Schneider Electric CAD50E7 TeSys D Relay 5NO 48V AC
Description
What the CAD50E7 is and how its code is built
This page covers the CAD50E7, a TeSys D control relay from Schneider Electric with five normally open contacts and a 48 V AC 50/60 Hz coil. It belongs to the CAD range, which uses the same compact housing as the TeSys D contactors but is built for control duty. Seven Star LLC is an independent supplier in Muscat and supplies the CAD50E7 in Oman and the GCC.
Part-number logic: the family is TeSys D control relay (CAD), the contact block is five normally open contacts, and the suffix E7 corresponds to the 48 V AC 50/60 Hz coil. That is exactly what the manufacturer’s description says for this reference, so a quote request should always quote the complete CAD50E7 and never just the family prefix.
Choosing the supply for the CAD50E7 coil
The coil is the one part that distinguishes the CAD50E7 from its siblings, so it deserves the closest reading.
A 48 V AC coil is another transformer-fed option, used on equipment whose control winding delivers 48 V. Compared with 24 V AC it halves the current for the same volt-amperes, which helps when many relays share one winding or the cable run is long. The datasheet figures of 70 VA inrush and 8 VA hold-in at 50 Hz give about 1.5 A at pull-in and 0.17 A held in at 48 V.
The window of 0.8 to 1.1 Uc at 50 Hz is about 38.4 to 52.8 V, and 40.8 V at the low end on a 60 Hz supply. The drop-out band of 0.3 to 0.6 Uc is about 14.4 to 28.8 V. This coil should not be confused with the 48 V DC reference of the same family: the AC and DC coils use different internal designs, and a relay with the wrong coil type will hum, overheat or fail to hold, depending on which way round the mistake is made.
Sizing the coil circuit is straightforward with the datasheet figures. The listed power is 70 VA inrush and 8 VA hold-in at 50 Hz; at 48 V that is roughly 1.46 A on pull-in and 167 mA held in. The coil operates within 38.4 to 52.8 V at 50 Hz (0.8 to 1.1 Uc), from 40.8 V at 60 Hz and releases within 14.4 to 28.8 V (0.3 to 0.6 Uc). As these currents are derived rather than quoted, leave margin in the supply and check them against the nameplate of the exact relay you receive.
CAD50E7 specification table
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / CAD50E7 |
| Range / type | TeSys Deca control relay (TeSys CAD) |
| Pole contact composition | 5 NO |
| Utilisation categories | DC-13; AC-14; AC-15 |
| Rated operational voltage (Ue) | ≤ 690 V AC 25 to 400 Hz |
| Control circuit voltage (Uc) | 48 V AC 50/60 Hz |
| Control voltage limits | 0.3 to 0.6 Uc (-40 to 70 °C):drop-out AC 50/60 Hz; 0.8 to 1.1 Uc (-40 to 60 °C):operational AC 50 Hz; 0.85 to 1.1 Uc (-40 to 60 °C):operational AC 60 Hz; 1 to 1.1 Uc (60 to 70 °C):operational AC 50/60 Hz |
| Operating time | 12 to 22 ms coil energisation and NO closing; 4 to 12 ms coil de-energisation and NO opening |
| Inrush / hold-in power | 70 VA 50 Hz (at 20 °C) / 8 VA 50 Hz (at 20 °C) |
| Thermal current (Ith) | 10 A (at 60 °C) |
| Rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| Associated fuse | 10 A gG conforming to IEC 60947-5-1 |
| Insulation voltage (Ui) | 690 V IEC 60947-5-1; 600 V UL and CSA |
| Mechanical durability / rate | 30 Mcycles / 180 cyc/mn |
| Mounting / terminals | DIN rail or plate; screw clamp 1 to 4 mm², 1.7 N.m |
| Dimensions (H x W x D) | 77 mm x 45 mm x 84 mm |
| Net weight | 0.58 kg |
| Degree of protection | IP2X front face conforming to VDE 0106 |
| Ambient temperature, operation | -40 to 60 °C; 60 to 70 °C with derating |
| Ambient temperature, storage | -60 to 80 °C |
| Certifications | CB; CCC; UL; CSA; EAC; CE; UKCA |
Pre-order checklist for the CAD50E7
- Coil: 48 V AC 50/60 Hz, confirmed from the supply drawing or the nameplate of the relay being replaced.
- Contacts: five normally open contacts, matched to the interlock and signalling circuits.
- Supply sizing: about 1.46 A at pull-in and 167 mA held in (derived from the datasheet power).
- Window: operates within 38.4 to 52.8 V at 50 Hz (0.8 to 1.1 Uc), from 40.8 V at 60 Hz and releases at 14.4 to 28.8 V (0.3 to 0.6 Uc).
- Contact load of the CAD50E7: 10 A thermal, AC-15, AC-14 or DC-13 duties; use a contactor for motor-power loads.
- Space: 77 mm high, 45 mm wide and 84 mm deep.
- Environment: operation up to 60 °C, up to 70 °C with derating; storage -60 to 80 °C.
- Type: AC and DC coils of the same voltage are different references; do not mix them.
Where the contacts of the CAD50E7 earn their keep
The 5 NO configuration is the version for pure signal multiplication. With no normally closed contacts, all five poles close when the coil is energised, so a single command can start, indicate and permit several circuits at once. The datasheet lists operating times only for the normally open contacts, as there are no normally closed contacts to describe.
Choose it when a single initiating contact, for example a PLC output or a protection relay trip contact, has to be repeated on five independent circuits: alarm annunciation, a shutdown loop, a remote indication, an interlock to another panel and a counter or logger. If any of those circuits needs a contact that opens when the relay operates, the 3 NO + 2 NC member of the family is the right choice instead.
