Schneider Electric LC1D115A6KUE 115 A Contactor 100-250 V AC/DC

Description

LC1D115A6KUE: 115 A TeSys Deca contactor with ring lugs and 100-250 V AC/DC coil

The LC1D115A6KUE is a Schneider Electric TeSys Deca contactor with ring lugs / busbars, a 100-250 V AC/DC coil and a 115 A AC-3 rating. The datasheet title reads: Contactor Deca 115A 3P 100-250V ACDC Lug. The LC1D115 is the 115 A frame of the TeSys Deca range, a heavy contactor rated 115 A in AC-3 and AC-3e at up to 440 V and 200 A in AC-1. It is built for motors of 55 kW at 400 V and for large resistive or capacitor-free switching duties, in a body 152 mm tall, about 99 mm wide and 155 mm deep. Seven Star LLC supplies the LC1D115A6KUE in Oman and the GCC as an independent supplier based in Muscat.

Reading the reference: LC1D115 is the 115 A TeSys Deca frame, the A6 group marks the ring lugs / busbars version, and KUE is the coil code for 100 to 250 V AC 50/60 Hz and 100 to 250 V DC. The same coil on the other terminal style is LC1D115AKUE. The datasheet gives a body of 152 x 99 x 155 mm (H x W x D) and a net weight of 2.2 kg.

Technical specifications of the LC1D115A6KUE

Parameter Specification
Manufacturer / part number Schneider Electric / LC1D115A6KUE
Description Contactor Deca 115A 3P 100-250V ACDC Lug
Range of product TeSys Deca Advanced (range: TeSys Deca)
Device short name LC1D
Product or component type Contactor
Contactor application Motor control; resistive load
Utilisation category AC-3; AC-3e; AC-1; AC-4; DC-1; DC-3; DC-5
Poles / contact composition 3P; 3 NO
Rated operational voltage [Ue] Power circuit: up to 1000 V AC (16.67 to 400 Hz); up to 300 V DC
Rated operational current [Ie] 115 A at <60 °C at up to 440 V AC (AC-3 and AC-3e); 200 A in AC-1
Control circuit voltage [Uc] 100 to 250 V AC 50/60 Hz and 100 to 250 V DC
Control voltage limits 0.8 Uc min to 1.1 Uc max operational; 0.1 Uc max drop-out (-40 to 60 °C)
Coil technology Built-in bidirectional peak limiting diode suppressor
Inrush power 170 VA; 105 W (at 20 °C)
Hold-in power 8 VA; 4.5 W (at 20 °C)
Motor power (AC-3), 400 V 55 kW at 400 V
Motor power, 60 Hz 75 hp at 460/480 V
Conventional free-air thermal current 200 A at 60 °C
Making / breaking capacity at 440 V 1560 A at 440 V / 1100 A at 440 V
Associated fuse rating 125 A aM at up to 440 V, 100 A aM at up to 690 V, 200 A gG at up to 690 V
Power dissipation 6 W per pole in AC-3, 22 W in AC-1
Mechanical durability 8 Mcycles
Electrical durability 1 Mcycles at 115 A AC-3; 0.5 Mcycles at 200 A AC-1
Maximum operating rate 2400 cycles per hour at 60 °C; 3600 at Uc, 20 °C
Operating time 20 to 90 ms closing; 10 to 80 ms opening
Power terminals Ring lugs (25 mm external diameter) or busbars 5 x 25 mm
Tightening torque (power) 12 N.m on M8 hexagonal head (13 mm)
Auxiliary contacts 1 NO + 1 NC, mechanically linked; NC mirror contact
Mounting support Plate
IP degree of protection IP20 front face (IEC 60529)
Protective treatment None (IEC 60068-2-30)
Ambient temperature -40 to 60 °C operation; 60 to 70 °C with derating; storage -60 to 80 °C
Operating altitude 0 to 3000 m without derating
Dimensions (H x W x D) 152 x 99 x 155 mm
Net weight 2.2 kg
Product certifications CB Scheme; CCC; cULus; CE; UKCA; EU-RO-MR by DNV-GL

Ring lugs and busbars on the LC1D115A6KUE

The power circuit of the LC1D115A6KUE is terminated with ring lugs (external diameter 25 mm) or with busbars of 5 x 25 mm cross section, and the datasheet specifies 12 N.m on the M8 hexagonal head (13 mm). That arrangement suits large fixed cable lugs crimped by the panel builder and busbar-connected starters, and it keeps the contact surface bolted rather than clamped. The contactor is plate-mounted only; the datasheet lists no rail mounting for this version.

