Brand: Eaton
Eaton PKZM0-6,3 Motor-Protective Circuit-Breaker 4-6.3 A
Description
Eaton PKZM0-6,3 motor-protective circuit-breaker, 4–6.3 A
The Eaton PKZM0-6,3 (catalog number 072738) is a three-pole motor-protective circuit-breaker from the Eaton Moeller PKZM0 series. It protects a motor feeder against overload, phase failure and short circuit, and it doubles as the manual on/off switch for the motor. The overload release is adjustable from 4 to 6.3 A, and the rated operational power at 380/400 V, 50 Hz is 2.2 kW. Seven Star LLC supplies the PKZM0-6,3 in Oman and the GCC for panel builders, maintenance teams and machine builders who need a compact starter protection device on a DIN rail.
Reading the PKZM0-6,3 model code
PKZM0 identifies the frame: a 45 mm wide, three-pole breaker with a turn-button actuator and screw terminals. The figure after the dash is the upper end of the current setting range in amperes, written with a decimal comma, so PKZM0-6,3 covers 4 to 6.3 A and has a rated uninterrupted current of 6.3 A. The neighbouring ratings in the same frame step up in the same way, which makes it easy to pick the next device when the motor current changes. The catalog number 072738 and the EAN 4015080727385 identify this exact version.
Technical specifications of the PKZM0-6,3
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Eaton PKZM0-6,3 (catalog number 072738) |
| Series | Eaton Moeller PKZM0 |
| Product category | Motor-protective circuit-breaker |
| Number of poles | Three-pole |
| Setting range | 4 – 6.3 A |
| Rated uninterrupted current Iu | 6.3 A |
| Rated operational voltage Ue | 690 V |
| Rated operational power AC-3e, 230 V, 50 Hz | 1.1 kW |
| Rated operational power AC-3e, 380/400 V, 50 Hz | 2.2 kW |
| Rated operational power AC-3e, 440 V, 50 Hz | 3 kW |
| Rated operational power AC-3e, 500 V, 50 Hz | 3 kW |
| Rated operational power AC-3e, 690 V, 50 Hz | 4 kW |
| Rated short-circuit breaking capacity Icu / Ics at 400 V AC | 150 kA / 150 kA |
| Rated short-circuit breaking capacity Ics at 500 V AC | 42 kA |
| Rated short-circuit breaking capacity Ics at 690 V AC | 2 kA |
| Rated impulse withstand voltage Uimp | 6000 V AC |
| Overvoltage category / pollution degree | III / 3 |
| Actuator | Turn button |
| Connection | Screw terminals |
| Degree of protection | IP20; terminals IP00 |
| Ambient operating temperature | −25 to 55 °C (open); −25 to 40 °C (enclosed) |
| Ambient storage temperature | −40 to 80 °C |
| Mechanical / electrical lifespan | 100,000 operations each |
| Operating frequency | 40 operations per hour |
| Dimensions (depth x height x width) | 76 x 93 x 45 mm |
| Weight | 0.29 kg |
The data above follows the manufacturer’s catalog sheet for catalog number 072738. For the US rating of the device, the sheet gives assigned motor power of 0.25 HP at 115/120 V single-phase, 1 HP at 200/208 V three-phase, 1.5 HP at 230/240 V three-phase, 3 HP at 460/480 V three-phase and 5 HP at 575/600 V three-phase, all at 60 Hz.
How the PKZM0-6,3 protects a motor
Each pole contains a thermal release and a magnetic release. The thermal element follows the motor current over time and trips when the current stays above the set value, which covers the usual overload situations such as a blocked pump or a worn bearing. The magnetic element reacts to short-circuit current without delay and opens all three poles. The breaker is phase-failure sensitive in line with IEC/EN 60947-4-1 and VDE 0660 part 102, so it also trips when one phase is lost and the motor would otherwise run on two phases. Temperature compensation is specified for −5 to 40 °C, with a residual error of up to 0.25 %/K above 40 °C, which is useful where a panel warms up in summer. The datasheet states that motors with efficiency class IE3 are covered as well.
The turn button switches the breaker on and off by hand, and the front carries a TEST marking for checking the trip. The breaking capacity of 150 kA at 400 V is high for a device of this size. At 500 V and 690 V the values drop to 42 kA and 2 kA, and the upstream protection must be checked against these numbers.
Where the PKZM0-6,3 fits in a motor starter
The most common use is the protection element of a direct-on-line starter: the PKZM0-6,3 sits ahead of a contactor and handles overload and short-circuit protection, while the contactor does the frequent switching. Because the breaker has a rated operating frequency of only 40 operations per hour, it is not meant to be the main switching element for motors that start and stop often. The front label carries a marking for the Eaton AK-PKZ0 auxiliary contact, which can be added when the control circuit needs a status signal. Related ratings in the same frame include the PKZM0-4 (2.5 to 4 A), the PKZM0-10 (6.3 to 10 A, 4 kW at 400 V) and the PKZM0-12 (8 to 12 A).
Choosing the right PKZM0 rating
Use the checklist below before ordering a PKZM0-6,3 or a neighbouring rating.
- Take the full-load current from the motor nameplate at the actual supply voltage, not from the kW figure alone.
- Pick the range so that this current falls in the middle of the dial, not at the very end of the scale.
- Check the prospective short-circuit current at the installation point against the 400 V, 500 V or 690 V breaking capacity listed above.
- Confirm the supply voltage: the device is rated to 690 V, but the short-circuit rating falls sharply above 440 V.
