (user manual and installation guide), and record the complete string FW1012-4-2-H-D so a spare matches the card slot, isolation code and cord type.
Documents and quotation
The Yokogawa datasheet GS 04L24B01-01EN is attached for download. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Send an RFQ stating FW1012-4-2-H-D, any slash options and the quantity.
Datasheets & Documents
- Datasheet Yokogawa FW1012-4-2-H-D Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.
Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.
Yokogawa at a glance
| Established | 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki |
|---|---|
| Milestones | Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986 |
| Headquarters | Tokyo, Japan |
| Product families | Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers |
Yokogawa products we list
| Family | Models | Typical use |
|---|---|---|
| Pressure and DP transmitters | EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable | Pressure, level and DP flow measurement in process plants |
| Temperature transmitters | YTA610, YTA710 | RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus |
| Flowmeters | ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 | Water and conductive liquids, mass flow of hydrocarbons, steam and gas |
| Analysers | TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover | Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen |
| Controllers and recorders | UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 | Single-loop control, furnace programs and data recording |
| Control and safety systems | CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 | Spares and expansions for CENTUM DCS, safety systems and STARDOM |
| Battery packs | S9129FA, S9185FA, S9548FA | Memory backup batteries for DCS and controller modules |
The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.
Where Yokogawa products are used
In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.
Ordering Yokogawa products: what we need
Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.
Facts checked against Yokogawa's corporate history, October 2026.
Browse Yokogawa products by category: PLC & I/O Cards, Flowmeters, Pressure Instrumentation, Automation Accessories, Temperature Instrumentation.
FAQ
Questions about the Yokogawa FW1012-4-2-H-D 12-Channel Paperless
Answers from our engineering team on installation, compatibility and integration.
01How is the FW1012-4-2-H-D order string built?
FW1012 is the twelve-channel body with a 1 s shortest interval, -4 adds a CF card slot with a 512 MB card, -2 selects the ten-language interface with degF and DST, -H gives 1000 VAC input withstand and -D supplies a UL/CSA power cord.
02What does the -H code mean on the FW1012-4-2-H-D?
It sets the withstanding voltage between measuring input terminals to 1000 VAC (50/60 Hz) for one minute; the alternative -L code would give 400 VAC.
03Which scan settings are available on the FW1012-4-2-H-D?
Scan intervals of 1 s, 2 s and 5 s. The A/D integration time can be AUTO, 50 Hz, 60 Hz or 100 ms, and the 100 ms setting limits the scan interval to 2 or 5 seconds.
04Can the FW1012-4-2-H-D connect to Ethernet?
Only with the /C7 Ethernet option; without /C7 or /C2 (RS-232) or /USB1 the unit has no communication path for loading data, as the datasheet notes.
05How big is the FW1012-4-2-H-D?
The case is 144 mm wide, 189.3 mm high and 184 mm deep measured from the panel mounting plane, and it weighs 2.3 kg without options.