Schneider Electric CAD32M7 TeSys D Relay 3NO+2NC 220V AC

Description

CAD32M7 control relay with a 220 V AC 50/60 Hz coil

Control circuits that need five switching points from one command often turn to the CAD32M7, a Schneider Electric TeSys Deca control relay with three normally open and two normally closed contacts and a 220 V AC 50/60 Hz coil. The manufacturer describes it as: TeSys D control relay – 3 NO + 2 NC – up to 690 V – 220 V AC standard coil. Seven Star LLC supplies the CAD32M7 in Oman and the GCC as an independent supplier based in Muscat.

The code is easy to decode once you know the pattern. CAD32 sets the five-pole contact block (three normally open and two normally closed contacts), the letter M marks 220 V, and the closing 7 marks a 50/60 Hz AC coil. The datasheet confirms this reference as a 220 V AC 50/60 Hz coil version.

Using three normally open and two normally closed contacts on the CAD32M7

Use the normally closed contacts for permissive and interlock loops that must fall away on operation, such as stopping a second starter while the first is running, or for a healthy-state signal that drops out when the relay operates. The normally open contacts are available to repeat start, run and trip signals. If a circuit needs more than three normally open contacts and no normally closed ones, the 5 NO version of the same family is the better match.

Contact data from the datasheet apply to all five poles: 10 A conventional thermal current at 60 °C, utilisation categories AC-15, AC-14 and DC-13, a rated operational voltage up to 690 V AC, and a minimum switching capability of 17 V and 5 mA, which makes the contacts suitable for low-level signals as well as for 24 V PLC inputs.

Datasheet values for the CAD32M7

Parameter Specification
Manufacturer / part number Schneider Electric / CAD32M7
Range / type TeSys Deca control relay (TeSys CAD)
Pole contact composition 3 NO + 2 NC
Utilisation categories DC-13; AC-14; AC-15
Rated operational voltage (Ue) ≤ 690 V AC 25 to 400 Hz
Control circuit voltage (Uc) 220 V AC 50/60 Hz
Control voltage limits 0.3 to 0.6 Uc (-40 to 70 °C):drop-out AC 50/60 Hz; 0.8 to 1.1 Uc (-40 to 60 °C):operational AC 50 Hz; 0.85 to 1.1 Uc (-40 to 60 °C):operational AC 60 Hz; 1 to 1.1 Uc (60 to 70 °C):operational AC 50/60 Hz
Operating time 12 to 22 ms coil energisation and NO closing; 4 to 12 ms coil de-energisation and NO opening; 4 to 19 ms coil energisation and NC opening; 6 to 17 ms coil de-energisation and NC closing
Inrush / hold-in power 70 VA 50 Hz (at 20 °C) / 8 VA 50 Hz (at 20 °C)
Thermal current (Ith) 10 A (at 60 °C)
Rated making capacity 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1
Associated fuse 10 A gG conforming to IEC 60947-5-1
Insulation voltage (Ui) 690 V IEC 60947-5-1; 600 V UL and CSA
Mechanical durability / rate 30 Mcycles / 180 cyc/mn
Mounting / terminals DIN rail or plate; screw clamp 1 to 4 mm², 1.7 N.m
Dimensions (H x W x D) 77 mm x 45 mm x 84 mm
Net weight 0.58 kg
Degree of protection IP2X front face conforming to VDE 0106
Ambient temperature, operation -40 to 60 °C; 60 to 70 °C with derating
Ambient temperature, storage -60 to 80 °C
Certifications CB; CCC; UL; CSA; EAC; CE; UKCA

How the 220 V AC 50/60 Hz coil of the CAD32M7 behaves

The coil is the one part that distinguishes the CAD32M7 from its siblings, so it deserves the closest reading.

The 220 V AC coil is the legacy mains-voltage choice. It is still specified by plants and machine builders whose documentation was written around a 220 V single-phase control supply, and it appears often when a panel imported years ago needs a replacement relay. The datasheet lists 70 VA inrush and 8 VA hold-in at 50 Hz, which at 220 V is about 0.32 A at pull-in and 36 mA held in.

