- Automation & ControlView all 1,933 products
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- Isolator & Barrier
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- HMI Displays
- Motor Soft Starters
- Industrial Computers
- Servo Drives
- Pneumatic Cylinders
- Machine Vision
- Automation Software
- Robotics
Brand: Schneider Electric
Schneider Electric A9N61501 Acti9 C60H-DC 1P 1 A C-Curve DC MCB
Description
A9N61501: Acti9 C60H-DC 1P 1 A C-curve DC miniature circuit breaker
The A9N61501 is a Schneider Electric Acti9 C60H-DC miniature circuit-breaker, single-pole, rated 1 A at 25 °C with a C curve and a thermal-magnetic trip unit. It is built for direct-current circuits (the datasheet lists network type DC) up to 250 V DC rated operational voltage, which makes it a protection device for battery banks, DC control supplies, solar strings and telecom or substation DC systems rather than AC distribution. Seven Star LLC supplies the A9N61501 in Oman and the GCC as an independent supplier based in Muscat.
The product title gives the family (C60H-DC), the pole count (1 pole), the rating (1 A) and the curve (C). A9N61501 has polarity markings on its terminals, which is why correct connection of positive and negative matters more than on an AC breaker.
Technical specifications of the A9N61501
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / A9N61501 |
| Range / product | Acti9 C60H-DC |
| Type | Miniature circuit-breaker, thermal-magnetic, distribution application |
| Poles | 1P, 1 protected pole |
| Rated current [In] | 1 A at 25 °C |
| Curve | C |
| Network type | DC |
| Rated operational voltage | 250 V DC |
| Rated insulation voltage / impulse | 500 V DC / 6 kV |
| Breaking capacity (Icu) | 20 kA at 110 V DC; 10 kA at 220 V DC; 6 kA at 250 V DC (EN/IEC 60947-2) |
| Service breaking capacity (Ics) | 15 kA at 110 V DC; 7.5 kA at 220 V DC; 4.5 kA at 250 V DC (75 % of Icu) |
| Utilisation category | Category A |
| Isolation | Suitable for isolation |
| Endurance | 20000 mechanical cycles; 3000 electrical cycles at L/R = 2 ms |
| Control / signalling | Toggle; ON/OFF indication |
| Dimensions | 2 modules of 9 mm |
| Net weight | 0.128 kg |
| Colour | White |
| Mounting | 35 mm symmetrical DIN rail, fixed |
| Comb busbar / distribution block | Compatible top or bottom |
| Locking | Padlockable in position O |
| Tightening torque | 2.5 N.m top or bottom (power circuit) |
| Earth-leakage protection | Without |
| Pollution degree / overvoltage category | 3 / IV |
| Tropicalisation | Class 2 |
| Operating temperature | -25–70 °C |
| Storage temperature | -40–85 °C |
| Altitude | 2000 m |
| Standards | EN/IEC 60947-2 |
Why a DC breaker is not an AC breaker: the A9N61501
An AC current passes through zero 100 or 120 times per second, which helps the arc extinguish; a DC arc has no natural zero crossing, so a breaker for DC needs an arc chamber and often a permanent magnet or specific polarity to blow the arc out. This is why the C60H-DC is marked with positive and negative terminals and why the datasheet gives its breaking capacity per DC voltage rather than a single AC figure. For this unit the values are 20 kA at 110 V DC, 10 kA at 220 V DC and 6 kA at 250 V DC: the capacity falls as the voltage rises, because a higher voltage makes the arc harder to extinguish.
Do not install it on an AC circuit and do not reverse the polarity unless the manufacturer’s wiring diagram shows how.
Rating, curve and trip behaviour
The A9N61501 is rated 1 A, the lowest current in its range, and has a C curve: the magnetic element releases at a multiple of the rated current, which for such a small rating is a very low absolute current. It is therefore well suited to protecting a small DC load, a control circuit, a sensor supply or a monitoring device from an upstream DC bus. The 1 A figure is defined at 25 °C; the datasheet lists an operating range of -25–70 °C, so the current at which the thermal element trips shifts with ambient temperature, something to remember in outdoor DC enclosures in the Gulf. Electrical endurance is 3000 cycles on an inductive load with L/R = 2 ms; the mechanical endurance of 20000 cycles is higher because it counts no-load operations.
