Schneider Electric 33363 ComPact NS1600N 3P Micrologic 5.0A
Description
33363: ComPact NS1600N 3P breaker with MicroLogic 5.0 A
The 33363 is a ComPact NS1600N fixed-mounted circuit breaker, three poles with three protected poles (3D), rated 1600 A, with a MicroLogic 5.0 A electronic trip unit and the datasheet performance level “N 50 kA 415 V AC”. Seven Star LLC supplies the 33363 in Oman and the GCC as an independent supplier based in Muscat.
Reading the name: NS marks the ComPact NS630b to 1600 range, 1600 is the rating in amperes at 50 °C, and the letter N is the performance level. The N performance level is rated 50 kA at 415 V AC according to the datasheet, with 30 kA Icu at 660/690 V.
Status note: the datasheet for the 33363 marks it as discontinued on 30 Sep 2024. It is therefore mainly relevant to maintenance, spares and like-for-like replacement of an existing installation. If you are designing a new board, ask us which current reference applies to the same duty and we will check the manufacturer documents before quoting, instead of assuming that a sibling is a drop-in.
Trip unit and settings of the 33363
This version carries the MicroLogic 5.0 A trip unit with long-time, short-time and instantaneous protection, which the datasheet abbreviates as LSI. It adds adjustable short-time pick-up of 1.5 to 10 x Ir with a delay of 0.1 to 0.4 s, and the datasheet states that zone selective interlocking is available. An LCD display with ammeter function and indicator LEDs complete the front of the unit.
With In = 1600 A the long-time pick-up can be set from about 640 A (0.4 x In) to 1600 A. The instantaneous pick-up spans 2 to 15 x In, which corresponds to roughly 3200 A up to 24000 A, and it can also be switched off, as the datasheet lists Off as an option.
The long-time delay tr is listed as 12.5 to 600 s at 1.5 x Ir; 0.5 to 24 s at 6 x Ir; 0.7 to 16.6 s at 7.2 x Ir and the thermal memory is 20 mn. These figures matter for coordination with upstream and downstream devices, so request a coordination study if the 33363 will sit between a transformer and several outgoing feeders.
33363 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / 33363 |
| Description | Circuit breaker, ComPact NS1600N, 50kA/415VAC, Micrologic 5.0A trip unit, 1600A, fixed, 3 poles 3d |
| Number of poles / protected poles | 3P / 3D |
| Rated current (In) | 1600 A at 50 °C |
| Rated operational voltage [Ue] | 690 V AC 50/60 Hz |
| Utilisation category | Category B |
| Performance level | N 50 kA 415 V AC |
| Ultimate breaking capacity [Icu] | 30 kA at 660/690 V AC; 50 kA at 380/415 V AC; 50 kA at 440 V AC; 85 kA at 220/240 V AC; 40 kA at 500/525 V AC |
| Service breaking capacity [Ics] | 30 kA at 500/525 V AC; 37 kA at 220/240 V AC; 37 kA at 380/415 V AC; 22 kA at 660/690 V AC; 37 kA at 440 V AC |
| Short-time withstand [Icw] | 19.2 kA 1 s conforming to IEC 60947-2 |
| Trip unit | MicroLogic 5.0 A, Electronic, protection LSI |
| Mounting mode / support | Fixed / Backplate |
| Long-time pick-up [Ir] | 0.4 to 1 x In |
| Long-time delay [tr] | 12.5 to 600 s at 1.5 x Ir; 0.5 to 24 s at 6 x Ir; 0.7 to 16.6 s at 7.2 x Ir |
| Short-time pick-up [Isd] | 1.5 to 10 x Ir |
| Short-time delay [tsd] | 0.1 to 0.4 s I²t=on; 0 to 0.4 s I²t=off |
| Instantaneous pick-up [Ii] | 2 to 15 x In; Off |
| Earth-leakage protection / ZSI | Without / With |
| Display / measurement | LCD display / Ammeter |
| Auxiliary contact composition | 1 NO/NC |
| Mechanical durability | 10000 cycles |
| Electrical durability | 1000 cycles at 690 V In; 2000 cycles at 690 V In/2; 2000 cycles at 440 V In; 5000 cycles at 440 V In/2 |
| Power losses | 74 W |
| Connections / pitch | Front (top), Front (bottom) / 70 mm |
| Dimensions (W x H x D) | 210 mm x 327 mm x 147 mm |
| Net weight | 14 kg |
| Standards | EN/IEC 60947-2 |
| Certifications | ASTA; ASEFA |
| Degree of protection | IP40 conforming to IEC 60529; IK07 conforming to EN 50102 |
| Ambient temperature (operation) | -25 to 70 °C |
| Status | Discontinued on 30 Sep 2024 (as marked on the datasheet) |
Breaking capacity and ratings of the 33363
The full Icu and Ics lists are in the table above; the figure to carry into a fault study is 50 kA Icu at 380/415 V AC, with 30 kA at 660/690 V AC.
Short-time withstand current Icw is 19.2 kA 1 s conforming to IEC 60947-2, the insulation voltage is 800 V AC 50/60 Hz conforming to IEC 60947-2 and the impulse withstand is 8 kV conforming to IEC 60947-2.
