MTL MTL5022 Loop-Powered Solenoid/Alarm Driver IIB

Description

MTL5022 overview

The MTL5022 is a loop-powered solenoid and alarm driver for IIB applications from the MTL5000 Series. It lets a switch or voltage change in the safe area control a device in the hazardous area. The unit can drive any certified intrinsically safe low-power load, as well as non-energy-storing simple apparatus such as an LED. Its input and output are isolated, so the control switch can be connected into either side of the 24 V dc supply circuit, which gives wiring flexibility in cabinets where the switching contact is on the positive or the negative rail.

Because the MTL5022 is loop-powered, the same 20 to 35 V dc connection that powers the module also supplies the energy delivered to the hazardous-area load, and no separate signal input is needed. A yellow LED shows the status of the output. According to the datasheet, the load may be located in Zone 0 for IIB gases, with temperature classes T4 to T6 if suitably certified, or in a Division 1 Group C location. The datasheet for the MTL5022 is dated August 2008.

Key features of the MTL MTL5022

  • One channel, loop-powered, designed for IIB hazardous-area loads
  • Output current limit of 60 mA, with at least 12.9 V available at 60 mA
  • Maximum open-circuit output voltage 24 V from 133 ohm, with an equivalent circuit shown in the datasheet
  • Isolated input and output, so the control contact can switch either side of the 24 V dc supply
  • Earth-leakage detection connection on terminal 3 for use with an earth-leakage detector
  • Yellow LED indicates the status of the output
  • Plug-in terminals and slim MTL5000 housing for DIN rail mounting
  • Supply 20 to 35 V dc with 115 mA typical consumption at 24 V

MTL5022 technical specifications

Values below are from the MTL5022 datasheet. Check the certification label on the supplied module before commissioning.

Parameter Value
Model MTL5022 solenoid/alarm driver, loop-powered, IIB
Channels One
Load location Zone 0, IIB, T4-6 if suitably certified; Div. 1, Group C
Input voltage 20 to 35 V dc
Minimum output voltage 12.9 V at 60 mA
Maximum output voltage 24 V from 133 ohm
Current limit 60 mA
Maximum current consumption (60 mA output) 115 mA typical at 24 V; 135 mA maximum at 20 to 35 V dc
Maximum power dissipation 1.5 W at 24 V; 2.1 W at 35 V
Indicator Yellow LED, status
Safety description 25 V, 135 ohm, 185 mA; Um 250 V rms or dc
Terminals 1 output -ve, 2 output +ve, 3 earth-leakage detection, 11 supply -ve, 12 supply +ve
Mounting 35 mm top-hat DIN rail, plug-in terminals (MTL5000 Series)
Ambient limits (MTL5000 Series, unenclosed, close-packed) -20 to +60 degrees C

The manufacturer’s instruction manual notes that the MTL5022 is suitable for IIA and IIB applications. The datasheet equivalent circuit shows an output that falls from its maximum voltage towards 12.9 V as the load current rises to the 60 mA limit, so always calculate the load against the output characteristic rather than a fixed voltage.

Typical applications in oil and gas, utilities, water and manufacturing

A solenoid driver like the MTL5022 is the standard way to operate intrinsically safe solenoid valves, beacons and sounders in classified areas. In oil and gas facilities in Oman, it commonly drives low-power solenoids on wellhead panels, pneumatic actuators on tank-farm valves, and warning devices at loading bays, controlled by a relay contact or a PLC output in the safe area. The ability to switch either side of the supply makes it easy to add to existing 24 V dc control circuits.

In utilities and water treatment, the MTL5022 is used for solenoids on biogas and fuel systems and for hazardous-area indicators in pump stations. Manufacturing plants in the GCC with classified zones, for example solvent stores or fuel handling, use the same module for alarm beacons. Because it is loop-powered, no second supply cable to the hazardous area is needed.

Selection and compatibility notes for MTL5022

Check that the intrinsically safe solenoid or alarm is certified for the output parameters of the MTL5022 (25 V, 135 ohm, 185 mA) and for the gas group of the installation. Compare the operating voltage and current of the load with the output characteristic: the minimum output is 12.9 V at 60 mA, which suits low-power IS solenoids but not high-power valves. For IIC gases or for loads that need more power, other drivers in the MTL range should be reviewed.

