Schneider Electric 33570 ComPact NS1600N 1600 A 4P Breaker

Description

33570: 1600 A ComPact NS1600N 4-pole breaker, MicroLogic 5.0

The 33570 is a fixed-mounting Schneider Electric ComPact NS molded-case circuit breaker rated 1600 A at 50 °C, listed in the datasheet as: circuit breaker Compact NS1600N – Micrologic 5.0 – 1600 A – 4 poles 4t. Seven Star LLC supplies it in Oman and the GCC as an independent supplier based in Muscat.

The device short name in the datasheet is Compact NS1600N. In this naming the digits give the frame current class, and the letter N is the breaking-capacity level: the datasheet’s performance level reads N 50 kA at 415 V AC. The trip unit is MicroLogic 5.0, an LSI electronic unit, and the device has 4 protected poles (4D), with the neutral pole on the left.

Please note that the datasheet carries a discontinued notice dated 30 Sep 2024. Seven Star LLC can still quote the 33570 where stock or alternatives exist, but availability should be confirmed before it is specified for a new project; for a like-for-like replacement we need the full nameplate of the breaker being replaced.

Technical specifications of the 33570

Parameter Specification
Manufacturer / part number Schneider Electric / 33570
Range ComPacT NS630b…1600
Device short name Compact NS1600N
Product type Circuit breaker, distribution application
Poles / protected poles 4P / 4D (neutral on the left)
Rated current In 1600 A at 50 °C (trip unit rating 1600 A at 50 °C)
Rated operational voltage Ue 690 V AC 50/60 Hz
Rated insulation voltage Ui / impulse Uimp 800 V AC / 8 kV
Suitability for isolation Yes, conforming to EN/IEC 60947-2; utilisation category B
Ultimate breaking capacity Icu at 380/415 V 50 kA (performance level N)
Short-time withstand Icw 19.2 kA for 1 s
Trip unit MicroLogic 5.0, electronic, protection functions LSI
Mounting Fixed, on backplate; front connections upstream and downstream, 70 mm pitch
Mechanical durability 10000 cycles
Electrical durability 1000 cycles at 690 V In; 2000 at 690 V In/2; 2000 at 440 V In; 5000 at 440 V In/2
Power losses 74 W
Auxiliary contact 1 NO/NC
Dimensions W x H x D 280 mm x 327 mm x 147 mm
Net weight 18 kg
Degree of protection IP40 (IEC 60529), IK07 (EN 50102)
Ambient temperature, operation -25 to 70 °C
Certifications listed ASTA, ASEFA
Warranty 18 months

MicroLogic 5.0 settings on the 33570

The MicroLogic 5.0 is an LSI unit: long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. The added short-time stage is what lets this breaker ride through a brief fault for a chosen time while a downstream breaker clears it, which is the basis of time-delayed selectivity on a distribution board.

Long-time pick-up Ir runs from 0.4 to 1 x In in 9 settings, so on this 33570 (In = 1600 A) from 640 A to 1600 A. The long-time delay tr is 12.5 to 600 s at 1.5 x Ir, 0.5 to 24 s at 6 x Ir and 0.7 to 16.6 s at 7.2 x Ir, with a 20 minute thermal memory.

The short-time pick-up Isd is adjustable from 1.5 to 10 x Ir in 9 settings, up to 16,000 A at Ir = 1600 A (calculated). The short-time delay tsd is 0 to 0.4 s with I²t off and 0.1 to 0.4 s with I²t on. The instantaneous pick-up Ii is 2 to 15 x In, or Off; for this rating that is 3,200 A to 24,000 A when it is in use.

Breaking capacity of the 33570 by voltage

The datasheet lists the following ratings, conforming to IEC 60947-2. Icu is the ultimate breaking capacity; Ics is the rated service breaking capacity.

Voltage (AC 50/60 Hz) Icu (kA) Ics (kA)
220/240 V 85 37
380/415 V 50 37
440 V 50 37
500/525 V 40 30
660/690 V 30 22

For the 1600 A frame the service breaking capacity Ics is lower than Icu: 37 kA at 380/415 V against 50 kA Icu, so the Ics/Icu ratio is not 100 %.

Icw is 19.2 kA for 1 s; utilisation category B.

Current rating, poles and heat in the panel for the 33570

At 415 V a three-phase load of 1600 A corresponds to roughly 1,150 kVA (calculated as √3 x 415 V x 1600 A; not a datasheet value). The datasheet gives the rated current as 1600 A at 50 °C, with the device operating in ambient temperatures up to 70 °C, so in a hot switchroom the loading of the 33570 should be checked against the manufacturer’s derating information rather than assumed to be 1600 A.

The 33570 is the four-pole version: 280 mm wide and 18 kg, against 210 mm and 14 kg for the three-pole reference of the same rating. The neutral is on the left. The datasheet lists neutral protection settings of no protection (3D), 0.5 x Ir (3D + N/2) and 1 x Ir (4D), so the neutral can be left unprotected, set to half the phase pick-up or set equal to it. Four-pole breakers are chosen for TN-S systems with significant third-harmonic or unbalanced single-phase load, and where the neutral must be switched by the same device.

