Schneider Electric GC2520M6 TeSys GC 25 A 2P 60 Hz Contactor

Description

GC2520M6 contactor: the 60 Hz, 220 to 240 V coil version of the 25 A GC contactor

The GC2520M6 is the TeSys GC 25 A two-pole modular contactor with a 220 to 240 V AC coil specified for 60 Hz control circuits. Its power section is the same as the other GC25 two-pole units: two normally open poles, AC-7a rating of 25 A, 250 V maximum operational voltage. What separates it is the coil, and the coil frequency is the reason a buyer asks for this reference instead of the 50 Hz one. Seven Star LLC supplies the GC2520M6 in Oman and the GCC as an independent supplier based in Muscat.

In the reference, GC25 gives the frame, 20 the two-pole arrangement, and M6 the mains-voltage 60 Hz coil that the datasheet title spells out as 220 to 240 V AC 60 Hz. Equipment built for North American or Asian markets and shipped to Gulf sites is the usual origin of 60 Hz control.

Technical specifications of the GC2520M6

Parameter Specification
Manufacturer / part number Schneider Electric / GC2520M6
Description Product datasheet Modular contactor, TeSys GC, AC-7a, 25A, 2NO, 220 to 240VAC 60 Hz coil
Range TeSys
Product name TeSys GC
Product or component type Modular contactor
Device short name GC25
Contactor application Lighting; Heating; Motor control
Utilisation category AC-7A; AC-7B
Poles description 2P
power pole contact composition 2 NO
[Ue] rated operational voltage <= 250 V AC
[Ie] rated operational current 25 A AC-7A; 8.5 A AC-7B
Operating position 30°/vertical
Control circuit type AC at 60 Hz
[Uc] control circuit voltage 220 to 240 V AC 60 Hz
[Uimp] rated impulse withstand 4 kV
[Ith] conventional free air thermal 25 A (at 50 °C) for power circuit
Irms rated making capacity 68 A at 400 V AC for power circuit conforming to IEC 61095
Rated breaking capacity 68 A at 400 V for power circuit conforming to IEC 61095
[Icw] rated short-time withstand 200 A 40 °C – 10 s for power circuit
Associated fuse rating 25 A gL at <= 440 V for power circuit
Average impedance 2.5 mOhm – Ith 25 A 50 Hz for power circuit
[Ui] rated insulation voltage 500 V conforming to IEC 61095; 500 V conforming to VDE 0110
Electrical durability AC-7A: 100000 cycles; AC-7B: 100000 cycles
Power dissipation per pole 1.6 W
Control type Remote control
Mounting mode Clip-on
Mounting support DIN rail; are subject to change – check with your local distributor.
Standards IEC 60947-5; IEC 61095
Connections – terminals Control circuit: screw clamp terminals 1 cable(s) 2.5 mm²flexible without cable end
Operating time 10 to 25 ms opening; 10 to 30 ms closing
Mechanical durability 1000000 cycles
Maximum operating rate 300 cyc/h 50 °C
Control circuit voltage limits Drop-out: 0.2 to 0.75 Uc at 50 Hz (at <50 °C); Operational: 0.85 to 1.1 Uc at 50 Hz (at <50 °C)
Inrush power in VA 15 VA 50 Hz (at 20 °C)
Hold-in power consumption in VA 3.8 VA 50 Hz (at 20 °C)

Matching the GC2520M6 to a 60 Hz installation

Most Gulf networks run at 50 Hz, so a 60 Hz contactor is a deliberate choice. It fits imported machines, marine and offshore packages and skids from 60 Hz countries, where the control supply is generated or transformed at 60 Hz. If the machine uses a 230 V control circuit at 50 Hz, a 50 Hz coil version is the correct neighbour instead.

The power side is unaffected by the coil frequency. Two poles switch a single-phase load up to 25 A AC-7a at up to 250 V AC, so lighting banks, heater elements and resistive loads are the natural fit.

What the 60 Hz coil means for the GC2520M6

The datasheet lists the control circuit type as AC at 60 Hz with a coil range of 220 to 240 V. Inrush is 15 VA 50 Hz (at 20 °C) and hold-in is 3.8 VA 50 Hz (at 20 °C), with the operating limits written as Drop-out: 0.2 to 0.75 Uc at 50 Hz (at <50 °C); Operational: 0.85 to 1.1 Uc at 50 Hz (at <50 °C).

Be careful when swapping coils between 50 and 60 Hz machines. A coil made for one frequency can overheat or chatter at the other, so a replacement should always carry the frequency that the control supply actually has.

