Brand:

Eaton NZMS2-A160 Molded Case Circuit Breaker 160 A 70 kA

Description

Eaton NZMS2-A160 molded case circuit-breaker, 160 A, higher breaking capacity

The Eaton NZMS2-A160 (catalog number 109964) is the higher-breaking-capacity sibling of the NZMN2-A160: a three-pole NZM2 molded case circuit-breaker with a thermomagnetic release for 160 A. The sheet lists a breaking capacity of 70 kA at 400/415 V, compared with 50 kA for the N version, and 65 kA at 440 V. It is meant for installations where the prospective short-circuit current at the board is high, such as boards close to large transformers. Seven Star LLC supplies the NZMS2-A160 in Oman and the GCC for switchgear builders and contractors.

What the NZMS2-A160 designation means

NZM is the molded case breaker series and 2 the frame size. The letter S marks a higher breaking-capacity class than the standard N, so the NZMS2-A160 and the NZMN2-A160 share frame, release and 160 A rating, but differ in the short-circuit values. A160 is the thermomagnetic release for 160 A with overload setting 125 to 160 A. Catalog number 109964 identifies this device; the sheet title calls it NZM2 TMTU, three-pole, 160 A, with screw terminal.

NZMS2-A160 technical specifications

Parameter Specification
Manufacturer / part number Eaton NZMS2-A160 (catalog number 109964)
Series Eaton Moeller NZM molded case circuit-breaker
Frame size NZM2
Number of poles Three-pole
Release system Thermomagnetic release
Rated current / amperage rating 160 A
Overload current setting Ir 125 – 160 A
Instantaneous current setting Ii 960 – 1600 A
Rated operational voltage 690 V AC; 750 V DC rating listed
Rated insulation voltage Ui 1000 V AC
Rated impulse withstand voltage Uimp, main / auxiliary contacts 8000 V / 6000 V
Utilization category A (IEC/EN 60947-2)
Overvoltage category III
Rated short-time withstand current, 0.3 s and 1 s 1.9 kA
Short-circuit total break time Less than 10 ms
Handle Rocker lever
Mounting Fixed built-in; DIN rail mounting optional
Degree of protection IP20 basic; IP40 front with insulating surround; IP66 with door-coupling rotary handle; terminals IP10 (tunnel) / IP00
Protection against direct contact Finger and back-of-hand proof, DIN EN 50274 / VDE 0106 part 110
Shock resistance 20 g (half-sinusoidal, 20 ms)
Ambient storage temperature −25 to 70 °C
Maximum operations per hour 120
Short-circuit breaking capacity, 230 V 100 kA
Short-circuit breaking capacity, 400/415 V 70 kA
Short-circuit breaking capacity, 440 V 65 kA
Short-circuit breaking capacity, 525 V 36 kA
Short-circuit breaking capacity, 690 V 6 kA
Short-circuit breaking capacity, 500 V DC / 750 V DC 7.5 kA / 7.5 kA
Short-circuit making capacity Icm, 240 V / 400/415 V 220 kA / 154 kA
Short-circuit making capacity Icm, 440 V / 525 V 143 kA / 80 kA
Pollution degree 3
Mechanical lifespan 20,000 operations
Electrical lifespan 10,000 operations at 400 V AC-1; 6500 operations at 415 V AC-3; 10,000 at 415 V AC-1
Dimensions (depth x height x width) 149 x 184 x 105 mm
Weight 2.342 kg

The breaking-capacity rows follow the table in the manufacturer specification sheet for catalog number 109964; for coordination studies consult the full sheet or the NZM technical information for Icu and Ics at each voltage.

What the higher breaking capacity of the NZMS2-A160 means

Breaking capacity is the largest short-circuit current a breaker can interrupt safely. The NZMS2-A160 lists 100 kA at 230 V, 70 kA at 400/415 V, 65 kA at 440 V, 36 kA at 525 V and 6 kA at 690 V. Compared with the NZMN2-A160, the 400/415 V value is 20 kA higher and the 440 V value almost doubles from 35 to 65 kA. The making capacity rises to 154 kA at 400/415 V, which is the peak current the breaker can close onto.

