Brand: Schneider Electric
Schneider Electric A9F90204 iC60L 2P 4A MA Circuit Breaker
Description
A9F90204: two-pole 4 A MA-curve miniature circuit breaker
The A9F90204 is a Schneider Electric Acti9 iC60L miniature circuit-breaker, listed in the datasheet as iC60L – miniature circuit breaker – 2P – 4A – MA curve. It is a magnetic-only motor-application breaker: the datasheet lists the application as Motor, the trip unit as magnetic and the network type as AC. The datasheet gives a breaking capacity of 40 kA Icu at 220–240 V AC under EN/IEC 60947-2 and also lists 380–415 V AC and 440 V AC bands. Seven Star LLC supplies the A9F90204 in Oman and the GCC as an independent supplier based in Muscat.
The datasheet for this reference carries the date 8 Nov 2026 and does not state a lifecycle status, so confirm availability before ordering. A 4 A rating is typical for control-panel auxiliaries: small power supplies, contactor coil groups, panel fans and instrument feeders. The datasheet also lists compatibility with add-on residual current devices: Vigi iC60 single terminal add-on residual current device 25/40/63 A; Quick Vigi iC60 single terminal add-on residual current device 25/40 A.
Technical specifications of the A9F90204
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / A9F90204 |
| Range / product name | Acti9 / Acti9 iC60 |
| Product type | Miniature circuit-breaker |
| Device short name | iC60L |
| Device application | Motor |
| Poles | 2P (2 protected poles) |
| Rated current [In] | 4 A |
| Curve / trip unit | Curve MA, magnetic |
| Network type / frequency | AC, 50/60 Hz |
| Magnetic tripping limit | 12 x In ± 20 % |
| Rated operational voltage [Ue] | 220–240 V AC 50/60 Hz; 380–415 V AC 50/60 Hz; 440 V AC 50/60 Hz |
| Rated insulation voltage [Ui] | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Rated impulse withstand [Uimp] | 6 kV conforming to EN/IEC 60947-2 |
| Mounting | Clip-on on rail, 4 pitches of 9 mm |
| Height / width / depth | 85 mm / 36 mm / 78.5 mm |
| Net weight | 0.25 kg |
| Terminals | Top or bottom, single terminal: 25 mm² rigid, 16 mm² flexible |
| Stripping length / torque | 14 mm for top or bottom connection; 2 N.m top or bottom |
| Durability | 20000 cycles mechanical; 10000 cycles electrical |
| Handle / indication | Toggle, contact position indicator, trip indicator |
| Protection / environment | IP20 conforming to IEC 60529; IP40 in modular enclosure (Insulation class II) conforming to IEC 60529; pollution degree 3; overvoltage category IV; tropicalisation 2 |
| Humidity / temperature | 95 % at 55 °C; operation -35–70 °C; storage -40–85 °C |
Breaking capacity of the A9F90204 by voltage band
Breaking capacity is the figure that decides whether a breaker can be installed at a given point of the network. Icu is the ultimate capacity; Ics is the service capacity, expressed as a share of Icu, after which the device is still expected to remain serviceable. For the A9F90204 the datasheet lists the following.
| Voltage band | Icu | Ics |
|---|---|---|
| 220–240 V AC 50/60 Hz | 40 kA | 20 kA (50 % of Icu) |
| 380–415 V AC 50/60 Hz | 20 kA | 10 kA (50 % of Icu) |
| 440 V AC 50/60 Hz | 15 kA | 7.5 kA (50 % of Icu) |
Compare these values with the prospective fault current at the installation point; if the supply side can exceed them, the design needs a higher-rated device or upstream back-up protection.