Make sure the control contact or output in the safe area can handle the 115 to 135 mA supply current and the 24 V dc circuit, and decide whether to use the earth-leakage detection terminal 3. If line fault detection or a voltage-free input is needed instead, the MTL5023 driver in the same range has those features.

Installation and commissioning

Before mounting the MTL5022, confirm the hazardous-area apparatus and the cable parameters against the entity values on the nameplate and in the manufacturer certificate, and decide where the intrinsic safety earth will be taken. Mount the unit on the 35 mm top-hat DIN rail in a clean enclosure or cabinet in the safe area, keeping hazardous-area and safe-area wiring physically separated and clearly labelled. Wire the control switch into the supply circuit as shown in the datasheet diagram; either side of the 24 V supply may be switched thanks to the isolation. If an earth-leakage detector is used, connect terminal 3 as shown in the manufacturer’s diagram.

Wire the MTL5022 strictly to the terminal table in the datasheet, tighten the terminal screws to the specified torque and check that no strands are left outside the clamp. Where the unit carries a certificate, the earth connection and the rail must meet the requirements stated there. After wiring, apply the supply, check the power indication, and simulate the field signal to prove the end-to-end loop before the plant is declared ready. Record the as-found readings for future loop checks of the MTL5022.

Maintenance and service life

The MTL5022 has no user-serviceable parts, so maintenance is mainly periodic inspection. During planned shutdowns, inspect terminals for corrosion and looseness, verify the supply voltage at the unit, and repeat the loop check recorded at commissioning. In coastal or humid locations around Muscat, Sohar and Duqm, a sealed or purged cabinet with a clean, dry interior greatly extends the life of any electronic interface such as the MTL5022.

If a loop drifts outside its tolerance or the unit shows no power indication with a healthy supply, replace the module rather than attempting repair, and keep the replacement documentation with the loop folder. Because certified intrinsically safe equipment must not be modified, any change in cabling, load or hazardous-area device should be re-assessed against the MTL5022 entity parameters before it is put into service.

Related products and ordering notes

Customers who enquire about the MTL5022 often also need matching accessories and neighbouring models from the same family, such as the MTL5023 solenoid/alarm driver with line fault detection, other MTL5000 drivers and repeaters, power bus kits and the MTL5099 dummy isolator. Tell us the solenoid make and gas group so we can confirm suitability before you order.

When you send an enquiry for the MTL5022, please quote the full part number exactly as printed on the nameplate, the quantity, and the intended application. If you are replacing an installed unit, a photograph of the nameplate helps us confirm the MTL5022 you need. Our team can arrange a quotation with delivery to Oman and across the GCC.

Frequently asked questions about MTL5022

The MTL5022 is a one-channel loop-powered IIB solenoid and alarm driver. It runs from 20 to 35 V dc, limits output to 60 mA, isolates input and output so either supply side can be switched, and carries a safety description of 25 V, 135 ohm and 185 mA.

Documents and quotation

A copy of the datasheet for the MTL5022 is available on this page for your engineering review. To request a quotation, send the RFQ with the part number MTL5022, the quantity, the delivery location and any certification or documentation requirements, and we will respond with availability and lead time. Please review the specification against your loop or system requirements before ordering.

Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with MTL. Product names and part numbers are used only to identify the item you ask for.

Other Models in the MTL5000 Range

Seven Star LLC supplies models from the MTL5000 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
MTL MTL5043 Dual-Output 4-20 mA Repeater Power SupplyIsolator & BarrierView details
MTL MTL5042 Repeater Power Supply for 2- or 3-Wire TransmittersIsolator & BarrierView details
MTL MTL5022 Loop-Powered Solenoid/Alarm Driver IIBIsolator & BarrierYou are viewing this model
Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

MTL is a British maker of intrinsic safety interfaces, surge protection and hazardous-area equipment, founded in 1971 in Luton as Measurement Technology Ltd, a spin-off from Kent Instrumentation. In 2008 Cooper Industries bought MTL Instruments for £144 million and placed it in its Crouse-Hinds division; Eaton acquired Cooper in 2012. MTL is now part of Eaton's Crouse-Hinds business, alongside the MEDC signalling range.

