Schneider Electric RM17TA00 RM17-TA 3-phase relay

Description

RM17TA00: RM17TA multifunction control relay in the Harmony range

The RM17TA00 is a Schneider Electric Harmony multifunction control relay from the RM17 family, built to supervise asymmetry, phase sequence and phase failure detection. It is self-powered from the monitored voltage, offers 1 changeover output contact, and is housed in a 17.5 mm wide DIN-rail case. Seven Star LLC supplies the RM17TA00 in Oman and the GCC as an independent supplier based in Muscat.

The datasheet we reviewed is dated 7 Nov 2026. It describes a unit without a test button on the front.

Technical specifications of the RM17TA00

Parameter Specification
Manufacturer / part number Schneider Electric / RM17TA00
Relay type Multifunction control relay
Relay name RM17TA
Monitored parameters Asymmetry; Phase sequence; Phase failure detection
Control type Without test button
Contacts 1 C/O
[Uc] control circuit voltage 208–480 V
Product specific application For 3-phase supply
[Us] rated supply voltage , self-powered
Supply voltage limits 183–528 V AC
Power consumption 0–22 VA at 400 V AC 50 Hz
Measurement range 208–480 V AC
Measurement voltage limits 183–528 V AC
Hysteresis 2%
Adjustment of asymmetry 5–15 % of Un selected threshold
Time delay type Adjustable 0.1–10 s, ± 10 % of the full scale value Tt- time delay upon fault
Reset time 1500 ms time delay
Response time < 200 ms (in the event of a fault)
Nominal output current 5 A
Maximum switching voltage 250 V AC
Switching capacity in VA 1250 VA
Minimum switching current 10 mA at 5 V DC
Maximum switching current 5 A AC; 5 A DC
Electrical durability 100000 cycles
Mechanical durability 30000000 cycles
Control circuit voltage limits – 12 % + 10 % Un
Phase failure sensitivity 0.7 Un
Standards IEC 60255-1
Product certifications GOST, CSA, GL, C-Tick, UL
Relative humidity 95 % at 55 °C conforming to IEC 60068-2-30
IP degree of protection IP20 (terminals) conforming to IEC 60529; IP30 (casing) conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
Overvoltage category III conforming to IEC 60664-1
Insulation resistance > 500 MΩ at 500 V DC conforming to IEC 60255-5
[Ui] rated insulation voltage 400 V conforming to IEC 60664-1
Operating position Any position without derating
Connections – terminals Screw terminals, 1 × 0.5–1 × 4 mm² (20 AWG–11 AWG) solid without cable end; Screw terminals, 2 × 0.5–2 × 2.5 mm² (20 AWG–14 AWG) solid without cable end; Screw terminals, 1 × 0.2–1 × 2.5 mm² (24 AWG–12 AWG) flexible with cable end; Screw terminals, 2 × 0.2–2 × 1.5 mm² (24 AWG–16 AWG) flexible with cable end
Tightening torque 0.6–1 N.m conforming to IEC 60947-1
Housing material Polycarbonate
Local signalling LED (green) for power ON; LED (yellow) for relay ON
Mounting support 35 mm symmetrical DIN rail conforming to IEC 60715
Storage temperature -40 to 70 °C
Operating temperature -20 to 50 °C
Width 17.5 mm
Height / depth 90 mm / 72 mm
Net weight 0.08 kg
Packing 1 piece, 92 g; 48 pieces in the second package level
Country of origin Indonesia
Warranty 18 months

Output contacts and durability of the RM17TA00

The output is 1 changeover contact, rated 5 A nominal at up to 250 V AC, with a switching capacity of 1250 VA and a minimum switching current of 10 mA at 5 V DC. The listed durability is 100000 cycles electrical and 30000000 cycles mechanical. The contacts of the RM17TA00 are intended for pilot duty such as contactor coils, signal lamps and PLC inputs. For larger loads use an interposing contactor and keep the relay contact for the control circuit.

Because the minimum switching current is small, the same output can also feed a low-level signal such as a PLC input, but a contact that has switched heavy inductive loads should not later be reused for low-level signals.

Settings, measurement and timing of the RM17TA00

The measuring range is 208–480 V AC. Time delay: Adjustable 0.1–10 s, ± 10 % of the full scale value Tt- time delay upon fault. Hysteresis is 2%. Response time: < 200 ms (in the event of a fault). Reset time is listed as 1500 ms time delay.

When commissioning the RM17TA00, set the thresholds against the real running values of the plant, not against the nameplate alone. Where an adjustable fault delay is available, a longer time suits starting transients and short disturbances, while a short time protects equipment faster. Note the dial positions on the commissioning sheet so the settings can be restored after maintenance.

