Schneider Electric 33480 ComPact NS1250N 4P Micrologic 2.0

Description

33480: ComPact NS1250N 4P breaker with MicroLogic 2.0

The 33480 is a ComPact NS1250N fixed-mounted circuit breaker, four poles with all four protected (4D), rated 1250 A, with a MicroLogic 2.0 electronic trip unit and the datasheet performance level “N 50 kA 415 V AC”. Seven Star LLC supplies the 33480 in Oman and the GCC as an independent supplier based in Muscat.

Reading the name: NS marks the ComPact NS630b to 1600 range, 1250 is the rating in amperes at 50 °C, and the letter N is the performance level. The N performance level is rated 50 kA at 415 V AC according to the datasheet, with 30 kA Icu at 660/690 V.

Status note: the datasheet for the 33480 marks it as discontinued on 30 Sep 2024. It is therefore mainly relevant to maintenance, spares and like-for-like replacement of an existing installation. If you are designing a new board, ask us which current reference applies to the same duty and we will check the manufacturer documents before quoting, instead of assuming that a sibling is a drop-in.

Information to send with an RFQ for the 33480

Because the item is discontinued, please include:

  • Part number 33480 and quantity.
  • Nameplate photograph of the existing breaker, if replacing one.
  • System voltage, frequency and prospective fault current.
  • Trip unit settings in use and any accessories fitted.
  • Delivery location and the date by which you need the breaker.

Size, weight and mounting of the 33480

The 33480 is a fixed breaker for mounting on a backplate, with front connections at the top and bottom on a 70 mm pitch. The body measures 280 mm wide, 327 mm high and 147 mm deep and weighs 18 kg. Power losses are listed as 44 W, a figure to include in the heat balance of the enclosure.

As a four-pole device it is 280 mm wide against 210 mm for the three-pole frames in this group, and it weighs 18 kg against 14 kg. The neutral position is left, and the neutral protection setting can be none (3D), 0.5 x Ir (3D + N/2) or 1 x Ir (4D).

33480 technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / 33480
Description circuit breaker Compact NS1250N – Micrologic 2.0 – 1250 A – 4 poles 4t
Number of poles / protected poles 4P / 4D
Neutral position Left
Rated current (In) 1250 A at 50 °C
Rated operational voltage [Ue] 690 V AC 50/60 Hz
Utilisation category Category B
Performance level N 50 kA 415 V AC
Ultimate breaking capacity [Icu] 30 kA at 660/690 V AC; 50 kA at 380/415 V AC; 50 kA at 440 V AC; 85 kA at 220/240 V AC; 40 kA at 500/525 V AC
Service breaking capacity [Ics] 30 kA at 660/690 V AC; 40 kA at 500/525 V AC; 50 kA at 220/240 V AC; 50 kA at 380/415 V AC; 50 kA at 440 V AC
Short-time withstand [Icw] 19.2 kA 1 s conforming to IEC 60947-2
Trip unit MicroLogic 2.0, Electronic, protection LI
Mounting mode / support Fixed / Backplate
Long-time pick-up [Ir] 0.4 to 1 x In
Long-time delay [tr] 12.5 to 600 s at 1.5 x Ir; 0.5 to 24 s at 6 x Ir; 0.7 to 16.6 s at 7.2 x Ir
Instantaneous pick-up [Ii] 1.5 to 10 x Ir
Neutral protection settings No protection (3D); 0.5 x Ir (3D + N/2); 1 x Ir (4D)
Earth-leakage protection / ZSI Without / Without
Auxiliary contact composition 1 NO/NC
Mechanical durability 10000 cycles
Electrical durability 2000 cycles at 690 V In; 3000 cycles at 690 V In/2; 4000 cycles at 440 V In; 5000 cycles at 440 V In/2
Power losses 44 W
Connections / pitch Front (top), Front (bottom) / 70 mm
Dimensions (W x H x D) 280 mm x 327 mm x 147 mm
Net weight 18 kg
Standards EN/IEC 60947-2
Certifications ASTA; ASEFA
Degree of protection IP40 conforming to IEC 60529; IK07 conforming to EN 50102
Ambient temperature (operation) -25 to 70 °C
Status Discontinued on 30 Sep 2024 (as marked on the datasheet)

ComPact NS comparison table around the 33480

The twelve references in this group of datasheets cover the 800, 1000, 1250 and 1600 A ratings in N and H performance levels, in three and four poles. Every row below carries a discontinued flag on its datasheet.