In the references of this family, the A6 in the part number marks the lug and busbar version, in contrast to the connector version without the 6. This reading comes from the datasheet titles, which describe A6 references as ‘lugs-ring or bars’ and the others as ‘connector’.

100-250 V AC/DC coil and control circuit of the LC1D115A6KUE

The coil of the LC1D115A6KUE is a wide-range AC/DC type: 100 to 250 V AC 50/60 Hz and 100 to 250 V DC. The datasheet states operational limits of 0.8 Uc minimum to 1.1 Uc maximum and a drop-out at or below 0.1 Uc, over -40 to 60 °C, for both AC and DC. Applied to this range, 0.8 x 100 V is 80 V and 1.1 x 250 V is 275 V. The coil carries a built-in bidirectional peak limiting diode suppressor, so a separate suppressor is not normally needed. Pick the 100 to 250 V coil when the contactor will be driven straight from phase and neutral at 230/240 V and you also want the option of 110 V or 220 V DC control later. It avoids a control transformer in simple starters and keeps spare-part holdings small.

Commissioning check on a 100 to 250 V coil: confirm the control voltage lies between 80 V and 275 V at the coil while closing. On a 240 V AC supply this leaves a wide margin; on a 110 V system it leaves less margin at the bottom, so check for voltage drop in long runs.

Wiring a 100 to 250 V coil: connect it to phase and neutral at 230/240 V, to 110 V or 220 V DC, or to a transformer. The datasheet gives 105 W inrush and a hold-in of 8 VA (4.5 W) for this coil, the lowest hold-in watts of the four coils, which keeps heat in the panel low.

Typical homes for the LC1D115A6KUE: general industrial motor starters fed straight from the single-phase network without a control transformer, panels where the site may change between 110 V and 230 V DC or AC, and OEM machines exported to several countries with different control voltages.

Ratings, motor sizes and short-circuit data of the LC1D115A6KUE

At 115 A AC-3 the datasheet lists 30 kW at 230 V, 55 kW at 400 V, 59 kW at 415 V, 75 kW at 500 V, 80 kW at 690 V and 65 kW at 1000 V. For 60 Hz motors the datasheet gives 30 hp at 200/208 V, 40 hp at 230/240 V, 75 hp at 460/480 V and 100 hp at 575/600 V. The utilisation categories listed are AC-3, AC-3e, AC-1, AC-4, DC-1, DC-3 and DC-5.

Supply voltage (AC-3) Motor power
230 V 30 kW
400 V 55 kW
415 V 59 kW
500 V 75 kW
690 V 80 kW
1000 V 65 kW

Making capacity is 1560 A at 440 V and breaking capacity 1100 A at 440 V. The datasheet pairs the contactor with 125 A aM fuses up to 440 V, 100 A aM up to 690 V, or 200 A gG up to 690 V for the power circuit, and the short-time withstand current is 1280 A for 10 s and 1800 A for 1 s at 40 °C.

Mechanical life is 8 million cycles; electrical life is 1 million cycles at 115 A AC-3 and 0.5 million at 200 A AC-1 (all at up to 440 V). The datasheet’s maximum operating rate is 2400 cycles per hour at 60 °C, and the safety data gives B10d of 684932 cycles at nominal load.

Power circuit insulation is rated 1000 V to IEC 60947-4-1 with an impulse withstand of 8 kV, overvoltage category III and pollution degree 3. Contact impedance is 0.45 mΩ at 200 A and 50 Hz.

The LC1D115A6KUE among the LC1D115 lug-terminal references

The table lists the 115 A ring lugs / busbars references in this series; the coil code is the only difference inside the group. The connector twin with the same coil is LC1D115AKUE.

Against the other coil bands of this frame, the 100 to 250 V AC/DC coil is the broad line-voltage choice for single-phase supplies, covering both 230/240 V AC and 220 V DC. The 48 to 130 V band cannot serve 230 V, and the 200 to 500 V band starts at 200 V and is aimed at line-to-line control, so this band is the natural fit for a phase-neutral supply.