Selection checklist for the RM17TA00

  • Network voltage and frequency, three-wire or four-wire.
  • Which faults matter: phase loss, sequence, asymmetry, over or undervoltage.
  • Number of output contacts and their rating.
  • Fault delay and whether the relay supplies itself from the monitored voltage.
  • Width 17.5 mm on the rail and enclosure space.
  • Approvals and temperature limits against the project specification.

Installing and commissioning the RM17TA00

The relay clips onto a 35 mm DIN rail. The datasheet lists the operating position as Any position without derating. Terminals are screw type: Screw terminals, 1 × 0.5–1 × 4 mm² (20 AWG–11 AWG) solid without cable end; Screw terminals, 2 × 0.5–2 × 2.5 mm² (20 AWG–14 AWG) solid without cable end. Tightening torque is 0.6–1 N.m conforming to IEC 60947-1.

Before energising the RM17TA00, check the nameplate range against the supply and compare the wiring with the diagram on the datasheet and on the side of the housing. Switch on and confirm the green supply LED and the output indication. Then provoke the monitored fault in a safe way, for example by removing a fuse on a spare circuit or by simulating the condition, and confirm that the output behaves as intended.

Environment, insulation and approvals for the RM17TA00

Storage is listed at -40 to 70 °C. Operation is listed at -20 to 50 °C. Relative humidity is 95 % at 55 °C conforming to IEC 60068-2-30. Protection is IP20 (terminals) conforming to IEC 60529, pollution degree 3 conforming to IEC 60664-1, rated insulation voltage 400 V conforming to IEC 60664-1. The housing is polycarbonate.

Certifications listed on the datasheet for this reference: GOST, CSA, GL, C-Tick, UL. Check the marks against your project specification, because requirements differ between sites.

In a closed panel in an Omani summer the air near the relay can be much hotter than the room, so leave space around it and keep it away from contactors and power resistors.

Where the RM17TA00 is used in Oman and the GCC

Typical uses include pump stations, air-conditioning plant and workshop machinery fed from three-phase panels, where a lost or reversed phase would damage the motor. It is also found in camps, desalination skids and packaged plant that are connected on site by different crews, so the sequence cannot be trusted until it is checked, and in generator-backed supplies and long overhead feeders, where supply quality varies more than on a stable utility network. Heat, dust, humidity and unstable supplies make supervision relays a low-cost way to protect larger equipment, but project specifications and local rules decide which protection is required.

Information to send with an RFQ for the RM17TA00

  • Exact reference RM17TA00 and quantity.
  • Supply voltage, frequency and type of network.
  • The load or machine being supervised and the required alarm or trip behaviour.
  • Required contact arrangement and rating.
  • Related relays, sockets or accessories needed on the same order.
  • Delivery location and timeline.

Documents and quotation

The Schneider Electric datasheet for the RM17TA00 is attached on this page and holds the complete specification summarised above, as printed on the manufacturer’s document dated 7 Nov 2026.

Send us the reference RM17TA00, quantity and delivery location and Seven Star LLC will reply to your request. We supply as an independent supplier based in Muscat and do not act for the manufacturer.

Other Models in the Se Harmony Rm17 Range

Seven Star LLC supplies models from the Se Harmony Rm17 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric RM17JC00MW RM17-J 2-20 A current relayContactors & Overload RelaysView details
Schneider Electric RM17TA00 RM17-TA 3-phase relayContactors & Overload RelaysYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric RM17TA00 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric RM17TA00 RM17-TA 3-phase relay

Answers from our engineering team on installation, compatibility and integration.

01What does the RM17TA00 monitor?
It is the RM17TA Harmony control relay for asymmetry, phase sequence and phase failure detection. See the functions list on this page for how each one works.
02What supply and measuring range does the RM17TA00 have?
The datasheet lists the supply as self-powered with limits of 183…528 V AC, and a measurement range of 208...480 V AC.
03What output does the RM17TA00 provide?
The output is 1 C/O contact, rated 5 A nominal at up to 250 V AC. Electrical durability is listed as 100000 cycles and mechanical durability as 30000000 cycles.
04How is the RM17TA00 mounted and what size is it?
It clips onto a 35 mm DIN rail and measures 17.5 mm wide, 90 mm high and 72 mm deep. Terminals are screw type, tightened to 0.6…1 N.m conforming to IEC 60947-1.
05What environment is the RM17TA00 rated for?
Operation is listed at -20 to 50 °C, storage at -40 to 70 degrees C, relative humidity 95 % at 55 °C conforming to IEC 60068-2-30 and protection IP20 (terminals) conforming to IEC 60529.