Selection checklist and RFQ details for the A9N61501
Check these points.
- System voltage: up to 250 V DC, and the prospective short-circuit current of the source at that voltage.
- Polarity: terminals marked, so wiring drawings must show positive and negative.
- Load: 1 A rated current, against the cable and the load.
- Space: 18 mm of rail.
- Lockout: padlock in position O.
With your enquiry, send:
- Part number A9N61501 and quantity.
- DC system voltage and source type (battery, rectifier, PV).
- Delivery location and date.
Installation and wiring of the A9N61501
The breaker is two modules (18 mm) wide and mounts on a 35 mm rail. It is compatible with comb busbars at top or bottom, so several DC branches can share a busbar. Tighten the power terminals to 2.5 N.m. The toggle can be padlocked in the O (open) position, which is the correct way to lock out a DC branch before maintenance. In battery circuits, always make the positive and negative connections to the terminals marked on the breaker, check polarity with a meter before closing, and remember that a battery bank remains live even when the charger is off. The datasheet lists no earth-leakage option for this device; insulation monitoring is handled elsewhere on the DC system.
Breaking capacity of the A9N61501 by DC voltage
The datasheet gives the following ultimate (Icu) and service (Ics) breaking capacities to EN/IEC 60947-2. Ics is stated as 75 % of Icu.
| DC voltage | Icu | Ics |
|---|---|---|
| 110 V DC | 20 kA | 15 kA |
| 220 V DC | 10 kA | 7.5 kA |
| 250 V DC | 6 kA | 4.5 kA |
Use the row at or above your system voltage, and compare it with the prospective short-circuit current of the battery or rectifier. A battery bank can deliver a very high fault current even at a low voltage, so verify the source data and not only the nominal voltage. The rated insulation voltage is 500 V DC with a 6 kV impulse withstand, and the overvoltage category is IV.
Where the A9N61501 is used in Oman and the GCC
DC breakers of this type are used on 24, 48, 110 and 220 V DC control and battery systems in substations, power plants, telecom sites and oil and gas facilities, and in small solar installations. A 1 A device typically feeds a single indicator, a protection relay supply or a field device. The temperature range of -25–70 °C and class 2 tropicalisation suit warm indoor battery rooms; outdoor cabinets in direct sun need shading or ventilation.
Documents and quotation
The manufacturer’s product datasheet for the A9N61501 is attached on this page for reference; it is the document to use when you verify ratings, dimensions and approvals against your own design. It lists the DC breaking capacities for this exact reference.
To receive a quotation, send the part number A9N61501 with quantity and delivery location in Oman or the GCC. Seven Star LLC replies with availability and lead time as an independent supplier based in Muscat.
Datasheets & Documents
- Datasheet Schneider Electric A9N61501 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric A9N61501 Acti9 C60H-DC 1P 1 A
Answers from our engineering team on installation, compatibility and integration.
01Is the A9N61501 for AC or DC?
It is a DC breaker; the datasheet lists network type DC with a rated operational voltage of 250 V DC. Do not use it on AC circuits.
02What is the breaking capacity of the A9N61501?
Ultimate breaking capacity is 20 kA at 110 V DC, 10 kA at 220 V DC and 6 kA at 250 V DC to EN/IEC 60947-2.
03Does polarity matter for the A9N61501?
Yes. It is a single-pole DC device with marked terminals, so positive and negative must be connected as shown on the product and in the wiring diagram.
04What are the dimensions of the A9N61501?
It is 2 modules of 9 mm wide, weighs 0.128 kg and mounts on a 35 mm DIN rail; it can be padlocked in position O.
05What rating and curve does the A9N61501 have?
It is rated 1 A at 25 degrees C with a C curve and a thermal-magnetic trip unit.


















Reviews
There are no reviews yet.