Schneider Electric CCT15225 Acti9 IC Astro 1C Twilight Switch

Description

CCT15225 Acti9 IC Astro 1C programmable astronomic switch

The CCT15225 is an astronomic twilight switch: instead of a light sensor it calculates sunrise and sunset from the geographic position and date, then switches its single changeover contact accordingly. It is part of the Schneider Electric Acti9 IC line, 45 mm wide on TH35 DIN rail, with a backlit LCD and menus in 18 languages. Seven Star LLC supplies the CCT15225 in Oman and the GCC as an independent supplier based in Muscat.

Because there is no photocell, cloud cover, dirt or shading cannot disturb it, which suits external lighting that should follow the sun year-round. The offset can shift switching by up to 120 minutes either side of the calculated time.

CCT15225 technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / CCT15225
Range / product name Acti9 IC
Product type Programmable astronomic twilight switch
Channels 1
Setting Weekly programming
Control type By calculation of sunrise/sunset times
Contacts C/O
Output Dry contact
Rated operational voltage 230 V AC +10 % -15 % at 50/60 Hz
Maximum switching current 10 A – 250 V AC pf = 0.6; 16 A – 250 V AC pf = 1
Minimum switching current 10 mA 230 V AC; 100 mA 24 V AC/DC
Maximum number of switchings 84
Accuracy ± 0.25 s/day 25 °C
Power consumption 0.5 W standby
Backup time 10 years
Display Backlit LCD
Information displayed Time; Operating time counter (per channel); Switching behaviour; Day
Control buttons 4 push-buttons
Mounting TH35 DIN rail conforming to EN 60715
Terminals 2 × 0.5–2.5 mm² screw terminals solid or flexible; 1 × 2.5 mm² screw terminals solid or flexible with sleeve
Dimensions 92.6 mm x 45 mm x 66.7 mm (H x W x D)
Net weight 115 g
Insulation class Class II
Overvoltage category Class 3
Marking CE
Standard EN 60730-2-7:2010
Operating temperature -30–55 °C
Storage / transport temperature -30–70 °C
Protection IP20
Relative humidity 90 %, non-condensing
Warranty 18 months

How the CCT15225 decides when to switch

The datasheet gives the control type as calculation of sunrise and sunset times, with position setting, weekly programming, holiday schedules and automatic winter/summer changeover among the functions. Operating modes listed are evening on, morning off, evening off morning on (shown as inactive) and timer only. The maximum number of switchings is 84, and accuracy is ± 0.25 s/day 25 °C.

  • External input for override
  • Code lock function
  • Holiday schedules
  • Automatic winter/summer time changeover
  • On/off permanent switching
  • Sunrise/sunset time offset ± 120 min
  • Position setting
  • Switch preselection

the CCT15225 against sensor-based twilight switches

The IC2000 family reacts to measured brightness, which is simple and local but depends on a clean, well-placed sensor. The IC Astro reacts to calculated time, which is predictable but does not see storms or heavy dust haze. Sites that want darkness-driven switching with a time schedule can use the IC2000P+ CCT15483 with its outdoor sensor.

CCT15225 in the IHP and IC Astro range

The programmable models from this lane compared on datasheet values:

Part number Type Channels Max switchings Min interval Languages
CCT15225 (this page) Programmable astronomic twilight switch 1 84 sunrise/sunset based 18
CCT15441 Programmable digital time switch 1 56 1 min 11
CCT15443 Programmable digital time switch 2 56 1 min 11
CCT15551 Programmable digital time switch 1 84 1s 11

Loads and contact rating of the CCT15225

The contact is rated 10 A – 250 V AC pf = 0.6 and 16 A – 250 V AC pf = 1 with a minimum of 10 mA 230 V AC and 100 mA 24 V AC/DC. Lamp-load limits from the datasheet:

  • Incandescent lamp 2600 W
  • Halogen lamp 2600 W
  • Non-corrected fluorescent tube 2300 VA
  • Serial-compensated fluorescent tube 2300 VA
  • Parallel compensated fluorescent lamp 730 VA 80 µF
  • Compact fluorescent lamp 170 W
  • LED lamp < 2 W 30 W
  • LED lamp ≥ 2 W 200 W

Heavier or inductive loads should be switched through a contactor, with the timer driving the coil.

Inrush current at switch-on, particularly with LED drivers and electronic ballasts, can exceed the steady rating for a few milliseconds. The lamp-load limits above already account for typical inrush, but groups of many drivers on one contact should be split or switched through a contactor.

Selection checklist for the CCT15225

  • Supply: 230 V AC +10 % -15 % at 50/60 Hz.
  • Channels needed: 1.
  • Control logic: sunrise/sunset calculation.
  • Load: inside the load table or through a contactor.
  • Temperature: -30–55 °C operating range.
  • Options: override input, memory stick, languages.

Installation and commissioning of the CCT15225

Mount this unit on TH35 rail, wire the supply and load with the 0.5 to 2.5 mm² screw terminals described on the datasheet, then set language, date, time and geographic position through the four push-buttons. The unit is Class II, IP20 and overvoltage category 3, so it belongs in a closed board.

After programming, test each output by manual operation, then watch the first scheduled switchings. A code lock function is listed to prevent changes by unauthorised persons, which is worth enabling on shared boards.

Before energising, confirm that the supply on the board matches 230 V AC +10 % -15 % at 50/60 Hz and that the load circuit has its own protective device, since the timer contact is not a short-circuit protection element. Keep control wiring tidy and clear of power cables so the unit’s push-buttons and display remain accessible for later changes, and label the output so maintenance staff know which circuit it controls.

Where the CCT15225 is used in Oman and the GCC

Typical jobs are street, facade, landscape and car-park lighting, mosque and compound lighting, and signage that should follow a daily or weekly routine. In hot and dusty switchrooms keep the board within the -30–55 °C range on the datasheet and avoid direct sun on the enclosure.

In practice many Gulf sites run lighting on a fixed evening-to-dawn pattern all year, and shift pumps, fans or irrigation by season. Document each programmed schedule on a label inside the board door, because a replaced timer comes up blank and the schedule has to be re-entered from the record.

Documents and quotation

The official Schneider Electric datasheet of this unit is attached on this page for download, so every figure above can be checked against the source.

To request a quotation, send us the part number CCT15225, the quantity and the delivery location through the RFQ form. Seven Star LLC replies with availability and lead time.

Datasheets & Documents
  • PDF Datasheet Schneider Electric CCT15225 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric CCT15225 Acti9 IC Astro 1C

Answers from our engineering team on installation, compatibility and integration.

01What is the CCT15225?
It is a Schneider Electric Acti9 programmable astronomic twilight switch with 1 channel(s) and a changeover dry contact, 45 mm wide for TH35 DIN rail.
02What supply voltage does the CCT15225 use?
The datasheet gives 230 V AC +10 % -15 % at 50/60 Hz and a maximum standby power consumption of 0.5 W standby.
03What is the maximum switching current of the CCT15225?
10 A - 250 V AC pf = 0.6; 16 A - 250 V AC pf = 1, with a minimum of 10 mA 230 V AC; 100 mA 24 V AC/DC.
04How long does the CCT15225 keep its program without supply?
The datasheet lists a backup time of 10 years.
05How many switchings can the CCT15225 store?
The datasheet gives a maximum of 84. See the datasheet linked on this page for the full figures.