- Automation & ControlView all 2,701 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Motor Soft Starters
- CCTV & Security
- Encoders
- HMI Displays
- Servo Drives
- Pneumatic Cylinders
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: MTL (Eaton)
MTL MTL7710+ Single-Channel Zener Barrier, 10 V 50 ohm 200 mA
Description
MTL7710+ overview
The MTL7710+ is a single-channel positive-polarity zener barrier for low-voltage circuits. It carries a safety description of 10 V, 50 ohm and 200 mA, and the correlation table in the datasheet lists the typical application as 4/6 V systems. It is a basic passive barrier, so there is no electronics to fail and no power supply to connect.
The MTL7710+ belongs to the MTL7700 range of DIN-rail mounting safety barriers, the successor to the long-established MTL700 series. The range has been used worldwide since 1984. As a single-channel module, this barrier installs on standard 35 mm top-hat rail without special hardware, and the removable plug-in terminals allow a loop to be disconnected simply by unplugging the terminal block. This page lists the figures from the manufacturer literature so that engineers can check suitability before sending an enquiry.
Key features of the MTL MTL7710+
- Safety description: 10 V, 50 ohm, 200 mA
- Polarity: Positive (negative version MTL7710- also listed)
- Maximum end-to-end resistance is 75 ohm, which keeps the voltage drop low for sensor circuits at a few volts.
- Working voltage at the leakage specification is 6.0 V and the maximum voltage is 7.0 V.
- The correlation table shows the MTL7710+/- as the DIN-rail successor to the MTL710+/-.
- Removable terminals accept conductors up to 2.5 mm squared (13 AWG), with hazardous-area terminals marked by blue labels
- Certified ia for all zones and IIC gases unless stated otherwise on the data table
MTL7710+ technical specifications
| Parameter | Value |
|---|---|
| Model | MTL7710+ |
| Range | MTL7700 DIN-rail safety barriers |
| Safety description | 10 V, 50 ohm, 200 mA |
| Polarity | Positive (negative version MTL7710- also listed) |
| Channels | 1 |
| Maximum end-to-end resistance | 75 ohm |
| Working voltage | 6.0 V |
| Maximum voltage | 7.0 V |
| Fuse rating | 50 mA |
| Maximum safe-area voltage Um | 250 V ac or dc |
| Ambient temperature, working | minus 20 to plus 60 degrees Celsius |
| Storage temperature | minus 40 to plus 80 degrees Celsius |
| Humidity | 5 to 95 percent RH |
| Mounting | 35 mm top-hat DIN rail |
| Weight | approximately 140 g |
Typical applications of the MTL7710+ in Oman and the GCC
The manufacturer lists the following duty for the MTL7710+: Low-voltage 4 V and 6 V dc systems in hazardous areas. In the Gulf region the MTL7700 barriers appear mostly in brownfield upgrades where an existing marshalling cabinet is being extended and the original barrier type must be matched exactly.
- Oil and gas: wellhead, separator and compressor instrumentation where field devices sit in classified areas
- Utilities and power generation: turbine auxiliaries, fuel gas skids and boiler instrumentation
- Water and desalination: chemical dosing and treatment areas with flammable vapour risk
- Manufacturing and petrochemical: solvent handling, storage tanks and loading bays
Plants that were commissioned with MTL700 or MTL7000 barriers often need a like-for-like part, and the datasheet correlation table was written for that purpose: it shows each model against its earlier equivalents.
Selection and compatibility notes for the MTL7710+
Check that the normal operating voltage of the field circuit stays below the 6.0 V working voltage, otherwise leakage current can disturb a sensitive signal. For circuits near 12 V, the MTL7715+ or MTL7767+ is the appropriate step up in the same range. This barrier is not suitable for 24 V loops.
Shunt-diode barriers need a high-integrity intrinsic safety earth, which this barrier provides through its DIN-rail connection, so the rail must be bonded to the plant IS earth by the route given in the installation manual. Always check the field device certificate for its maximum input parameters and the cable capacitance and inductance, since the barrier certificate sets the permitted values. The maximum safe-area voltage Um for the whole range is 250 V.
Installation and commissioning
Clip the module onto the rail, connect the safe-area wiring to terminals 1 and 2 (and 5 and 6 on dual units) and the hazardous-area wiring to the blue-labelled terminals 3 and 4 (and 7 and 8). Verify that the rail earth resistance meets the project requirement before energising. Mark each module with the loop tag using the tag holder, and keep intrinsically safe and non-intrinsically safe wiring segregated, as required by installation codes. Before connecting the field cable, measure the loop with the barrier fitted and compare it with the loop drawing. Hazardous-area terminals can be unplugged to isolate a loop during testing.
Maintenance and spare parts
A barrier has no moving parts, so routine work is limited to checking terminal tightness, the rail earth connection and the labels. If the fuse has blown, replace the whole module rather than attempting repair, and investigate the safe-area fault that caused it. Terminal spares are listed in the range datasheet: safe-area terminals SAF7712 and SAF7756, hazardous-area terminals HAZ7734 and HAZ7778, and the tag holder TH7700, each supplied in packs of 10.
Related products and ordering notes
Accessories for this barrier include the PB7700 power bus, the BPL7700 bussed power links, the TAG57 tagging strip and the DX070 and DX170 enclosures. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Because many MTL7700 models have similar numbers, quote the full part number MTL7710+ including any plus, minus or ac suffix, since the suffix defines the polarity and the safety description.
