Schneider Electric LADN11 TeSys D 1 NO + 1 NC Contact Block

Description

LADN11: the standard 1 NO + 1 NC front block for LC1D contactors

The LADN11 is the standard Schneider Electric TeSys D front auxiliary contact block with one normally open and one normally closed contact and screw terminals. It is the accessory most often added to a TeSys D contactor to give a self-hold and a status or interlock contact. Seven Star LLC supplies the LADN11 in Oman and the GCC as an independent supplier based in Muscat.

The 11 in the reference stands for one NO and one NC. The block is the slim version: 26 mm wide, 48 mm high and 42 deep according to the datasheet, which leaves room beside it for a second block on a wide contactor. The wide four-contact versions in the same family are the LADN22, LADN31 and LADN40.

Technical specifications of the LADN11

Parameter Specification
Manufacturer / part number Schneider Electric / LADN11
Description Product datasheet Auxiliary contact block, TeSys D, 1NO + 1NC, front mounting, screw terminals
Range TeSys; TeSys Deca
Product name TeSys Deca
Product or component type Auxiliary contact block
Device short name LADN
Range compatibility TeSys D CAD; TeSys D LC1D; TeSys F LC1F; TeSys F CR1F; TeSys Deca CAD; TeSys Deca LC1D
Mounting location Front
Pole contact composition 1 NO + 1 NC
Contacts operation Instantaneous
[Ue] rated operational voltage 690 V AC 25 to 400 Hz
[Ie] rated operational current 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13
[Ui] rated insulation voltage 690 V conforming to IEC 60947-5-1; 600 V conforming to UL; 600 V conforming to CSA
[Ith] conventional free air thermal 10 A (at 60 °C)
Standards EN/IEC 60947-5-1; GB/T 14048.5; EN 50012; UL 60947-5-1; CSA C22.2 No 60947-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ
Product certifications CB Scheme; UL; CSA; CCC; EAC; UKCA
Irms rated making capacity 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1
Permissible short-time rating 100 A 60 °C 1 s; 120 A 60 °C 500 ms; 140 A 60 °C 100 ms; are subject to change – check with your local distributor.
Protection type GG fuse 10 A
Mechanical durability 30 Mcycles
Minimum switching current 5 mA
Minimum switching voltage 17 V
Non-overlap time 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact
Insulation resistance > 10 MOhm
Connections – terminals Screw clamp terminals 1 cable(s) 1 to 4 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1 to 4 mm²flexible without cable end
Height 48 mm
Width 26 mm
Depth 42 mm
Environmental characteristic Normal environment
IP degree of protection IP20 conforming to IEC 60529
Ambient air temperature (operation, as listed) -5 to 60 °C
Operating altitude 3000 m

What a 1 NO + 1 NC block gives the LADN11 user

A single NO contact held across the start button seals the contactor in, which is the foundation of two-wire and three-wire control. The NC contact then adds either an interlock against a reverse contactor or a status loop. Together they cover most small motor starters without further wiring.

The datasheet lists a non-overlap time of 1.5 ms between the NC and NO contacts, so they do not conduct together at switching, which matters for reversing interlocks.

Compatibility and ratings of the LADN11

The range compatibility line in the datasheet is TeSys D CAD and LC1D, TeSys F LC1F and CR1F, and the TeSys Deca CAD and LC1D. The block mounts on the front face.

Rated operational voltage is 690 V AC at 25 to 400 Hz, with conventional thermal current of 10 A at 60 °C. Rated operational current is 6 A at 120 V AC-15, 1.04 A at 690 V AC-15, 0.55 A at 125 V DC-13 and 0.1 A at 600 V DC-13. Making capacity is 140 A AC and 250 A DC, protection is a 10 A gG fuse, mechanical durability is 30 Mcycles, and the minimum switching level is 5 mA at 17 V. The non-overlap time between the NC and NO contacts is 1.5 ms on energisation and on de-energisation.

Choosing the LADN11 against other TeSys D blocks

  • 1 NO + 1 NC, screw terminals, 26 mm wide.
  • Mount on LC1D or CAD, or on LC1F, CR1F per the datasheet.
  • If you need the EN 50012 marked version, look at the LADN11G.
  • If you need more contacts in one block, see the LADN22.
  • Check the logic level: below 17 V or 5 mA reliability falls.

LADN family: the LADN11 compared with its siblings

All six references below are front-mounting TeSys D blocks with screw clamp terminals; they differ in contact pattern and width.

Reference Contacts Width Protection
LADN11 1 NO + 1 NC 26 mm IP20 conforming to IEC 60529
LADN11G 1 NO + 1 NC 26 mm IP20 conforming to IEC 60529
LADN20 2 NO 26 mm IP20 conforming to IEC 60529
LADN22 2 NO + 2 NC 44 mm IP20 conforming to IEC 60529
LADN31 3 NO + 1 NC 44 mm IP2X conforming to IEC 60529
LADN40 4 NO 44 mm IP2X conforming to IEC 60529

Installing the LADN11 and testing it

Snap the block on the front of the contactor and tighten the terminals at 1.7 N.m with a flat 6 mm or a Philips or Pozidriv No 2 screwdriver. Terminals accept 1 to 4 mm² flexible conductor with ferrule.

Operate the contactor by hand and check with a meter that the NO closes and the NC opens, then re-torque after a heat cycle. Good terminal discipline here prevents the most common control-circuit faults.

LADN11 in Oman and the GCC

TeSys D contactors run pumps, compressors, fans and conveyors across industry in the Gulf, and the LADN11 is the commodity auxiliary block on them. It is held as a spare by maintenance teams, because the block is small and the downtime caused by a missing contact can be long.

The ambient limit of -5 to 60 °C should be checked for outdoor panels in summer.

Information to send with an RFQ for the LADN11

  • Full reference and quantity required
  • Contactor model the block mounts on
  • Contact arrangement needed (NO and NC count)
  • Control voltage and load of each circuit
  • Delivery location and timing

Documents and quotation

A datasheet for the LADN11 is attached on this page. It carries the electrical, mechanical and environmental data summarised above, so the figures can be checked against your drawings.

Send the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Datasheets & Documents
  • PDF Datasheet Schneider Electric LADN11 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric LADN11 TeSys D 1 NO + 1 NC

Answers from our engineering team on installation, compatibility and integration.

01What contacts does the LADN11 have?
One normally open and one normally closed contact.
02How wide is the LADN11?
26 mm wide, 48 mm high and 42 mm deep. See the datasheet linked on this page for the full figures.
03Which contactors accept the LADN11?
TeSys D CAD and LC1D, TeSys F LC1F and CR1F, and TeSys Deca CAD and LC1D.
04What is the mechanical durability?
30 Mcycles. See the datasheet linked on this page for the full figures.
05Which certifications are listed?
CB Scheme, UL, CSA, CCC, EAC and UKCA. See the datasheet linked on this page for the full figures.