GC modular contactor family compared with the GC2520M6

The five GC references below come from the same TeSys GC datasheet series and differ in current rating, pole count and coil. The highlighted row is the one on this page.

Reference Poles Rated current Coil Width Inrush Hold-in
GC2520B5 2P 25 A AC-7A / 8.5 A AC-7B 24 V AC 50 Hz 17.5 mm 15 VA 50 Hz (at 20 ° 3.8 VA 50 Hz (at 20
GC2520M6 2P 25 A AC-7A / 8.5 A AC-7B 220 to 240 V AC 60 Hz 17.5 mm 15 VA 50 Hz (at 20 ° 3.8 VA 50 Hz (at 20
GC2530M5 3P 25 A AC-7A / 8.5 A AC-7B 220 to 240 V AC 50 Hz 36 mm 34 VA 50 Hz (at 20 ° 4.6 VA 50 Hz (at 20
GC4020M5 2P 40 A AC-7A / 15 A AC-7B 220 to 240 V AC 50 Hz 36 mm 34 VA 50 Hz (at 20 ° 4.6 VA 50 Hz (at 20
GC4030M5 3P 40 A AC-7A / 15 A AC-7B 220 to 240 V AC 50 Hz 54 mm 53 VA 50 Hz (at 20 ° 6.5 VA 50 Hz (at 20

GC2520M6 ordering checklist

  • Confirm the control frequency is 60 Hz and the voltage lies in the 220 to 240 V range.
  • Check the load type: 25 A applies to AC-7a, while 8.5 A applies to AC-7b motor duty.
  • Check the number of poles needed; this is the two-pole version with 2 NO.
  • Mounting is a clip-on DIN rail module, 17.5 mm wide.
  • Look at the sale unit in the datasheet: it quotes a set quantity of 12 for this reference.
  • Compare the part with the existing nameplate if you replace a unit, since the coil code is on the front.

Where a 60 Hz GC2520M6 turns up in Oman and the GCC

Typical sites are imported packaged plant: desalination and water-treatment skids, camp and accommodation equipment, workshop machines and marine auxiliaries built to 60 Hz standards. The contactor often drives a heater, a lighting contactor circuit or a small auxiliary load inside such a package.

For spares, the 60 Hz coil is the detail that people forget. Keeping the GC2520M6 as a labelled spare avoids a machine standing idle because only the 50 Hz variant was in stock.

Installing the GC2520M6

Clip the module on the rail, wire the 60 Hz coil to A1 and A2 and the load across the two power poles. Screw clamps on both circuits are tightened to 0.8 N.m according to the datasheet.

After energising the circuit, check that the coil does not hum. Hum or heat points to a wrong frequency or a supply with high harmonic content, and it is much cheaper to find that at commissioning than after the first summer.

Information to send with an RFQ for the GC2520M6

  • Full reference and quantity required
  • Coil voltage and frequency available on site
  • Load type and current (resistive, lighting or motor)
  • Number of poles and enclosure space available
  • Delivery location and timing

Documents and quotation

A datasheet for the GC2520M6 is attached on this page. It carries the electrical, mechanical and environmental data summarised above, so the figures can be checked against your drawings.

Send the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Other Models in the Se Tesys Gc Range

Seven Star LLC supplies models from the Se Tesys Gc range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric GC2520B5 TeSys GC 25 A 2P ContactorContactors & Overload RelaysView details
Schneider Electric GC2520M6 TeSys GC 25 A 2P 60 Hz ContactorContactors & Overload RelaysYou are viewing this model
Schneider Electric GC4020M5 TeSys GC 40 A 2P ContactorContactors & Overload RelaysView details
Schneider Electric GC4030M5 TeSys GC 40 A 3P ContactorContactors & Overload RelaysView details
Datasheets & Documents
  • PDF Datasheet Schneider Electric GC2520M6 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric GC2520M6 TeSys GC 25 A 2P 60 Hz

Answers from our engineering team on installation, compatibility and integration.

01Is the GC2520M6 a 50 Hz or 60 Hz coil?
The datasheet lists the control circuit as AC at 60 Hz with a 220 to 240 V coil.
02What current does the GC2520M6 switch?
It is rated 25 A in AC-7a and 8.5 A in AC-7b, on two normally open poles at up to 250 V AC.
03What is the rated impulse withstand of the GC2520M6?
The datasheet gives 4 kV, with a rated insulation voltage of 500 V.
04What temperature range is listed for the GC2520M6?
The ambient air temperature range is -40 to 70 degrees C and the altitude limit is 3000 m.
05How many modules does the GC2520M6 occupy?
One 18 mm module, 17.5 mm wide. See the datasheet linked on this page for the full figures.