The release is the same thermomagnetic design: overload setting 125 to 160 A and instantaneous setting 960 to 1600 A. The breaker is utilization category A, withstands 1.9 kA for 0.3 s and 1 s, and has an insulation voltage of 1000 V AC.

Where the NZMS2-A160 is the right choice

The S class is chosen when the calculated fault level at the installation point exceeds what the N class can interrupt. Examples are main distribution boards fed by large transformers, generator-backed boards with several machines in parallel and industrial boards in the substation itself. If the fault level is moderate, the NZMN2-A160 usually suffices and costs less in installation terms. The NZMS2-A160 lists electrical lifespan of 10,000 operations at 400 V in AC-1 and 6500 at 415 V in AC-3, so it can also be used for occasional switching of loads.

Selection checklist for the NZMS2-A160

  • Calculate the prospective short-circuit current at the board and compare with 70 kA at 400/415 V.
  • Set Ir within 125 to 160 A according to the cable or motor current.
  • Check the 690 V value: only 6 kA, so use another breaker for 690 V boards with high fault level.
  • Define accessories before ordering.
  • Check enclosure space for the 105 mm width, 184 mm height and 149 mm depth, and a weight of 2.342 kg.

Installation and maintenance of the NZMS2-A160

Mount the NZMS2-A160 on a plate or DIN rail, connect conductors to the screw terminals or rear connection and fit the terminal covers. Set Ir and Ii and test the mechanism. After a short-circuit trip inspect the breaker and the connected equipment before closing again, following the manufacturer guidance. Periodically operate the breaker and check terminals for heat marks.

Typical applications in Oman and the GCC

High fault levels occur in Gulf installations with large transformers, utility substations and generator plants. The NZMS2-A160 is used as feeder protection in such boards, in motor control centres of process plants, and in industrial buildings. High ambient temperatures call for ventilation and checks against the breaker temperature ratings.

Eaton NZM2 and neighbouring ratings

Model Rating / frame Note
NZMN2-A160 125 – 160 A 50 kA at 400/415 V, standard breaking capacity
NZMS2-A160 125 – 160 A 70 kA at 400/415 V, higher breaking capacity
NZMN2-A250 Frame NZM2, 250 A Larger NZM2 rating
NZMN1-A80 Frame NZM1, 80 A Smaller frame
NZMN3-AE400 Frame NZM3, 400 A Larger frame, electronic release

The table places the device within the NZM range; ratings of neighbouring devices must be confirmed from their own sheets.

Information to send with an RFQ for NZMS2-A160

  • Exact model NZMS2-A160 (catalog number 109964) and the quantity, including spares.
  • Prospective short-circuit current and system voltage.
  • Required Ir setting range and load type.
  • Accessories: auxiliary contacts, shunt trip, handle and terminals.
  • Delivery location (Muscat, Sohar, Salalah or elsewhere in the GCC) and the date you need the goods.
  • Any documents you need with the quotation, such as an installation leaflet or declaration of conformity.

Documents and quotation

The manufacturer specification sheet for NZMS2-A160 is attached on this page, so you can check the ratings, dimensions and approvals against your project before you order. Installation leaflets and declarations of conformity can be requested separately.

Seven Star LLC supplies Eaton industrial control products in Oman and the GCC. To request a quotation, send model NZMS2-A160, the quantity and your delivery location, and we will confirm availability and lead time for your order.

