Brand:

Yokogawa UM33A Digital Indicator with Alarms

Description

Yokogawa UM33A is a digital indicator with alarms for panel mounting. It reads one universal input, shows it on a color LCD, compares it against eight alarm settings and can retransmit the value as a current signal, but it does not run a control loop. That makes the UM33A the right component when a plant needs a clear local readout and alarm contacts for a temperature, pressure or level signal without paying for control functions. The facts here come from the manufacturer’s General Specifications GS 05P03D21-01EN, 8th edition, March 2026.

What the Yokogawa UM33A does

The UM33A has one universal input that accepts thermocouples, RTDs, DC voltage, DC current and mV signals, with a selectable sampling period of 50, 100 or 200 ms. The 5-digit, 14-segment PV display switches between white and red, with characters 14.2 mm high, and sits above an orange 5-digit data display and a 12-segment bar graph. Measured-input computation adds bias of minus 100.0 to 100.0 percent of the input span, a first-order lag filter of 1 to 120 seconds, and a 10-segment linearizer approximation for non-linear signals.

UM33A alarm, contact and retransmission functions

  • Eight alarm settings with up to nine alarm output points depending on the model code
  • Alarm types: PV high/low limit, PV rate-of-change, self-diagnosis and FAIL
  • Stand-by action, latch with forced reset, hysteresis and ON/OFF delay timers per alarm
  • Contact inputs can reset peak and bottom values, release a latched alarm (ACK), switch the LCD backlight, change PV color, or call message interrupt displays 1 to 4
  • One retransmission output, 4 to 20 mA or 0 to 20 mA DC, shared with the 14.5 to 18.0 V DC loop supply
  • Max and min readings retained and displayed, resettable through a contact input

UM33A specifications at a glance

Model UM33A digital indicator with alarms
Universal inputs 1
Input sampling period 50, 100 or 200 ms
Allowable input TC, mV, mA or RTD input: plus/minus 10 V DC; V input: plus/minus 20 V DC; mA input: plus/minus 40 mA
Type K accuracy Plus/minus 0.1 % of instrument range plus/minus 1 digit at 0 degrees C or above (range -270.0 to 1370.0 degrees C)
Alarm relays Alarm 1 to 3: 1a contacts, 240 V AC 1 A or 30 V DC 1 A; alarm 4: 1c contact, 250 V AC 3 A or 30 V DC 3 A
Front dimensions 96 (W) x 48 (H) mm, depth 65 mm from the panel face
Panel cutout 92 +0.8/0 (W) x 45 +0.6/0 (H) mm
Weight 0.5 kg or less
Case Polycarbonate, flame retardancy UL94V-0; white (light gray) or black (light charcoal gray)
Power 100 to 240 V AC (+10 %/-15 %), 50/60 Hz; 24 V AC/DC with /DC option
Power consumption 15 VA (with /DC: 7 VA on DC, 11 VA on AC)
Ambient temperature -10 to 50 degrees C; 0 to 40 degrees C with the CC-Link option
Startup / warm-up Within 10 seconds / 30 minutes or more
Front protection IP66, NEMA4 hose-down only

Communication on the UM33A

The UM33A talks Modbus (RTU or ASCII) as a slave over RS-485, supports PC link and ladder communication, and offers an embedded CC-Link remote device interface (Ver. 1.10 and Ver. 2.00) for Mitsubishi Electric PLC networks. RS-485 runs from 600 to 38400 bps over up to 1200 m with an external 220 ohm terminator, and up to 31 units share a line. CC-Link baud rates run from 156 kbps to 10 Mbps, with the transmission distance shrinking from 1.2 km at 156 kbps to 100 m at 10 Mbps, and the node count reaches 42 remote devices. A Modbus master function lets the UM33A read data from UT and UP controllers on the same line.