Contact data from the datasheet apply to all five poles: 10 A conventional thermal current at 60 °C, utilisation categories AC-15, AC-14 and DC-13, a rated operational voltage up to 690 V AC, and a minimum switching capability of 17 V and 5 mA, which makes the contacts suitable for low-level signals as well as for 24 V PLC inputs.
Sibling references: CAD50E7 and the other CAD50 relays
The CAD50E7 is one member of a family of TeSys D control relays that share the housing, the contact data and the mounting. Only the coil voltage and type change from one reference to the next, together with the contact arrangement: the CAD32 series is 3 NO + 2 NC and the CAD50 series is 5 NO. The table lists the CAD50 references we are asked for most.
If the supply is not in the table, ask us; the CAD32 series has the other contact arrangement. AC-coil versions are 84 mm deep and DC-coil versions 93 mm, which matters in a shallow enclosure.
| Reference | Coil voltage and type | Contacts |
|---|---|---|
| CAD50B7 | 24 V AC 50/60 Hz | 5 NO |
| CAD50BD | 24 V DC standard | 5 NO |
| CAD50BL | 24 V DC low consumption | 5 NO |
| CAD50E7 (this page) | 48 V AC 50/60 Hz | 5 NO |
| CAD50FD | 110 V DC standard | 5 NO |
| CAD50GD | 125 V DC standard | 5 NO |
| CAD50MD | 220 V DC standard | 5 NO |
| CAD50P7 | 230 V AC 50/60 Hz | 5 NO |
| CAD50U7 | 240 V AC 50/60 Hz | 5 NO |
Applications of the CAD50E7 in Oman and the GCC
Low-voltage AC coils are used where a control transformer separates the relay circuit from the mains. In the GCC they appear mostly in machine panels, HVAC and pump control cabinets built by international manufacturers, where a 24, 42 or 48 V winding supplies relays, pilot lamps and solenoid valves. Here the relay is a repeater and interlock element between a controller output and field loads or drives.
Panels in the region commonly see high ambient temperatures, so the transformer that feeds the coil, not only the relay, deserves attention. The datasheet allows operation up to 60 °C with derating to 70 °C, but an undersized transformer in a hot cabinet is the more likely source of unreliable pull-in than the relay itself.
For the CAD50E7, that means five normally open contacts from one 48 V AC 50/60 Hz command, sitting next to LC1D contactors of the same TeSys D family on the same rail.
Fitting the CAD50E7 in a panel
Mount the CAD50E7 on a 35 mm DIN rail or on a plate; the datasheet lists both. It measures 77 mm x 45 mm x 84 mm and weighs 0.58 kg, so allow space for the wires to bend at the terminals and for air to circulate around the housing. Tighten the screw-clamp terminals to 1.7 N.m with a Philips No 2, Pozidriv No 2 or 6 mm flat screwdriver, and do not exceed the cable sizes of 1 to 4 mm² per terminal listed in the datasheet.
Commissioning is simple: energise the coil at nominal voltage, verify that all five poles move together, and check the contact action with a meter before connecting the field loads. The mechanical durability is 30 million cycles and the maximum operating rate is 180 cycles per minute, so in normal control duty there is no routine wear item to schedule. In a dusty site, clean the panel and check terminal tightness during planned shutdowns, because loose terminals, more often than the relay itself, cause intermittent faults.
RFQ details for the CAD50E7
- Full reference CAD50E7 and the quantity
- The coil voltage and type seen on the supply drawing or on the old relay nameplate
- The load or circuit each contact will switch (voltage, current, signal level)
- Panel or machine the relay must fit, and whether it is a spare, a replacement or a new installation
- Delivery location in Oman or the GCC and the date required
Documents and quotation
A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above, and it is worth reading beside the panel drawing before you order.
Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.
Other Models in the Se Cad50 Range
Seven Star LLC supplies models from the Se Cad50 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric CAD50B7 TeSys D Relay 5NO 24V AC | Contactors & Overload Relays | View details |
| Schneider Electric CAD50BD TeSys D Relay 5NO 24V DC | Contactors & Overload Relays | View details |
| Schneider Electric CAD50BL TeSys D Relay 5NO 24VDC Low Power | Contactors & Overload Relays | View details |
| Schneider Electric CAD50E7 TeSys D Relay 5NO 48V AC | Contactors & Overload Relays | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric CAD50E7 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric CAD50E7 TeSys D Relay 5NO 48V AC
Answers from our engineering team on installation, compatibility and integration.
01What coil does the CAD50E7 have?
The datasheet lists a 48 V AC 50/60 Hz AC 50/60 Hz coil. The operational window is 38.4 to 52.8 V at 50 Hz and drop-out is 14.4 to 28.8 V.
02How many contacts does the CAD50E7 have?
It has five normally open contacts, with a 10 A conventional thermal current at 60 °C and utilisation categories AC-15, AC-14 and DC-13.
03How much power does the coil of the CAD50E7 draw?
The datasheet gives 70 VA inrush and 8 VA hold-in at 50 Hz. At 48 V that is about 1.46 A at pull-in and 167 mA held in, derived from the stated power.
04What are the dimensions and weight of the CAD50E7?
77 mm high, 45 mm wide and 84 mm deep, with a net weight of 0.58 kg. It mounts on a DIN rail or a plate.
05What ambient temperature does the CAD50E7 accept?
Operation is listed from -40 to 60 °C, and up to 70 °C with derating; storage is -60 to 80 °C. Altitude is 0 to 3000 m.