Part number Model Poles In (A) Trip unit Icu at 380/415 V
33363 NS1600N 3P 1600 ML 5.0 A 50 kA
33466 NS800N 3P 800 ML 2.0 50 kA
33467 NS800H 3P 800 ML 2.0 70 kA
33469 NS800N 4P 800 ML 2.0 50 kA
33470 NS800H 4P 800 ML 2.0 70 kA
33472 NS1000N 3P 1000 ML 2.0 50 kA
33473 NS1000H 3P 1000 ML 2.0 70 kA
33475 NS1000N 4P 1000 ML 2.0 50 kA
33478 NS1250N 3P 1250 ML 2.0 50 kA
33479 NS1250H 3P 1250 ML 2.0 70 kA
33480 NS1250N 4P 1250 ML 2.0 50 kA
33481 NS1250H 4P 1250 ML 2.0 70 kA

Site conditions for the 33480 in Oman and the GCC

The datasheet lists an operating ambient of -25 to 70 °C, relative humidity of 0 to 95 %, IP40 with IK07 and pollution degree 3 conforming to IEC 60947. The operating altitude is 0 to 2000 m without derating; 2000 m to 5000 m with derating.

In Oman these breakers sit in main low-voltage switchboards at substations, desalination and water plants, industrial power houses and large buildings. Summer heat inside the switchboard, dust and coastal humidity are the usual risks, so compare the room temperature with the figures above.

Discontinued status and replacement planning for the 33480

Discontinued does not stop installed 33480 units from working, and the datasheet figures stay valid for them; what changes is availability. For a like-for-like swap, match the rated current of 1250 A, the poles (4P), the breaking capacity (50 kA at 380/415 V), the trip unit type and the size of 280 mm x 327 mm x 147 mm with its 70 mm connection pitch. Send us a nameplate photograph and we will compare it against the datasheet.

Breaking capacity and ratings of the 33480

The full Icu and Ics lists are in the table above; the figure to carry into a fault study is 50 kA Icu at 380/415 V AC, with 30 kA at 660/690 V AC.

Short-time withstand current Icw is 19.2 kA 1 s conforming to IEC 60947-2, the insulation voltage is 800 V AC 50/60 Hz conforming to IEC 60947-2 and the impulse withstand is 8 kV conforming to IEC 60947-2.

Trip unit and settings of the 33480

This version carries the MicroLogic 2.0 trip unit, which gives long-time and instantaneous protection (LI) only; there is no short-time stage and the datasheet lists zone selective interlocking as Without.

With In = 1250 A the long-time pick-up can be set from about 500 A (0.4 x In) to 1250 A. The instantaneous pick-up is 1.5 to 10 x Ir, so with Ir at its maximum the top setting works out to about 12500 A; at a lower Ir the instantaneous threshold falls in proportion.

The long-time delay tr is listed as 12.5 to 600 s at 1.5 x Ir; 0.5 to 24 s at 6 x Ir; 0.7 to 16.6 s at 7.2 x Ir and the thermal memory is 20 mn. These figures matter for coordination with upstream and downstream devices, so request a coordination study if the 33480 will sit between a transformer and several outgoing feeders.

Documents and quotation

The manufacturer datasheet for this reference is attached on this page, so you can compare the figures quoted here with the original before you commit to a design or a purchase order.

To proceed, send the part number, the quantity and a few lines about the installation and we will reply with availability and a quotation. Seven Star LLC works as an independent supplier in Muscat with no affiliation to the manufacturer.

Other Models in the Se Compact Ns Range

Seven Star LLC supplies models from the Se Compact Ns range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric 33470 ComPact NS800H 4P Micrologic 2.0Circuit BreakersView details
Schneider Electric 33480 ComPact NS1250N 4P Micrologic 2.0Circuit BreakersYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric 33480 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric 33480 ComPact NS1250N 4P

Answers from our engineering team on installation, compatibility and integration.

01Is the 33480 still in production?
The datasheet marks it as discontinued on 30 Sep 2024. Existing breakers remain valid in service, but availability depends on remaining stock, so confirm status and lead time before planning around it.
02What breaking capacity does the 33480 have?
The datasheet lists 50 kA Icu at 380/415 V AC and 30 kA at 660/690 V AC, with the performance level shown as N 50 kA 415 V AC.
03Which trip unit is fitted to the 33480?
MicroLogic 2.0, an electronic unit with LI protection. Long-time and instantaneous settings are adjustable; there is no short-time stage or ZSI.
04What are the dimensions and weight of the 33480?
The datasheet gives 280 mm wide, 327 mm high and 147 mm deep, with a net weight of 18 kg.
05How is the 33480 mounted and connected?
It is a fixed breaker on a backplate with front connections top and bottom at a 70 mm pitch.