Lovato ADXL0060600 Soft Starter 60 A with Built-in Bypass

Description

Lovato ADXL0060600 soft starter, 60 A with built-in bypass

The Lovato ADXL0060600 is a soft starter for three-phase asynchronous motors with a rated current of 60 A and a built-in bypass. It supports supply voltages from 208 to 600 V AC and an IEC motor rating of 30 kW at 400 V. Seven Star LLC supplies the ADXL0060600 in Oman and the GCC as an independent supplier in Muscat.

The code is read as ADXL for the family, 0060 for 60 A and 600 for the 600 V class. Two phases are controlled by thyristors, and the third passes straight through, which keeps the unit compact. Larger parts in the same family include the ADXL0085600 and the ADXL0115600, and a variant with 24 V auxiliary supply carries a 024 suffix.

ADXL0060600 technical specifications

Parameter Specification
Manufacturer / part number Lovato / ADXL0060600
Motor type Three-phase asynchronous
Rated supply voltage 208 to 600 V AC, 50/60 Hz
Auxiliary supply Us 100 to 240 V AC
Rated current Ie 60 A
Motor power in-line, IEC (40 °C) 15 kW at 230 V; 30 kW at 400 V; 37 kW at 500 V
Motor power, UL 20 HP at 220-240 V; 30 HP at 380-415 V; 40 HP at 440-480 V; 50 HP at 550-600 V
Controlled phases / bypass 2 / built-in
Start methods Torque ramp, voltage ramp, constant torque, each with current limit
Stop methods Torque ramp, voltage ramp, free-wheel
Interface Backlit LCD, NFC programming, optical port, 6 languages
Digital I/O 3 inputs (one configurable for PTC); 3 outputs (2 NO plus 1 changeover)
Temperature -20 to +60 °C, derating 0.5 percent per degree above 40 °C
Altitude 1000 m without derating
Dimensions and weight 75 x 218 x 171.5 mm; 2.1 kg
Protection degree IP00

How the ADXL0060600 starts a motor

Instead of applying full voltage, the starter uses thyristors to raise motor voltage gradually. In voltage-ramp mode the voltage grows in a set time, while in torque-ramp mode the controller estimates the torque and shapes it, which gives a smoother mechanical start for pumps and conveyors. A current limit can cap the starting current in either mode, protecting a weak supply or a generator.

When the motor reaches speed, the built-in bypass contacts close and carry the current, removing the thyristors from the circuit. Heat and losses then drop to a very low level, so the 60 A starter can sit in a normal panel with natural cooling or optional forced cooling. At stop, a torque ramp or a voltage ramp can slow the motor gently, which prevents water hammer in pumping lines.

Protection functions of the ADXL0060600

The motor protection set covers overload at start and during running with selectable trip classes, locked rotor, current asymmetry and minimum torque for dry-run detection. Supply protection includes phase loss, phase sequence, frequency and voltage limits. The starter protects itself against overcurrent, overtemperature, bypass failure, shorted phase, sensor failure and cooling fan failure, and it asks for maintenance with a counter.

ADXL0060600 in the control system

Three digital inputs accept start, stop, reset and other programmable functions; the third can be switched to a PTC thermistor input. Three outputs include a line contactor command, a run indication and a global alarm. A clock, event log, hour counter and start counter support maintenance. For other sizes the neighbours are the ADXL0045600 (45 A), ADXL0085600 (85 A) and ADXL0135600 (135 A).

ADXL0060600 selection checklist

  • Motor nameplate current well within 60 A
  • Supply voltage between 208 and 600 V AC
  • Auxiliary supply of 100 to 240 V AC available
  • Load type, to choose torque or voltage ramp
  • Starts per hour, which sets the thermal sizing
  • Ambient temperature and altitude derating
  • Enclosure with IP20 or better, since the unit itself is IP00

Installing and commissioning the ADXL0060600

Mount vertically with the clearances given in the manual, by screws or on rail with the accessory EXP8003. Connect line to the input side, motor to the output, and feed the control supply separately. Because the housing is IP00, finger-safe covers or a closed panel are required.

Program the motor current, start ramp, current limit and trip class from the front keypad, or use NFC from a phone. Run an unloaded test, then a loaded start, and save the event log. Check the starter temperature after the first hours of operation.

Typical ADXL0060600 applications in Oman and the GCC

At 30 kW and 400 V, the starter suits water pumps, booster sets, fans and compressors at utilities, hotels and light industry. High site temperatures matter: above 40 °C the rated current falls by 0.5 percent per degree, so a hot panel in July will reduce capacity.

ADXL family members

Part Rated current 400 V power
ADXL0045600 45 A Smaller pumps
ADXL0060600 60 A 30 kW
ADXL0085600 85 A Medium pumps
ADXL0115600 115 A 55 kW
ADXL0135600 135 A Larger pumps

Soft starters and variable speed drives are often compared. A soft starter controls only the starting and stopping of a motor at fixed speed, while a drive also changes speed in operation. For a pump or fan that always runs at full speed after start, the soft starter is simpler, smaller and cheaper in operating losses because the bypass removes the heat. If the process needs flow control, a drive from the VLB range is the better answer, and our team can discuss both options against the duty.

Information to send with an RFQ for the ADXL0060600

  • Part number ADXL0060600 and quantity
  • Motor power, voltage and current
  • Load and starting duty
  • Control supply voltage
  • Panel temperature and cooling
  • Delivery location

Documents and quotation

Send the part number ADXL0060600 and we will confirm the documents available for it, such as the technical data sheet, wiring diagram and instruction sheet, together with availability and lead time.

Seven Star LLC is an independent supplier in Muscat and is not an official channel of the manufacturer. Share the quantity, delivery location and project reference with the request and we will answer with a formal quotation.

Other Models in the Lovato Adxl Softstarter Range

Seven Star LLC supplies models from the Lovato Adxl Softstarter range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Lovato ADXL0075600 Soft Starter 75 A with BypassMotor Soft StartersView details
Lovato ADXL0060600 Soft Starter 60 A with Built-in BypassMotor Soft StartersYou are viewing this model
Lovato ADXL0115600 Soft Starter 115 A with Built-in BypassMotor Soft StartersView details
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.

Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.

Lovato Electric at a glance

Established 1922, Bergamo, Italy
Headquarters Gorle (Bergamo), Italy
Ownership Private, family-run for four generations
Product families Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs

Lovato products we list

Family Models Typical use
Contactors BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing Switching motors, heaters, lighting and capacitor banks
Motor protection and starters SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay Short-circuit and overload protection and direct starting of motors
Soft starters ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 Reducing starting current and mechanical shock on pumps, fans and compressors
Variable speed drives VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 Speed control of pumps, fans and conveyors to save energy
Power management and control DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC Power factor correction, mains/generator changeover and energy monitoring

Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.

Where Lovato products are used

In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.

Ordering Lovato products: what we need

Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.

Facts checked against Lovato Electric company profile brochures, October 2026.

FAQ

Questions about the Lovato ADXL0060600 Soft Starter 60 A with Built-in

Answers from our engineering team on installation, compatibility and integration.

01What current is the ADXL0060600 rated for?
The rated starter current is 60 A, equal to 30 kW at 400 V under IEC conditions at 40 degrees C.
02Does it have a bypass?
Yes, a built-in bypass is fitted, which removes the thyristor losses once the motor has reached speed.
03How many phases are controlled?
The data sheet lists two controlled phases.
04What start methods are available?
Torque ramp, voltage ramp and constant torque, each with current limit.
05What protection degree does it have?
The degree is IP00, so it must be installed inside an enclosure.