Seven Star LLC lists MTL isolators, a fieldbus barrier and the configuration tools for them, and supplies MTL (Eaton) barriers and spare modules to sites in Oman as an independent supplier.

MTL (Eaton) company profile

Founded 1971, Luton, England, as Measurement Technology Ltd
Origin Spin-off from Kent Instrumentation
Headquarters Luton, England
Ownership Eaton (Crouse-Hinds), via Cooper Industries from 2008
Product families MTL5500 and MTL4500 isolators, MTL7700 zener barriers, 9300 fieldbus barriers, surge protection devices, process junction boxes, PCS45 configuration software; MEDC beacons, sounders and call points

Milestones

  • 1971: Measurement Technology Ltd is founded in Luton.
  • 2007: MTL acquires ELPRO Technologies, RTK Instruments and Ocean Technical Systems.
  • 2008: Cooper Industries acquires MTL Instruments for £144 million.
  • 2012: Eaton acquires Cooper Industries.

MTL product families listed here

Most of the listed items are DIN-rail galvanic isolators. The MTL5541 repeater power supply and the MTL5576-THC temperature converter belong to the MTL5500 range, and the MTL 5043 repeater power supply comes from the earlier MTL5000 range that many plants still run. The MTL 9370-FB2 is a fieldbus barrier for intrinsically safe FOUNDATION fieldbus spurs. PCS45 software with the PCL45USB link is the configurator for MTL converter modules. For the listed part CPM08-BN, please send a label photo so the number can be matched to the manufacturer's records. Newer labels show Eaton MTL, older ones Measurement Technology Ltd, and the module numbers are the same. The MTL 9608 is a fieldbus junction box with eight spur outlets plus a trunk-in connection, listed under the Crouse-Hinds series part number FCS-9608.

Where MTL barriers and isolators are used

These interfaces sit in marshalling cabinets wherever instruments are located in Zone 0, 1 or 2 areas: gas plants, refineries, offshore platforms, tank farms and chemical units across the GCC. They power 2-wire transmitters, pass HART, convert thermocouple signals and drive solenoids or alarms while limiting energy to the field circuit.

MTL (Eaton) products we list

Family Examples
Isolator & Barrier Eaton MTL5541 Repeater Power Supply, MTL 5043, MTL 9370-FB2 Intrinsically Safe Fieldbus…, MTL CPM08-BN, MTL5576-THC Temperature Isolator Module
Automation Accessories MTL 9608 Process Junction Box
Automation Software MTL PCS45 Configuration Software and PCL…

Ordering MTL modules: what we need

Send the full module number including every suffix, for example MTL5576-THC and not just MTL5576, and the quantity. Tell us if the module mounts on DIN rail or on a backplane, because MTL5500 and MTL4500 parts are not interchangeable. For a fieldbus barrier give the number of spurs and the enclosure reference. A photo of the side label, which shows the certificate numbers, helps when the certificate for your project file must match.

Facts checked against the Eaton MTL company history and Drives & Controls coverage of the 2008 Cooper offer, October 2026.

FAQ

Questions about the MTL MTL5022 Loop-Powered Solenoid/Alarm Driver IIB

Answers from our engineering team on installation, compatibility and integration.

01What does the MTL5022 do?
It lets a safe-area switch or voltage change control an intrinsically safe solenoid, alarm or similar low-power load in a hazardous area, powered from a 20 to 35 V dc loop.
02What is the output limit of the MTL5022?
The datasheet gives a 60 mA current limit with at least 12.9 V at 60 mA and a maximum of 24 V from 133 ohm.
03Which gas group is the MTL5022 for?
The datasheet describes a IIB unit with the load in Zone 0, IIB, T4 to T6 if suitably certified, or Division 1 Group C.
04What are the MTL5022 safety parameters?
The datasheet states 25 V, 135 ohm and 185 mA with Um 250 V rms or dc.