Discontinued status and replacement planning for the 33363
Discontinued does not stop installed 33363 units from working, and the datasheet figures stay valid for them; what changes is availability. For a like-for-like swap, match the rated current of 1600 A, the poles (3P), the breaking capacity (50 kA at 380/415 V), the trip unit type and the size of 210 mm x 327 mm x 147 mm with its 70 mm connection pitch. Send us a nameplate photograph and we will compare it against the datasheet.
Size, weight and mounting of the 33363
The 33363 is a fixed breaker for mounting on a backplate, with front connections at the top and bottom on a 70 mm pitch. The body measures 210 mm wide, 327 mm high and 147 mm deep and weighs 14 kg. Power losses are listed as 74 W, a figure to include in the heat balance of the enclosure.
Being a three-pole device, it is 210 mm wide, narrower than the 280 mm of the four-pole frames in this group, and it weighs 14 kg. There is no neutral pole, so a neutral conductor, if present, runs separately.
Information to send with an RFQ for the 33363
Because the item is discontinued, please include:
- Part number 33363 and quantity.
- Nameplate photograph of the existing breaker, if replacing one.
- System voltage, frequency and prospective fault current.
- Trip unit settings in use and any accessories fitted.
- Delivery location and the date by which you need the breaker.
Site conditions for the 33363 in Oman and the GCC
The datasheet lists an operating ambient of -25 to 70 °C, relative humidity of 0 to 95 %, IP40 with IK07 and pollution degree 3 conforming to IEC 60947. The operating altitude is 0 to 2000 m without derating; 2000 m to 5000 m with derating.
In Oman these breakers sit in main low-voltage switchboards at substations, desalination and water plants, industrial power houses and large buildings. Summer heat inside the switchboard, dust and coastal humidity are the usual risks, so compare the room temperature with the figures above.
ComPact NS comparison table around the 33363
The twelve references in this group of datasheets cover the 800, 1000, 1250 and 1600 A ratings in N and H performance levels, in three and four poles. Every row below carries a discontinued flag on its datasheet.
| Part number | Model | Poles | In (A) | Trip unit | Icu at 380/415 V |
|---|---|---|---|---|---|
| 33363 | NS1600N | 3P | 1600 | ML 5.0 A | 50 kA |
| 33466 | NS800N | 3P | 800 | ML 2.0 | 50 kA |
| 33467 | NS800H | 3P | 800 | ML 2.0 | 70 kA |
| 33469 | NS800N | 4P | 800 | ML 2.0 | 50 kA |
| 33470 | NS800H | 4P | 800 | ML 2.0 | 70 kA |
| 33472 | NS1000N | 3P | 1000 | ML 2.0 | 50 kA |
| 33473 | NS1000H | 3P | 1000 | ML 2.0 | 70 kA |
| 33475 | NS1000N | 4P | 1000 | ML 2.0 | 50 kA |
| 33478 | NS1250N | 3P | 1250 | ML 2.0 | 50 kA |
| 33479 | NS1250H | 3P | 1250 | ML 2.0 | 70 kA |
| 33480 | NS1250N | 4P | 1250 | ML 2.0 | 50 kA |
| 33481 | NS1250H | 4P | 1250 | ML 2.0 | 70 kA |
Documents and quotation
The manufacturer datasheet for this reference is attached on this page, so you can compare the figures quoted here with the original before you commit to a design or a purchase order.
To proceed, send the part number, the quantity and a few lines about the installation and we will reply with availability and a quotation. Seven Star LLC works as an independent supplier in Muscat with no affiliation to the manufacturer.
Other Models in the Se Compact Ns Range
Seven Star LLC supplies models from the Se Compact Ns range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric 33363 ComPact NS1600N 3P Micrologic 5.0A | Circuit Breakers | You are viewing this model |
| Schneider Electric 33466 ComPact NS800N 3P Micrologic 2.0 | Circuit Breakers | View details |
| Schneider Electric 33470 ComPact NS800H 4P Micrologic 2.0 | Circuit Breakers | View details |
| Schneider Electric 33480 ComPact NS1250N 4P Micrologic 2.0 | Circuit Breakers | View details |
| Schneider Electric 33555 ComPact NS800N 800 A 4P Breaker | Circuit Breakers | View details |
| Schneider Electric 33564 ComPact NS1250N 1250 A 3P Breaker | Circuit Breakers | View details |
Datasheets & Documents
- Datasheet Schneider Electric 33363 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric 33363 ComPact NS1600N 3P
Answers from our engineering team on installation, compatibility and integration.
01Is the 33363 still in production?
The datasheet marks it as discontinued on 30 Sep 2024. Existing breakers remain valid in service, but availability depends on remaining stock, so confirm status and lead time before planning around it.
02What breaking capacity does the 33363 have?
The datasheet lists 50 kA Icu at 380/415 V AC and 30 kA at 660/690 V AC, with the performance level shown as N 50 kA 415 V AC.
03Which trip unit is fitted to the 33363?
MicroLogic 5.0 A, an electronic unit with LSI protection. It includes an LCD display, an ammeter function and zone selective interlocking.
04What are the dimensions and weight of the 33363?
The datasheet gives 210 mm wide, 327 mm high and 147 mm deep, with a net weight of 14 kg.
05How is the 33363 mounted and connected?
It is a fixed breaker on a backplate with front connections top and bottom at a 70 mm pitch.