Part number Coil band Terminals Note
LC1D115A6BNE 24-60 V AC/DC lugs-ring or bars Same frame
LC1D115A6EHE 48-130 V AC/DC lugs-ring or bars Same frame
LC1D115A6KUE 100-250 V AC/DC lugs-ring or bars This page
LC1D115A6LSE 200-500 V AC/DC lugs-ring or bars Same frame
LC1D115ABNE 24-60 V AC/DC connector Same frame
LC1D115AEHE 48-130 V AC/DC connector Same frame
LC1D115AKUE 100-250 V AC/DC connector Same frame
LC1D115ALSE 200-500 V AC/DC connector Same frame

Selection checklist for the LC1D115A6KUE

  • Motor size: up to 55 kW at 400 V in AC-3, 59 kW at 415 V.
  • Whether the starter is direct-on-line or a star-delta or soft-starter bypass, since the contactor sees different currents.
  • Coil voltage band (24-60, 48-130, 100-250 or 200-500 V AC/DC) and available control power.
  • Terminal style: ring lugs or busbars (A6 references) versus connector (A references).
  • Fuse or breaker for short-circuit protection: 125 A aM at up to 440 V per the datasheet.
  • Overload protection: electronic overload relay or motor protection suitable for 115 A frames.
  • Check the actual control voltage and its type (AC or DC); this coil covers both between 100 V and 250 V.
  • Confirm the 100-250 V AC/DC control supply can deliver the 170 VA inrush at the lowest voltage it reaches in operation.

Typical applications of the LC1D115A6KUE in Oman and the GCC

A 115 A contactor typically starts 45 to 55 kW pumps, large fans, compressors and crushers, and is also used for switching resistive banks and transformer-fed heating. In Oman and the GCC it is found in MCC starter buckets for water treatment, in desalination feed pump drives and in industrial ventilation.

The datasheet lists a protective treatment of ‘None’ for this frame, against ‘TH’ on the compact 9 to 25 A contactors, so a heavy contactor in a humid or salt-laden coastal atmosphere should be inside a sealed, ventilated panel instead of exposed to air. Summer temperatures in the region also call for attention to the 60 °C operating limit and the derating up to 70 °C given in the datasheet.

Information to send with an RFQ for the LC1D115A6KUE

  • The reference LC1D115A6KUE and the quantity required
  • The coil voltage on any contactor it replaces, and whether the control is AC or DC
  • Motor power, supply voltage and starter type, so the 115 A frame can be confirmed
  • Terminal style on site: ring lugs or busbars, or connector terminals
  • Delivery location and timing, and whether the item is a spare or new installation

Documents and quotation

A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above.

Send us the part number LC1D115A6KUE, the quantity and the application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Other Models in the Se Lc1d115 Lug Range

Seven Star LLC supplies models from the Se Lc1d115 Lug range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric LC1D115A6BNE 115 A Contactor 24-60 V AC/DCContactors & Overload RelaysView details
Schneider Electric LC1D115A6EHE 115 A Contactor 48-130 V AC/DCContactors & Overload RelaysView details
Schneider Electric LC1D115A6KUE 115 A Contactor 100-250 V AC/DCContactors & Overload RelaysYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric LC1D115A6KUE Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric LC1D115A6KUE 115 A Contactor

Answers from our engineering team on installation, compatibility and integration.

01What is the AC-3 rating of the LC1D115A6KUE?
The datasheet lists 115 A at up to 440 V in AC-3 and AC-3e, and 200 A in AC-1.
02What coil voltage range does the LC1D115A6KUE accept?
The control circuit voltage is 100 to 250 V AC 50/60 Hz and 100 to 250 V DC; operational limits are 0.8 Uc minimum to 1.1 Uc maximum.
03How are the power circuits of the LC1D115A6KUE connected?
It has ring lugs or busbars; the power circuit tightening torque in the datasheet is 12 N.m.
04What motor power does the LC1D115A6KUE cover at 400 V?
The datasheet gives 55 kW at 400 V in AC-3, and 75 hp at 460/480 V for 60 Hz motors.
05How big and heavy is the LC1D115A6KUE?
The datasheet lists 152 x 99 x 155 mm (H x W x D) and a net weight of 2.2 kg.