Brand: Schneider Electric
Schneider Electric CAD32N7 TeSys D Relay 3NO+2NC 415V AC
Description
CAD32N7: a relay with three normally open and two normally closed contacts for 415 V AC 50/60 Hz control circuits
If you are replacing or specifying a 415 V AC 50/60 Hz control relay with three normally open and two normally closed contacts, the CAD32N7 is the Schneider Electric TeSys Deca reference to look at. Its datasheet title reads: TeSys D control relay – 3 NO + 2 NC – up to 690 V – 415 V AC standard coil. Seven Star LLC supplies the CAD32N7 in Oman and the GCC as an independent supplier based in Muscat.
How the reference breaks down: CAD means a TeSys Deca control relay, 32 fixes the contacts at three normally open and two normally closed contacts, and N7 fixes the coil at 415 V AC 50/60 Hz. Because the other family members share the same housing, an error in the last two characters is the most common cause of a relay that arrives and does not suit the panel.
Technical data of the CAD32N7 at a glance
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / CAD32N7 |
| Range / type | TeSys Deca control relay (TeSys CAD) |
| Pole contact composition | 3 NO + 2 NC |
| Utilisation categories | AC-14; DC-13; AC-15 |
| Rated operational voltage (Ue) | ≤ 690 V AC 25 to 400 Hz |
| Control circuit voltage (Uc) | 415 V AC 50/60 Hz |
| Control voltage limits | 0.3 to 0.6 Uc (-40 to 70 °C):drop-out AC 50/60 Hz; 0.8 to 1.1 Uc (-40 to 60 °C):operational AC 50 Hz; 0.85 to 1.1 Uc (-40 to 60 °C):operational AC 60 Hz; 1 to 1.1 Uc (60 to 70 °C):operational AC 50/60 Hz |
| Operating time | 12 to 22 ms coil energisation and NO closing; 4 to 12 ms coil de-energisation and NO opening; 4 to 19 ms coil energisation and NC opening; 6 to 17 ms coil de-energisation and NC closing |
| Inrush / hold-in power | 70 VA 50 Hz (at 20 °C) / 8 VA 50 Hz (at 20 °C) |
| Thermal current (Ith) | 10 A (at 60 °C) |
| Rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| Associated fuse | 10 A gG conforming to IEC 60947-5-1 |
| Insulation voltage (Ui) | 690 V IEC 60947-5-1; 600 V UL and CSA |
| Mechanical durability / rate | 30 Mcycles / 180 cyc/mn |
| Mounting / terminals | DIN rail or plate; screw clamp 1 to 4 mm², 1.7 N.m |
| Dimensions (H x W x D) | 77 mm x 45 mm x 84 mm |
| Net weight | 0.58 kg |
| Degree of protection | IP2X front face conforming to VDE 0106 |
| Ambient temperature, operation | -40 to 60 °C; 60 to 70 °C with derating |
| Ambient temperature, storage | -60 to 80 °C |
| Certifications | CB; CCC; UL; CSA; EAC; CE; UKCA |
Field use of the CAD32N7 in the Gulf
A coil rated at 400, 415 or 440 V is connected between two phases, which suits simple motor starters, pump panels and fan control without a control transformer. In the GCC, 415 V is the local nominal phase-to-phase voltage, and 400 V and 440 V coils appear mostly in imported or marine-style equipment designed around those values.
Because the coil circuit is at line voltage, these relays are common in rugged, no-frills panels for water transfer, irrigation, desalination auxiliary drives and workshop equipment. The contact rating of 690 V keeps the coil and contact circuits in the same insulation class, which simplifies the wiring and the labelling inside the cabinet.
For the CAD32N7, that means three normally open and two normally closed contacts from one 415 V AC 50/60 Hz command, sitting next to LC1D contactors of the same TeSys D family on the same rail.
Contact block of the CAD32N7
Use the normally closed contacts for permissive and interlock loops that must fall away on operation, such as stopping a second starter while the first is running, or for a healthy-state signal that drops out when the relay operates. The normally open contacts are available to repeat start, run and trip signals. If a circuit needs more than three normally open contacts and no normally closed ones, the 5 NO version of the same family is the better match.
Contact data from the datasheet apply to all five poles: 10 A conventional thermal current at 60 °C, utilisation categories AC-15, AC-14 and DC-13, a rated operational voltage up to 690 V AC, and a minimum switching capability of 17 V and 5 mA, which makes the contacts suitable for low-level signals as well as for 24 V PLC inputs.
Coil data and timing of the CAD32N7
The coil is the one part that distinguishes the CAD32N7 from its siblings, so it deserves the closest reading.
The 415 V AC coil matches the nominal phase-to-phase voltage of the public network in Oman, which is 415 V on a 240 V phase supply, so it is connected between two phases of the local mains without a control transformer. The datasheet lists 70 VA inrush and 8 VA hold-in at 50 Hz, about 0.17 A at pull-in and 19 mA held in at 415 V.
The window of 0.8 to 1.1 Uc at 50 Hz is about 332 to 456.5 V, with a drop-out band of 0.3 to 0.6 Uc, about 124.5 to 249 V. That upper limit of 456.5 V comfortably exceeds a 415 V network with a positive tolerance. A coil at this voltage should be connected only where both phases are protected by suitable fusing, and the panel should show clearly that the coil circuit is at line voltage. The same coil code is not interchangeable with the 400 V or 440 V siblings, which are matched to slightly different supplies.
