A9C20864: four-pole 63 A contactor, the top frame of the iCT family

The A9C20864 is a Schneider Electric Acti9 contactor listed in the datasheet as: iCT 63A 4NO 220 to 240V 50Hz contactor. The A9C20864 is the 63 A frame of the iCT range: four normally open poles in a six-pitch body that switches three phases and neutral at up to 63 A AC-7A. It handles the largest loads that the Acti9 modular contactor family carries. Seven Star LLC supplies the A9C20864 in Oman and the GCC as an independent supplier based in Muscat.

The reference reads as A9C family, 63 A, four poles all normally open (4P, 4 NO), coil 220 to 240 V AC at 50 Hz. The datasheet lists only 63 A AC-7A for this reference; unlike the lower frames, it does not list an AC-7B motor-type rating, which should be remembered when a motor load is considered.

Technical specifications of the A9C20864

Parameter Specification
Manufacturer / part number Schneider Electric / A9C20864
Description iCT 63A 4NO 220 to 240V 50Hz contactor
Range of product Acti9
Product name Acti9 iCT
Product or component type Contactor
Device short name iCT
Device application Motor-heating-lighting
Poles 4P
[Ie] rated operational current 63 A AC-7A
Pole contact composition 4 NO
Network type AC
Control type Remote control
[Uc] control circuit voltage 220 to 240 V AC 50 Hz
Network frequency 50 Hz
[Ue] rated operational voltage 400 V AC 50 Hz
Maximum power 2.1 W at 400 V AC
[Ui] rated insulation voltage 500 V AC 50/60 Hz
[Uimp] rated impulse withstand 4 kV
Control signal type Maintained
Switching frequency 100 switching operations/day
Local signalling Action indicator
Hold-in power consumption in VA 6.5 VA
Inrush power in VA 53 VA
Mounting mode Clip-on
Mounting support 35 mm symmetrical DIN rail
9 mm pitches 6
Height 85 mm
Width 54 mm
Depth 60 mm
Mechanical durability 1000000 cycles
Electrical durability 100000 cycles IEC/EN 61095 63 A 50 Hz AC-7A; 30000 cycles IEC/EN 61095 20 A 50 Hz AC-7B; 30000 cycles IEC/EN 61095 50 Hz AC-7C
Tightening torque Control circuit: 0.8 N.m; Power circuit: 3.5 N.m
Market segment Small commercial; Residential
Standards IEC/EN 61095
Noise level 30 dB
IP degree of protection IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Relative humidity 95 % at 55 °C
Operating altitude 2000 m
Ambient air temperature, operation -5 to 60 °C
Ambient air temperature, storage -40 to 70 °C

Power circuit and coil data of the A9C20864

The rated operational current is 63 A AC-7A. Rated operational voltage: 400 V AC 50 Hz. Maximum power figure: 2.1 W at 400 V AC. Coil voltage: 220 to 240 V AC 50 Hz. Hold-in consumption: 6.5 VA. Inrush consumption: 53 VA. Rated insulation voltage: 500 V AC 50/60 Hz. Rated impulse withstand voltage: 4 kV. Mechanical durability: 1000000 cycles.

The body width matches the 40 A four-pole frame at 54 mm, and the coil data are identical at 6.5 VA hold-in and 53 VA inrush; what distinguishes the 63 A frame is the larger conductor cross-section and the contacts. The power circuit tightening torque in the datasheet is 3.5 N.m, which has to be applied with a proper screwdriver and checked again after the first heating cycles.

AC-7A and AC-7B ratings of the A9C20864: reading the load categories

Two numbers describe this contactor’s capability, one per load category. The higher figure is for AC-7A, meaning resistive and lightly inductive circuits such as heaters and lamp groups, and the lower one is for AC-7B, meaning small motors of appliance type. Industrial motors with heavy starting current are outside the intent of both categories and belong on a motor contactor with an overload relay.

Electrical durability in the datasheet: 100000 cycles IEC/EN 61095 63 A 50 Hz AC-7A; 30000 cycles IEC/EN 61095 20 A 50 Hz AC-7B; 30000 cycles IEC/EN 61095 50 Hz AC-7C.

How the A9C20864 compares with neighbouring iCT contactors

The A9C20844 differs in current 40 A AC-7A against 63 A AC-7A here. The A9C20868 differs in contacts 2 NO + 2 NC against 4 NO here; current 63 A AC-7A against 63 A AC-7A here.

The table below lists the iCT references of this group with their main differences so that a purchase order can be checked against the family.