The window of 0.8 to 1.1 Uc at 50 Hz is about 176 to 242 V, which is wide enough to cover both a 220 V supply and the 230 V and 240 V nominal values now used on public networks, although the upper limit of 242 V leaves little margin on a 240 V supply with a positive tolerance. For a site that actually runs at 240 V, the 240 V coil is the better match, and the sibling reference with that voltage should be quoted instead.

The datasheet gives operating times of 12 to 22 ms coil energisation and NO closing, 4 to 12 ms coil de-energisation and NO opening, 4 to 19 ms coil energisation and NC opening, 6 to 17 ms coil de-energisation and NC closing. The 50/60 Hz AC coil responds quickly, with closing times of 12 to 22 ms.

Installation and maintenance of the CAD32M7

Fit the relay in an enclosure with the front face reachable for inspection: the datasheet quotes IP2X at the front face, which protects against finger contact but not against dust. The weight of 0.58 kg is modest, so the relay is held securely by its rail clip, but plate mounting is preferable on machines with strong vibration. The datasheet lists vibration resistance of 2 Gn open and 4 Gn closed (5 to 300 Hz) and shock resistance of 10 Gn open and 15 Gn closed for 11 ms.

For spares planning, the CAD32M7 is a good candidate for a stocked spare because it is physically identical to its siblings and the coil is the only part that differs. Mark the coil voltage clearly on the terminal block door or on the panel diagram, test it after any control-supply change, and keep a record of the coil code. The datasheet gives an 18-month warranty from the manufacturer, which applies to the product as supplied by its own channel.

Typical applications for the CAD32M7 in the region

Mains-voltage AC coils at 110 to 240 V are used for general control: starting pumps and fans, repeating status signals and building interlocks between motor starters. In Oman the nominal single-phase voltage is 240 V, so the 220, 230 and 240 V coils are the ones most often seen in local panels, depending on how the equipment was originally specified.

For the CAD32M7, that means three normally open and two normally closed contacts from one 220 V AC 50/60 Hz command, sitting next to LC1D contactors of the same TeSys D family on the same rail.

Checks before ordering the CAD32M7

  • Coil: 220 V AC 50/60 Hz, confirmed from the supply drawing or the nameplate of the relay being replaced.
  • Contacts: three normally open and two normally closed contacts, matched to the interlock and signalling circuits.
  • Supply sizing: about 0.32 A at pull-in and 36.4 mA held in (derived from the datasheet power).
  • Window: operates within 176 to 242 V at 50 Hz (0.8 to 1.1 Uc), from 187 V at 60 Hz and releases at 66 to 132 V (0.3 to 0.6 Uc).
  • Contact load of the CAD32M7: 10 A thermal, AC-15, AC-14 or DC-13 duties; use a contactor for motor-power loads.
  • Space: 77 mm high, 45 mm wide and 84 mm deep.
  • Environment: operation up to 60 °C, up to 70 °C with derating; storage -60 to 80 °C.
  • Type: AC and DC coils of the same voltage are different references; do not mix them.

Related references to the CAD32M7

The CAD32M7 is one member of a family of TeSys D control relays that share the housing, the contact data and the mounting. Only the coil voltage and type change from one reference to the next, together with the contact arrangement: the CAD32 series is 3 NO + 2 NC and the CAD50 series is 5 NO. The table lists the CAD32 references we are asked for most.

If the supply is not in the table, ask us; the CAD50 series has the other contact arrangement. AC-coil versions are 84 mm deep and DC-coil versions 93 mm, which matters in a shallow enclosure.