Information to send with an RFQ for the A9F90204
- Full reference (A9F90204) and quantity
- Supply voltage, frequency and AC or DC use at the installation point
- Prospective short-circuit current and the load or cable the breaker protects
- Existing board, rail and neighbouring devices, including any add-on residual current device
- Delivery location, timing, and whether the order is a spare or a new installation
The A9F90204 within the iC60L MA-curve listing
No other 2P reference of this curve appears in this listing, so this unit stands alone at its pole count here. The table lists every reference of this device and curve that appears in our catalogue range.
| Reference | Poles | Rated current | Icu at 220–240 V AC |
|---|---|---|---|
| A9F90204 (this page) | 2P | 4 A | 40 kA |
Where the A9F90204 is used in Oman and the GCC
In Oman and the GCC the iC60 family appears in commercial buildings, industrial distribution boards, utility auxiliary panels and process cabinets. This unit fits circuits where a 4 A two-pole MA-curve breaker with this fault capacity is needed in a compact 9 mm module. Gulf plant rooms combine heat, dust and humidity; the datasheet gives operation from -35–70 °C, relative humidity of 95 % at 55 °C and tropicalisation class 2, so site conditions should be compared against these limits and against the derating practice of the board builder.
Installation and maintenance of the A9F90204
This unit clips onto a rail; the datasheet lists the mounting mode as clip-on. Strip conductors to 14 mm and tighten terminals to 2 N.m, using a calibrated screwdriver. Terminals accept 25 mm² rigid and 16 mm² flexible conductors at either the top or the bottom. The datasheet lists suitability for isolation, so the open breaker can serve as a disconnection point; follow the site lock-out procedure when working downstream.
Check periodically that the trip indicator is clear, that the handle moves freely and that terminals have not discoloured. Mechanical durability is 20000 cycles and electrical durability is 10000 cycles. A device that has cleared a heavy fault should be inspected and replaced rather than assumed intact.
2P construction of the A9F90204
As a two-pole device, it opens two conductors together, typically phase and neutral of a single-phase circuit or two phases of a line-to-line load, and occupies four 9 mm pitches (36 mm) of rail. Both poles are tied by the common handle, so a fault on either one opens both. Compared with two single-pole units it also gives a cleaner, shorter busbar arrangement in the board.
Net weight is 0.25 kg and the body is 36 mm wide, 85 mm high and 78.5 mm deep, so a panel layout should reserve 36 mm of rail per device plus a small gap for heat when several breakers sit side by side.
Using a 4 A rating: what the A9F90204 protects
Low-current ratings need attention to cable and load rather than to fault level. A very small breaker does not protect a cable against anything the cable could not already survive, so its job is mostly to isolate a faulty control feeder quickly and to give the maintenance team a visible, labelled switch point.
The MA curve is a magnetic-only characteristic with an instantaneous trip at 12 × In ± 20 %. It is intended for motor circuits where overload protection comes from a separate thermal device, such as a thermal relay or motor protection relay in the starter, while the breaker clears short circuits.
Documents and quotation
A datasheet for this unit is attached on this page. It lists the electrical, mechanical and environmental data summarised above and should be read together with the manufacturer’s installation instructions.
Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.
Datasheets & Documents
- Datasheet Schneider Electric A9F90204 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric A9F90204 iC60L 2P 4A MA Circuit
Answers from our engineering team on installation, compatibility and integration.
01What is the rated current of the A9F90204?
The datasheet gives 4 A, with a MA curve and a magnetic trip unit. The magnetic tripping limit is 12 x In plus or minus 20 %.
02What breaking capacity does the A9F90204 have at 230 V AC?
The datasheet lists 40 kA Icu for the 220 to 240 V AC band, with a service capacity Ics of 20 kA. Compare it with the prospective fault current at the installation point.
03How wide is the A9F90204 and how many poles does it have?
It is a 2P device, 36 mm wide, 85 mm high and 78.5 mm deep, occupying 4 pitches of 9 mm on the rail.
04What conductors fit the A9F90204 terminals?
The datasheet lists single terminals at top or bottom for 25 mm2 rigid and 16 mm2 flexible conductors, with a tightening torque of 2 N.m.
05Can the A9F90204 be used on DC circuits?
The datasheet lists network type AC and gives no DC breaking capacity for this reference, so do not apply it to DC circuits without confirming with the manufacturer.