Reference Poles / contacts Rated current Coil Width
A9C20731 1P / 1 NO 25 A AC-7A, 8.5 A AC-7B 230 to 240 V AC 50 Hz 18 mm
A9C20732 2P / 2 NO 25 A AC-7A, 8.5 A AC-7B 230 to 240 V AC 50 Hz 18 mm
A9C20834 4P / 4 NO 25 A AC-7A, 8.5 A AC-7B 220 to 240 V AC 50 Hz 36 mm
A9C20838 4P / 2 NO + 2 NC 25 A AC-7A, 8.5 A AC-7B 220 to 240 V AC 50 Hz 36 mm
A9C20842 2P / 2 NO 40 A AC-7A, 15 A AC-7B 220 to 240 V AC 50 Hz 36 mm
A9C20843 3P / 3 NO 40 A AC-7A, 15 A AC-7B 220 to 240 V AC 50 Hz 54 mm
A9C20844 4P / 4 NO 40 A AC-7A, 15 A AC-7B 220 to 240 V AC 50 Hz 54 mm
A9C20864 (this page) 4P / 4 NO 63 A AC-7A 220 to 240 V AC 50 Hz 54 mm
A9C20868 4P / 2 NO + 2 NC 63 A AC-7A, 20 A AC-7B 220 to 240 V AC 50 Hz 54 mm
A9C22512 2P / 2 NO 16 A AC-7A, 6 A AC-7B 220 V AC 50 Hz 18 mm

Selection checklist for the A9C20864

  • Confirm there is no motor load: the datasheet gives only an AC-7A rating for this frame.
  • Fit a protective device upstream and size cabling for continuous 63 A.
  • Match coil voltage and frequency to the control supply; this reference uses 220 to 240 V AC 50 Hz.
  • Check the width of 54 mm (6 pitches) against free rail space and spare gaps for heat.
  • Confirm the number of operations per day stays within the datasheet figure.

Mounting, wiring and maintenance of the A9C20864

During commissioning, energise the coil with the load circuit isolated and watch the action indicator; the datasheet lists local signalling by an action indicator on the front. Then close the load circuit and measure current and voltage drop. Switching frequency is limited to 100 switching operations/day, so check that a control program, a time switch or a building management output does not chatter the contactor many times per hour.

The datasheet lists the environment as -5 to 60 °C in operation and -40 to 70 °C in storage, relative humidity of 95 % at 55 °C, an altitude limit of 2000 m and pollution degree 2.

Where the A9C20864 is used in Oman and the GCC

At 63 A, typical duty is a distribution-level switch for a lighting feeder in a retail unit, a bank of electric heating or an air-conditioning auxiliary supply. Sites in the GCC use such contactors on the load side of a protective device to give remote or automatic switching without relying on the breaker as an operating device.

Use a coordinated upstream protective device and a cable sized for continuous load; the contactor does not protect the circuit. With 1,000,000 mechanical cycles and 100,000 electrical cycles at 63 A AC-7A listed, durability is good, but the datasheet limit of 100 switching operations per day should be respected for repetitive duty.

Information to send with an RFQ for the A9C20864

  • Full reference (A9C20864) and quantity required
  • Supply and control voltage at site, with the frequency
  • Existing panel, rail and neighbouring devices it must fit beside
  • Delivery location and timing
  • Whether it is a spare, a like-for-like replacement or a new installation
  • Load type and current: lighting, heating or motor-type

Documents and quotation

A datasheet for the A9C20864 is attached on this page. It lists the electrical, mechanical and environmental data summarised above, and it should be read together with the manufacturer’s installation instructions for the final design.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Other Models in the Se Acti9 Ict Range

Seven Star LLC supplies models from the Se Acti9 Ict range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric A9C20731 iCT 25 A 1NO 230-240 V ContactorContactors & Overload RelaysView details
Schneider Electric A9C20732 iCT 25 A 2NO 230-240 V ContactorContactors & Overload RelaysView details
Schneider Electric A9C20834 iCT 25 A 4NO 220-240 V ContactorContactors & Overload RelaysView details
Schneider Electric A9C20838 iCT 25 A 2NO+2NC 220-240 V ContactorContactors & Overload RelaysView details
Schneider Electric A9C20842 iCT 40 A 2NO 220-240 V ContactorContactors & Overload RelaysView details
Schneider Electric A9C20843 iCT 40 A 3NO 220-240 V ContactorContactors & Overload RelaysView details
Schneider Electric A9C20844 iCT 40 A 4NO 220-240 V ContactorContactors & Overload RelaysView details
Schneider Electric A9C20864 iCT 63 A 4NO 220-240 V ContactorContactors & Overload RelaysYou are viewing this model
Schneider Electric A9C20868 iCT 63 A 2NO+2NC 220-240 V ContactorContactors & Overload RelaysView details
Schneider Electric A9C22512 iCT 16 A 2NO 220 V ContactorContactors & Overload RelaysView details
Datasheets & Documents
  • PDF Datasheet Schneider Electric A9C20864 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric A9C20864 iCT 63 A 4NO 220-240 V

Answers from our engineering team on installation, compatibility and integration.

01What coil or control voltage does the A9C20864 use?
The datasheet lists 220 to 240 V AC 50 Hz. Check this against the real control supply before ordering.
02What are the dimensions of the A9C20864?
The datasheet gives a width of 54 mm; see the table above for height and depth.
03How many contacts does the A9C20864 have and how are they arranged?
The datasheet lists 4 NO. Check that this arrangement matches your control circuit before ordering.
04How is the A9C20864 mounted?
The datasheet gives: 35 mm symmetrical DIN rail.
05What ambient temperature range is listed for the A9C20864?
The datasheet lists -5 to 60 °C in operation and -40 to 70 °C in storage. In hot Gulf plant rooms the operating upper limit should be compared with the real panel temperature.