Reference Coil voltage and type Contacts
CAD32BD 24 V DC standard 3 NO + 2 NC
CAD32BL 24 V DC low consumption 3 NO + 2 NC
CAD32D7 42 V AC 50/60 Hz 3 NO + 2 NC
CAD32ED 48 V DC standard 3 NO + 2 NC
CAD32F7 110 V AC 50/60 Hz 3 NO + 2 NC
CAD32FD 110 V DC standard 3 NO + 2 NC
CAD32JD 12 V DC standard 3 NO + 2 NC
CAD32M7 (this page) 220 V AC 50/60 Hz 3 NO + 2 NC
CAD32MD 220 V DC standard 3 NO + 2 NC
CAD32N7 415 V AC 50/60 Hz 3 NO + 2 NC
CAD32R7 440 V AC 50/60 Hz 3 NO + 2 NC
CAD32U7 240 V AC 50/60 Hz 3 NO + 2 NC
CAD32V7 400 V AC 50/60 Hz 3 NO + 2 NC

What to include when you request a quote for the CAD32M7

  • Delivery location in Oman or the GCC and the date required
  • Panel or machine the relay must fit, and whether it is a spare, a replacement or a new installation
  • The load or circuit each contact will switch (voltage, current, signal level)
  • The coil voltage and type seen on the supply drawing or on the old relay nameplate
  • Full reference CAD32M7 and the quantity

Documents and quotation

A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above, and it is worth reading beside the panel drawing before you order.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Other Models in the Se Cad32 Range

Seven Star LLC supplies models from the Se Cad32 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric CAD32BD TeSys D Relay 3NO+2NC 24V DCContactors & Overload RelaysView details
Schneider Electric CAD32BL TeSys D Relay 3NO+2NC 24VDC Low PowerContactors & Overload RelaysView details
Schneider Electric CAD32D7 TeSys D Relay 3NO+2NC 42V ACContactors & Overload RelaysView details
Schneider Electric CAD32ED TeSys D Relay 3NO+2NC 48V DCContactors & Overload RelaysView details
Schneider Electric CAD32F7 TeSys D Relay 3NO+2NC 110V ACContactors & Overload RelaysView details
Schneider Electric CAD32FD TeSys D Relay 3NO+2NC 110V DCContactors & Overload RelaysView details
Schneider Electric CAD32JD TeSys D Relay 3NO+2NC 12V DCContactors & Overload RelaysView details
Schneider Electric CAD32M7 TeSys D Relay 3NO+2NC 220V ACContactors & Overload RelaysYou are viewing this model
Schneider Electric CAD32MD TeSys D Relay 3NO+2NC 220V DCContactors & Overload RelaysView details
Schneider Electric CAD32N7 TeSys D Relay 3NO+2NC 415V ACContactors & Overload RelaysView details
Schneider Electric CAD32R7 TeSys D Relay 3NO+2NC 440V ACContactors & Overload RelaysView details
Schneider Electric CAD32U7 TeSys D Relay 3NO+2NC 240V ACContactors & Overload RelaysView details
Schneider Electric CAD32V7 TeSys D Relay 3NO+2NC 400V ACContactors & Overload RelaysView details
Datasheets & Documents
  • PDF Datasheet Schneider Electric CAD32M7 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric CAD32M7 TeSys D Relay 3NO+2NC

Answers from our engineering team on installation, compatibility and integration.

01What coil does the CAD32M7 have?
The datasheet lists a 220 V AC 50/60 Hz AC 50/60 Hz coil. The operational window is 176 to 242 V at 50 Hz and drop-out is 66 to 132 V.
02How many contacts does the CAD32M7 have?
It has three normally open and two normally closed contacts, with a 10 A conventional thermal current at 60 °C and utilisation categories AC-15, AC-14 and DC-13.
03How much power does the coil of the CAD32M7 draw?
The datasheet gives 70 VA inrush and 8 VA hold-in at 50 Hz. At 220 V that is about 0.32 A at pull-in and 36.4 mA held in, derived from the stated power.
04What are the dimensions and weight of the CAD32M7?
77 mm high, 45 mm wide and 84 mm deep, with a net weight of 0.58 kg. It mounts on a DIN rail or a plate.
05Can the CAD32M7 work in a hot panel?
Operation is listed from -40 to 60 °C, and up to 70 °C with derating; storage is -60 to 80 °C. Altitude is 0 to 3000 m.