Schneider Electric A9V22325 Vigi iC60 3P 25 A 100 mA

Description

A9V22325: Vigi iC60 3P 25 A 100 mA add-on block

The A9V22325 is a Schneider Electric Acti9 Vigi iC60 add-on residual current device in a three-pole version, rated 25 A with 100 mA sensitivity and Type A detection. It is not a stand-alone breaker: it is clipped to the side of a compatible iC60 miniature circuit-breaker and connected by screws, which adds earth-leakage protection to the overload and short-circuit protection that the breaker already provides. Seven Star LLC supplies the A9V22325 in Oman and the GCC as an independent supplier based in Muscat.

Decoding the product from the datasheet: A9V22325 has a 230–415 V AC rated operational voltage, so the block can sit on a single-phase 230 V circuit or on a three-phase system up to 415 V, it occupies 6 modules of 9 mm and weighs 0.21 kg. Its tripping is voltage independent, meaning the residual current function does not depend on the mains voltage being present to operate.

What 100 mA and Type A mean for the A9V22325

The A9V22325 offers a 100 mA threshold, a medium sensitivity that is typically selected to protect against earth-fault currents in a feeder or to leave room for time discrimination with finer downstream devices, not as the main protection for personal contact. The tripping delay is listed as instantaneous, so there is no built-in time delay for selectivity at this reference.

Type A responds to sinusoidal alternating residual current and to pulsating DC residual current, which makes it a better match for single-phase rectifier loads and electronic equipment that can inject such components into an earth fault. Selecting the sensitivity and the type is a design decision, not a catalogue preference: use the earthing system, the load type and the applicable wiring rules to decide, and avoid putting several loads with natural leakage behind one very sensitive block.

Where the A9V22325 fits in Oman and the GCC

Earth-leakage add-on blocks of this kind are used in commercial buildings, camps, workshops, pump houses, desalination plant auxiliaries, utility substations, and small distribution boards in oil and gas facilities. A 100 mA three-pole unit such as the A9V22325 is normally installed on feeders, with finer devices downstream. Humid coastal air, dust and high summer temperatures put stress on terminals and on the test mechanism, so periodic inspection is a good habit.

Technical specifications of the A9V22325

Parameter Specification
Manufacturer / part number Schneider Electric / A9V22325
Range / product name Acti9 / Acti9 Vigi iC60 (add-on residual current device)
Poles 3P
Rated current [In] 25 A
Earth-leakage sensitivity 100 mA
Protection time delay Instantaneous
Earth-leakage type Type A
Network AC, 50/60 Hz
Rated operational voltage [Ue] 230–415 V AC 50/60 Hz (EN/IEC 61009-1 and 61009-2-1)
Rated insulation voltage [Ui] 500 V AC (IEC 60947-2)
Rated impulse withstand [Uimp] 6 kV (IEC 60947-2)
Residual current tripping Voltage independent
Location in system Outgoer
Range compatibility Acti9 iC60 miniature circuit-breaker / Acti9 Reflex iC60 integrated control circuit breaker
Compatible breakers IC60a/N/H/L/P single terminal miniature circuit-breaker ≤ 25 A; Disbo iC60N/H miniature circuit-breaker ≤ 25 A; IC60L MA miniature circuit-breaker ≤ 16 A; Reflex iC60 integrated control circuit breaker ≤ 25 A
Local signalling Trip indicator
Mounting Clip-on, DIN rail; electrical connection to the breaker by screws
Comb busbar compatibility Bottom: yes
Width in 9 mm pitches 6
Dimensions H × W × D 91 mm × 54 mm × 73.5 mm
Net weight 0.21 kg
Terminals Tunnel type, bottom, 1 cable: 1–25 mm² rigid without cable end; 1–16 mm² flexible without cable end; 1–16 mm² flexible with cable end
Wire stripping length / torque 14 mm / 2 N.m (bottom)
Protection degree IP20 (IEC 60529); IP40 in modular enclosure
Pollution degree 3
Surge withstand 8/20 µs impulse, 250 A (IEC 61009-1)
Operating temperature -25–60 °C
Storage temperature -40–85 °C
Warranty 18 months

Compatible iC60 breakers for the A9V22325

The datasheet lists the range compatibility as Acti9 iC60 miniature circuit-breaker and Acti9 Reflex iC60 integrated control circuit breaker. The product compatibility entries for the A9V22325 are: IC60a/N/H/L/P single terminal miniature circuit-breaker ≤ 25 A; Disbo iC60N/H miniature circuit-breaker ≤ 25 A; IC60L MA miniature circuit-breaker ≤ 16 A; Reflex iC60 integrated control circuit breaker ≤ 25 A. The upper current limit in each line is the point to watch: the add-on block rated 25 A is intended to pair with breakers at or below that class, and some breaker versions are restricted to lower currents than the others.