The datasheet gives operating times of 12 to 22 ms coil energisation and NO closing, 4 to 12 ms coil de-energisation and NO opening, 4 to 19 ms coil energisation and NC opening, 6 to 17 ms coil de-energisation and NC closing. The 50/60 Hz AC coil responds quickly, with closing times of 12 to 22 ms.
Installing and keeping the CAD32N7 in service
Fit the relay in an enclosure with the front face reachable for inspection: the datasheet quotes IP2X at the front face, which protects against finger contact but not against dust. The weight of 0.58 kg is modest, so the relay is held securely by its rail clip, but plate mounting is preferable on machines with strong vibration. The datasheet lists vibration resistance of 2 Gn open and 4 Gn closed (5 to 300 Hz) and shock resistance of 10 Gn open and 15 Gn closed for 11 ms.
For spares planning, the CAD32N7 is a good candidate for a stocked spare because it is physically identical to its siblings and the coil is the only part that differs. Mark the coil voltage clearly on the terminal block door or on the panel diagram, test it after any control-supply change, and keep a record of the coil code. The datasheet gives an 18-month warranty from the manufacturer, which applies to the product as supplied by its own channel.
Family table including the CAD32N7
The CAD32N7 is one member of a family of TeSys D control relays that share the housing, the contact data and the mounting. Only the coil voltage and type change from one reference to the next, together with the contact arrangement: the CAD32 series is 3 NO + 2 NC and the CAD50 series is 5 NO. The table lists the CAD32 references we are asked for most.
If the supply is not in the table, ask us; the CAD50 series has the other contact arrangement. AC-coil versions are 84 mm deep and DC-coil versions 93 mm, which matters in a shallow enclosure.
| Reference | Coil voltage and type | Contacts |
|---|---|---|
| CAD32BD | 24 V DC standard | 3 NO + 2 NC |
| CAD32BL | 24 V DC low consumption | 3 NO + 2 NC |
| CAD32D7 | 42 V AC 50/60 Hz | 3 NO + 2 NC |
| CAD32ED | 48 V DC standard | 3 NO + 2 NC |
| CAD32F7 | 110 V AC 50/60 Hz | 3 NO + 2 NC |
| CAD32FD | 110 V DC standard | 3 NO + 2 NC |
| CAD32JD | 12 V DC standard | 3 NO + 2 NC |
| CAD32M7 | 220 V AC 50/60 Hz | 3 NO + 2 NC |
| CAD32MD | 220 V DC standard | 3 NO + 2 NC |
| CAD32N7 (this page) | 415 V AC 50/60 Hz | 3 NO + 2 NC |
| CAD32R7 | 440 V AC 50/60 Hz | 3 NO + 2 NC |
| CAD32U7 | 240 V AC 50/60 Hz | 3 NO + 2 NC |
| CAD32V7 | 400 V AC 50/60 Hz | 3 NO + 2 NC |
What to confirm before you buy the CAD32N7
- Coil: 415 V AC 50/60 Hz, confirmed from the supply drawing or the nameplate of the relay being replaced.
- Contacts: three normally open and two normally closed contacts, matched to the interlock and signalling circuits.
- Supply sizing: about 0.17 A at pull-in and 19.3 mA held in (derived from the datasheet power).
- Window: operates within 332 to 457 V at 50 Hz (0.8 to 1.1 Uc), from 353 V at 60 Hz and releases at 124 to 249 V (0.3 to 0.6 Uc).
- Contact load of the CAD32N7: 10 A thermal, AC-15, AC-14 or DC-13 duties; use a contactor for motor-power loads.
- Space: 77 mm high, 45 mm wide and 84 mm deep.
- Environment: operation up to 60 °C, up to 70 °C with derating; storage -60 to 80 °C.
- Type: AC and DC coils of the same voltage are different references; do not mix them.
Quotation details we need for the CAD32N7
- Delivery location in Oman or the GCC and the date required
- Panel or machine the relay must fit, and whether it is a spare, a replacement or a new installation
- The load or circuit each contact will switch (voltage, current, signal level)
- The coil voltage and type seen on the supply drawing or on the old relay nameplate
- Full reference CAD32N7 and the quantity
Documents and quotation
A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above, and it is worth reading beside the panel drawing before you order.
Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.
Other Models in the Se Cad32 Range
Seven Star LLC supplies models from the Se Cad32 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
Datasheets & Documents
- Datasheet Schneider Electric CAD32N7 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric CAD32N7 TeSys D Relay 3NO+2NC
Answers from our engineering team on installation, compatibility and integration.
01What coil does the CAD32N7 have?
The datasheet lists a 415 V AC 50/60 Hz AC 50/60 Hz coil. The operational window is 332 to 457 V at 50 Hz and drop-out is 124 to 249 V.
02How many contacts does the CAD32N7 have?
It has three normally open and two normally closed contacts, with a 10 A conventional thermal current at 60 °C and utilisation categories AC-15, AC-14 and DC-13.
03How much power does the coil of the CAD32N7 draw?
The datasheet gives 70 VA inrush and 8 VA hold-in at 50 Hz. At 415 V that is about 0.17 A at pull-in and 19.3 mA held in, derived from the stated power.
04What are the dimensions and weight of the CAD32N7?
77 mm high, 45 mm wide and 84 mm deep, with a net weight of 0.58 kg. It mounts on a DIN rail or a plate.
05Can the CAD32N7 work in a hot panel?
Operation is listed from -40 to 60 °C, and up to 70 °C with derating; storage is -60 to 80 °C. Altitude is 0 to 3000 m.