MTL7710+ FAQ summary
Typical questions concern the safety description, polarity and replacement of earlier MTL700 units. The data is 10 V, 50 ohm, 200 mA, and the table above gives its resistance and voltage data. Questions about hazardous-area certification should be checked against the current certificate listed on the manufacturer website.
Documents and quotation
The range datasheet EPS7700 is attached to this page and covers specifications, wiring diagrams and ordering information. To request a quotation, send an RFQ with the part number MTL7710+, the quantity and your delivery location in Oman or the GCC, and we will reply with availability and lead time.
Other Models in the MTL7700 Range
Seven Star LLC supplies models from the MTL7700 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| MTL MTL7728+ Zener Safety Barrier, 28 V 300 ohm 93 mA | Isolator & Barrier | View details |
| MTL MTL7706+ Overvolt-Protected Transmitter Barrier, 28 V 300 ohm 93 m | Isolator & Barrier | View details |
| MTL MTL7707+ 2-Channel Overvolt-Protected Barrier, 28 V 300 ohm 93 mA | Isolator & Barrier | View details |
| MTL MTL7710+ Single-Channel Zener Barrier, 10 V 50 ohm 200 mA | Isolator & Barrier | You are viewing this model |
Datasheets & Documents
- Datasheet MTL7700 Range Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
MTL is a British maker of intrinsic safety interfaces, surge protection and hazardous-area equipment, founded in 1971 in Luton as Measurement Technology Ltd, a spin-off from Kent Instrumentation. In 2008 Cooper Industries bought MTL Instruments for £144 million and placed it in its Crouse-Hinds division; Eaton acquired Cooper in 2012. MTL is now part of Eaton's Crouse-Hinds business, alongside the MEDC signalling range.
Seven Star LLC lists MTL isolators, a fieldbus barrier and the configuration tools for them, and supplies MTL (Eaton) barriers and spare modules to sites in Oman as an independent supplier.
MTL (Eaton) company profile
| Founded | 1971, Luton, England, as Measurement Technology Ltd |
|---|---|
| Origin | Spin-off from Kent Instrumentation |
| Headquarters | Luton, England |
| Ownership | Eaton (Crouse-Hinds), via Cooper Industries from 2008 |
| Product families | MTL5500 and MTL4500 isolators, MTL7700 zener barriers, 9300 fieldbus barriers, surge protection devices, process junction boxes, PCS45 configuration software; MEDC beacons, sounders and call points |
Milestones
- 1971: Measurement Technology Ltd is founded in Luton.
- 2007: MTL acquires ELPRO Technologies, RTK Instruments and Ocean Technical Systems.
- 2008: Cooper Industries acquires MTL Instruments for £144 million.
- 2012: Eaton acquires Cooper Industries.
MTL product families listed here
Most of the listed items are DIN-rail galvanic isolators. The MTL5541 repeater power supply and the MTL5576-THC temperature converter belong to the MTL5500 range, and the MTL 5043 repeater power supply comes from the earlier MTL5000 range that many plants still run. The MTL 9370-FB2 is a fieldbus barrier for intrinsically safe FOUNDATION fieldbus spurs. PCS45 software with the PCL45USB link is the configurator for MTL converter modules. For the listed part CPM08-BN, please send a label photo so the number can be matched to the manufacturer's records. Newer labels show Eaton MTL, older ones Measurement Technology Ltd, and the module numbers are the same. The MTL 9608 is a fieldbus junction box with eight spur outlets plus a trunk-in connection, listed under the Crouse-Hinds series part number FCS-9608.
Where MTL barriers and isolators are used
These interfaces sit in marshalling cabinets wherever instruments are located in Zone 0, 1 or 2 areas: gas plants, refineries, offshore platforms, tank farms and chemical units across the GCC. They power 2-wire transmitters, pass HART, convert thermocouple signals and drive solenoids or alarms while limiting energy to the field circuit.
MTL (Eaton) products we list
Ordering MTL modules: what we need
Send the full module number including every suffix, for example MTL5576-THC and not just MTL5576, and the quantity. Tell us if the module mounts on DIN rail or on a backplane, because MTL5500 and MTL4500 parts are not interchangeable. For a fieldbus barrier give the number of spurs and the enclosure reference. A photo of the side label, which shows the certificate numbers, helps when the certificate for your project file must match.
Facts checked against the Eaton MTL company history and Drives & Controls coverage of the 2008 Cooper offer, October 2026.
Browse MTL (Eaton) products by category: Isolator & Barrier, Automation Software.
FAQ
Questions about the MTL MTL7710+ Single-Channel Zener Barrier, 10 V 50
Answers from our engineering team on installation, compatibility and integration.
01What is the MTL7710+ used for?
The manufacturer lists it for: Low-voltage 4 V and 6 V dc systems in hazardous areas.
02What is the safety description of the MTL7710+?
The datasheet gives 10 V, 50 ohm, 200 mA; the range is certified ia for all zones and IIC gases except where noted.
03Does the MTL7710+ need an intrinsic safety earth?
Yes. Shunt-diode barriers rely on a high-integrity intrinsic safety earth, which in the MTL7700 range is made through the DIN rail mounting.
04How is the MTL7710+ mounted?
It clips onto standard 35 mm top-hat DIN rail with removable plug-in terminals that accept conductors up to 2.5 mm squared.
05How do I request a quotation for the MTL7710+?
Send an RFQ with the part number MTL7710+, quantity and delivery location in Oman or the GCC, and we will reply with availability and lead time.