The Reflex iC60 integrated control circuit breaker is included in the compatibility list, so the block can also be used with that control-breaker version. Because the block has 3 poles, the breaker normally has to match that pole count; confirm the pairing against the compatibility table before ordering the breaker and block as a set.

Other Vigi iC60 blocks and how they differ from the A9V22325

The other 3-pole blocks in our lane are: A9V41325 (3P 25 A 30 mA AC), A9V41363 (3P 63 A 30 mA AC). Across the entire set, the key differences are pole count, current class (25 A, 40 A or 63 A), sensitivity (10, 30, 100 or 300 mA), type (AC or A) and the voltage window. The A9V22325 is the one with 3 poles, 25 A, 100 mA, Type A and 230-415 V AC 50/60 Hz V AC.

For reference, the wider list we are quoting is: A9V01225 (2P 25 A 30 mA), A9V10225 (2P 25 A 10 mA), A9V12225 (2P 25 A 100 mA), A9V12263 (2P 63 A 100 mA), A9V12463 (4P 63 A 100 mA), A9V41225 (2P 25 A 30 mA), A9V41263 (2P 63 A 30 mA), A9V41325 (3P 25 A 30 mA), A9V41363 (3P 63 A 30 mA), A9V41425 (4P 25 A 30 mA), A9V41440 (4P 40 A 30 mA), A9V41463 (4P 63 A 30 mA), A9V44240 (2P 40 A 300 mA). The width and the weight also change with pole count and current, which affects how much space the combination takes in a board.

Installation and testing of the A9V22325

Connect the this unit to the bottom of the matching breaker with the supplied screw connection, then fix the assembly on DIN rail. Terminals at the bottom are tunnel type: 1–25 mm² rigid without cable end; 1–16 mm² flexible without cable end; 1–16 mm² flexible with cable end. Strip the conductor to 14 mm and tighten to 2 N.m; the comb busbar is compatible at the bottom.

After energising, use the front test button to confirm tripping, and check the trip indicator shows the fault state. Record the test in the maintenance log and repeat it at regular intervals. Keep in mind the temperature window of -25–60 °C for operation; in hot enclosures at Gulf sites, mount the block away from other heat sources and consider derating or ventilating the board. The unit is IP20 on its own and IP40 when fitted in a modular enclosure.

Information to send with an RFQ for the A9V22325

For a fast quotation on the this unit, send the part number, quantity, the type and rating of the miniature circuit-breaker it will be fitted to, the system voltage and earthing arrangement, the residual current sensitivity required by your design, and the delivery address in Oman or the GCC. If you are replacing an existing assembly, a photo of the label helps us match the pole count and current class.

Documents and quotation

A datasheet for the this unit is attached on this page. The version we reviewed is dated 8 Nov 2026.

Send the part number and your project details through the RFQ form; Seven Star LLC will confirm availability and lead time in Oman and the GCC.

Other Models in the Se Vigi Ic60 Range

Seven Star LLC supplies models from the Se Vigi Ic60 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric A9V01225 Vigi iC60 2P 25 A 30 mAAutomation AccessoriesView details
Schneider Electric A9V10225 Vigi iC60 2P 25 A 10 mAAutomation AccessoriesView details
Schneider Electric A9V22325 Vigi iC60 3P 25 A 100 mAAutomation AccessoriesYou are viewing this model
Schneider Electric A9V41225 Vigi iC60 2P 25 A 30 mAAutomation AccessoriesView details
Schneider Electric A9V41263 Vigi iC60 2P 63 A 30 mAAutomation AccessoriesView details
Datasheets & Documents
  • PDF Datasheet Schneider Electric A9V22325 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric A9V22325 Vigi iC60 3P 25 A 100 mA

Answers from our engineering team on installation, compatibility and integration.

01What does the A9V22325 add to an iC60 breaker?
It is a 3-pole add-on residual current device with 100 mA sensitivity and Type A detection, clipped to a compatible iC60 breaker to add earth-leakage protection.
02What is the earth-leakage setting of the A9V22325?
The datasheet lists 100 mA with instantaneous tripping and Type A. Voltage-independent tripping is stated for the residual current function.
03Which breakers is the A9V22325 compatible with?
The datasheet lists iC60 single terminal breakers up to 25 A and related iC60 versions, with some variants limited to lower currents. Confirm the exact pairing before ordering.
04What are the dimensions and weight of the A9V22325?
The datasheet gives 91 mm high, 54 mm wide and 73.5 mm deep, weight 0.21 kg, occupying 6 modules of 9 mm.
05What operating temperature applies to the A9V22325?
The operating range is -25…60 °C and storage is -40 to 85 °C, with IP20 protection or IP40 in a modular enclosure.