Other Models in the Eaton Nzm2 Range

Seven Star LLC supplies models from the Eaton Nzm2 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Eaton NZMN2-A160 Molded Case Circuit Breaker 160 A 3-PoleCircuit BreakersView details
Eaton NZMS2-A160 Molded Case Circuit Breaker 160 A 70 kACircuit BreakersYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Eaton NZMS2-A160 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Eaton is a power management company that began in 1911, when Joseph O. Eaton started a truck axle business in New York and moved it to Cleveland, Ohio, in 1914. It grew from vehicle components into electrical equipment, hydraulics and aerospace systems. Since buying Cooper Industries in 2012, Eaton has been incorporated in Ireland with its head office in Dublin, and it is listed on the New York Stock Exchange.

Seven Star LLC lists Eaton NZM molded case circuit breakers, PKZM0 motor-protective circuit breakers and Bussmann series Class J fuses, and supplies them to panel builders and maintenance teams in Oman and the GCC.

Eaton company profile

Founded 1911, New York, USA, by Joseph O. Eaton
Early move Cleveland, Ohio, 1914
Headquarters Dublin, Ireland, since the 2012 Cooper Industries acquisition
Listing New York Stock Exchange (ETN)
Brands Eaton, Moeller, Bussmann, Crouse-Hinds, MTL and MEDC
Product families FAZ and PL miniature circuit breakers, NZM moulded-case breakers, DILM contactors, PowerXL variable frequency drives, 9PX and 93PM UPS, Bussmann fuses, hazardous-area enclosures and signalling

Milestones

  • 1911: Joseph O. Eaton starts an axle business in New York.
  • 1914: The business moves to Cleveland.
  • 2012: Eaton acquires Cooper Industries and redomiciles in Ireland.

Eaton circuit protection listed here

The NZMN1-A80 is a frame size 1 molded case circuit breaker rated 80 A with a thermomagnetic release for cable and system protection. The PKZM0-1,6 is a motor-protective circuit breaker whose overload release is adjustable from 1 to 1.6 A, used as a manual motor starter. The LPJ-35SP is a Bussmann series Low-Peak Class J time-delay fuse rated 35 A at 600 V AC. Older NZM and PKZ devices carry the Moeller name on the nameplate, and the type designations are the same.

Where Eaton breakers and fuses are used

Motor control centers, feeder panels, machine control cabinets and UL-style fused disconnects.

Eaton products we list

Family Examples
Circuit Breakers LPJ-35SP Class J Time-Delay Fuse, NZMN1-A80 Molded Case Circuit Breaker, NZMN2-A250 Molded Case Circuit Breaker, NZMN3-AE400 Molded Case Circuit Breaker, PKZM0-1
AC Drives DA1-342D2FB-A20C AC Drive, PowerXL DG1-34140FN-C21C Variable Freque…

Ordering Eaton parts: what we need

Send the full type and article number, the number of poles, the current rating or setting range, and any accessories such as auxiliary contacts, trip releases or rotary handles.

Facts checked against Eaton's corporate history and investor materials, October 2026.

FAQ

Questions about the Eaton NZMS2-A160 Molded Case Circuit Breaker 160 A

Answers from our engineering team on installation, compatibility and integration.

01What is the breaking capacity of the NZMS2-A160?
The sheet table lists 100 kA at 230 V, 70 kA at 400/415 V, 65 kA at 440 V, 36 kA at 525 V and 6 kA at 690 V.
02What current settings does the NZMS2-A160 have?
It is a 160 A thermomagnetic breaker. The overload setting Ir is 125 to 160 A and the instantaneous setting is 960 to 1600 A.
03How does the NZMS2-A160 differ from the NZMN2-A160?
Same frame, release and 160 A rating, but higher breaking capacity: 70 kA instead of 50 kA at 400/415 V. The weight is 2.342 kg against 2.321 kg.
04What is the electrical lifespan of the NZMS2-A160?
The sheet lists 10,000 operations at 400 V AC-1, 6500 operations at 415 V AC-3 and 10,000 operations at 415 V AC-1. Mechanical lifespan is 20,000 operations.
05What are the dimensions of the NZMS2-A160?
149 mm depth, 184 mm height and 105 mm width, with a weight of 2.342 kg, as listed on the specification sheet.