The datasheet states power losses of 74 W for this device. That heat stays inside the enclosure, so when several breakers sit in one cubicle their dissipation is added to the busbar and cable losses when the cooling or ventilation is sized.

Related ComPact NS references

Seven Star LLC also handles other ComPact NS references. Check poles, trip unit and breaking-capacity level before substituting any of them for the 33570.

33568 is NS1600N with 3 poles instead of 4.

Accessories such as release coils, rotary handles and motor mechanisms are separate part numbers; send them with the breaker reference for a complete quotation.

Installing and maintaining the 33570

Before energising, check that the 33570 is mounted on its backplate, that busbars or cable lugs match the 70 mm connection pitch and that the contact surfaces are clean. Then set the trip unit: Ir first, then tr, then the short-circuit thresholds. Record the settings on the single-line diagram. Because the unit is LSI, the Isd and tsd settings must be coordinated with the downstream breakers, and if Ii is set to Off the short-circuit stage relies on Isd alone.

The trip unit has 4 red LEDs for fault indication and 1 yellow LED for overload, a first diagnosis after a trip. Electrical durability is 1000 cycles at 690 V In; 2000 at 690 V In/2; 2000 at 440 V In; 5000 at 440 V In/2; use it when planning inspection intervals.

With IP40 and IK07 protection and pollution degree 3, the 33570 belongs inside an enclosed switchboard; the stated humidity limit is 0 to 95 %.

Where the 33570 is used in Oman and the GCC

A 1600 A rating is used on the larger incomers and bus-section positions: the LV side of a 1000 kVA class transformer, central chiller plants, compressor houses and the main board of an industrial building. In the Gulf the real constraints are ambient temperature in electrical rooms, dust from desert wind and humidity near the coast, which is why enclosure ventilation and the breaker’s operating ambient of up to 70 °C deserve a check. The MicroLogic 5.0 with its short-time stage gives a selective-capable device for boards with several tiers of protection.

Information to send with an RFQ for the 33570

To quote quickly and correctly, please send:

  • Reference 33570 and quantity; also state whether a replacement for an existing device is intended, since the datasheet shows it as discontinued.
  • Poles needed (4) and, for a four-pole device, the neutral protection setting expected.
  • System voltage, available fault level at the board and the intended Icu level (N).
  • Trip unit required (MicroLogic 5.0) and whether the settings will be supplied by the protection study.
  • Control type (toggle or rotary handle) and any accessories required.
  • Delivery location in Oman or the GCC, required documents and target date.

Documents and quotation

The official English datasheet for the 33570 is attached on this page. It lists the electrical data, trip-unit settings, dimensions and environmental information used above, and carries the discontinued notice mentioned earlier.

To request a quotation, send the part number 33570, the quantity and the delivery location. Seven Star LLC is an independent supplier in Muscat and quotes according to current availability.

Other Models in the Se Compact Ns Range

Seven Star LLC supplies models from the Se Compact Ns range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric 33363 ComPact NS1600N 3P Micrologic 5.0ACircuit BreakersView details
Schneider Electric 33466 ComPact NS800N 3P Micrologic 2.0Circuit BreakersView details
Schneider Electric 33470 ComPact NS800H 4P Micrologic 2.0Circuit BreakersView details
Schneider Electric 33480 ComPact NS1250N 4P Micrologic 2.0Circuit BreakersView details
Schneider Electric 33546 ComPact NS630bN 630 A 3P BreakerCircuit BreakersView details
Schneider Electric 33555 ComPact NS800N 800 A 4P BreakerCircuit BreakersView details
Schneider Electric 33564 ComPact NS1250N 1250 A 3P BreakerCircuit BreakersView details
Schneider Electric 33570 ComPact NS1600N 1600 A 4P BreakerCircuit BreakersYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric 33570 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric 33570 ComPact NS1600N 1600 A 4P

Answers from our engineering team on installation, compatibility and integration.

01What is the rated current of the 33570?
The datasheet gives 1600 A at 50 °C, with a trip unit rating of 1600 A at 50 °C. Ir can be set between 0.4 and 1 x In.
02Does the 33570 have a short-time protection stage?
Yes. The MicroLogic 5.0 is an LSI unit with an adjustable short-time pick-up of 1.5 to 10 x Ir and a delay of up to 0.4 s.
03What is the breaking capacity of the 33570?
Icu is 50 kA at 380/415 V AC and 30 kA at 660/690 V AC; Ics at 380/415 V is 37 kA, all conforming to IEC 60947-2.
04Is the 33570 still in production?
The datasheet carries a discontinued notice dated 30 Sep 2024. Confirm availability or an alternative with us before specifying it.
05What are the dimensions and weight of the 33570?
The datasheet gives 280 mm wide, 327 mm high, 147 mm deep and 18 kg, with 4 poles and the neutral on the left.