How UM33A differs from other UTAdvanced units

The UM33A shares its display and navigation style with the UT55A, UT75A and UP55A but removes the control outputs. Its 48 mm height makes it a half-height unit, compared with the 96 x 96 mm front of the UT75A and UP55A, so two indicators can occupy the cutout area of a single controller. The PV character is 14.2 mm instead of the 21.5 mm of the larger units, which matters for operator reading distance. If a loop later needs control, the cutout will not match and the panel must be recut.

Use cases for UM33A in Oman and the GCC

Typical placements include furnace flue temperature indication with a high alarm tied to an interlock, chilled water temperature display in district-cooling plants, tank temperature monitoring at fuel depots, and motor winding temperature repeating in switchgear rooms. The CC-Link version suits factories that already run a Mitsubishi PLC and wish to bring several readings in without analog cards.

Installing and maintaining UM33A

Cut a 92 x 45 mm opening, slide the unit in from the front and secure the left and right brackets. Observe the mounting attitude of up to 30 degrees above horizontal with no downward tilt. Wire to the M3 screw terminals with square washers. Alarm 1 to 3 outputs need a load of at least 1 mA and alarm 4 needs at least 10 mA. Keep a parameter backup made with LL50A, and test alarm relays on a regular schedule.

Ordering UM33A

Please give the UM33A suffix code, supply voltage, communication option and quantity when you send an enquiry. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Documents and quotation

The manufacturer datasheet GS 05P03D21-01EN for the UM33A is available on this page. To request a quote, send an RFQ with the part number UM33A, the full model code and the quantity.

Ordering Checklist for the Yokogawa UM33A

Before you ask for a quotation for the Yokogawa UM33A, check the full order code on the nameplate of the unit you are replacing, the supply voltage, and the process or signal ranges your system expects. If this is an upgrade rather than a like-for-like swap, tell us the existing make and model so that mounting, wiring and connection details can be checked against the controllers & data acquisition already installed. For multi-unit orders, list the quantity per site and the delivery location in Oman or the wider GCC, so packing, paperwork and lead time can be confirmed in a single quotation.

Datasheets & Documents
  • PDF Datasheet Yokogawa UM33A Digital Indicator with Alarms Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.

Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.

Yokogawa at a glance

Established 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki
Milestones Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986
Headquarters Tokyo, Japan
Product families Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers

Yokogawa products we list

Family Models Typical use
Pressure and DP transmitters EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable Pressure, level and DP flow measurement in process plants
Temperature transmitters YTA610, YTA710 RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus
Flowmeters ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 Water and conductive liquids, mass flow of hydrocarbons, steam and gas
Analysers TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen
Controllers and recorders UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 Single-loop control, furnace programs and data recording
Control and safety systems CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 Spares and expansions for CENTUM DCS, safety systems and STARDOM
Battery packs S9129FA, S9185FA, S9548FA Memory backup batteries for DCS and controller modules

The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.

Where Yokogawa products are used

In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.

Ordering Yokogawa products: what we need

Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.

Facts checked against Yokogawa's corporate history, October 2026.

FAQ

Questions about the Yokogawa UM33A Digital Indicator with Alarms

Answers from our engineering team on installation, compatibility and integration.

01Is the Yokogawa UM33A a controller?
No. The UM33A is a digital indicator with alarms. It displays one universal input, drives alarm outputs and offers a retransmission output, but it does not run PID control.
02What is the panel cutout of the UM33A?
The cutout is 92 mm wide by 45 mm high (plus 0.8 and 0.6 mm tolerances). The case is 96 x 48 mm at the front and 65 mm deep behind the panel face.
03How many alarms does the UM33A offer?
It provides eight alarm settings, with up to nine alarm output points depending on the model code. Alarm 1 to 3 are 1a relays and alarm 4 is a 1c relay.
04Does the UM33A support CC-Link?
Yes. An embedded CC-Link remote device interface (Ver. 1.10 and Ver. 2.00) is available, with up to 42 nodes; with it the ambient range narrows to 0 to 40 degrees C.
05What signals can the UM33A read?
One universal input handles thermocouples, RTDs, DC voltage, DC current and mV inputs, with bias, a 1 to 120 s filter and a 10-segment linearizer available.