- Decide whether an auxiliary contact is needed before the panel layout is fixed.
- Check the ambient conditions of the panel; the open-air rating is up to 55 °C and the enclosed rating up to 40 °C.
Installation and maintenance of the PKZM0-6,3
The PKZM0-6,3 snaps onto a 35 mm top-hat rail to IEC/EN 60715 with a height of 7.5 or 15 mm. Mount it with the turn button accessible from the front, connect the supply to terminals 1/L1, 3/L2 and 5/L3 at the top and the motor to 2/T1, 4/T2 and 6/T3 at the bottom, and tighten the screws to the torque in the instruction leaflet. After wiring, set the current dial to the motor nameplate current and switch on. During maintenance, check the terminals for discolouration, confirm the setting after any motor replacement, and exercise the turn button now and then in installations where it rarely operates. A device that trips again immediately after reset should be investigated for a motor or cable fault before it is replaced.
Typical applications in Oman and the GCC
In Oman and the wider Gulf region the PKZM0-6,3 is used on small pumps, fans, compressors, conveyor drives and gate or door motors in utilities, desalination plants, oil and gas facilities, HVAC plant rooms and light industry. Panels in these places are exposed to heat, dust and humidity, so the enclosure temperature should be checked against the 40 °C enclosed rating, and filtered ventilation or panel cooling should be used when the room is hot. With 2.2 kW rated at 400 V, the device suits small three-phase motors on auxiliary services such as dosing pumps, small circulation pumps and extraction fans.
Eaton PKZM0 family at a glance
| Model | Setting range | Typical use |
|---|---|---|
| PKZM0-4 | 2.5 – 4 A | Lower current rating in the PKZM0 range |
| PKZM0-6,3 | 4 – 6.3 A | 2.2 kW at 380/400 V, the model on this page |
| PKZM0-10 | 6.3 – 10 A | 4 kW at 380/400 V |
| PKZM0-12 | 8 – 12 A | Higher current rating in the PKZM0 range |
The table gives the family order only; the full catalog ratings of each device should be confirmed from its own data sheet before use.
Information to send with an RFQ for the PKZM0-6,3
- Eaton catalog number 072738 or model code PKZM0-6,3.
- Quantity and required delivery location.
- Motor nameplate current, voltage and power.
- Any accessory needed alongside the breaker, such as an auxiliary contact.
- Project name or end use, so that the rating and approvals can be checked against the application.
Documents and quotation
Seven Star LLC supplies Eaton industrial control products in Oman and the GCC. Send the part number PKZM0-6,3 together with the quantity and the motor data, and we will confirm availability and the documents we can provide for it.
Datasheets & Documents
- Datasheet Eaton PKZM0-6,3 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Eaton is a power management company that began in 1911, when Joseph O. Eaton started a truck axle business in New York and moved it to Cleveland, Ohio, in 1914. It grew from vehicle components into electrical equipment, hydraulics and aerospace systems. Since buying Cooper Industries in 2012, Eaton has been incorporated in Ireland with its head office in Dublin, and it is listed on the New York Stock Exchange.
Seven Star LLC lists Eaton NZM molded case circuit breakers, PKZM0 motor-protective circuit breakers and Bussmann series Class J fuses, and supplies them to panel builders and maintenance teams in Oman and the GCC.
Eaton company profile
| Founded | 1911, New York, USA, by Joseph O. Eaton |
|---|---|
| Early move | Cleveland, Ohio, 1914 |
| Headquarters | Dublin, Ireland, since the 2012 Cooper Industries acquisition |
| Listing | New York Stock Exchange (ETN) |
| Brands | Eaton, Moeller, Bussmann, Crouse-Hinds, MTL and MEDC |
| Product families | FAZ and PL miniature circuit breakers, NZM moulded-case breakers, DILM contactors, PowerXL variable frequency drives, 9PX and 93PM UPS, Bussmann fuses, hazardous-area enclosures and signalling |
Milestones
- 1911: Joseph O. Eaton starts an axle business in New York.
- 1914: The business moves to Cleveland.
- 2012: Eaton acquires Cooper Industries and redomiciles in Ireland.
Eaton circuit protection listed here
The NZMN1-A80 is a frame size 1 molded case circuit breaker rated 80 A with a thermomagnetic release for cable and system protection. The PKZM0-1,6 is a motor-protective circuit breaker whose overload release is adjustable from 1 to 1.6 A, used as a manual motor starter. The LPJ-35SP is a Bussmann series Low-Peak Class J time-delay fuse rated 35 A at 600 V AC. Older NZM and PKZ devices carry the Moeller name on the nameplate, and the type designations are the same.
Where Eaton breakers and fuses are used
Motor control centers, feeder panels, machine control cabinets and UL-style fused disconnects.
Eaton products we list
Ordering Eaton parts: what we need
Send the full type and article number, the number of poles, the current rating or setting range, and any accessories such as auxiliary contacts, trip releases or rotary handles.
Facts checked against Eaton's corporate history and investor materials, October 2026.
Browse Eaton products by category: Circuit Breaker.
FAQ
Questions about the Eaton PKZM0-6,3 Motor-Protective Circuit-Breaker
Answers from our engineering team on installation, compatibility and integration.
01What current range does the PKZM0-6,3 cover?
The overload release is adjustable from 4 A to 6.3 A and the rated uninterrupted current is 6.3 A. Set the dial to the motor nameplate current rather than to the maximum value.
02What motor power does the PKZM0-6,3 suit?
At 380/400 V and 50 Hz the rated operational power in AC-3e is 2.2 kW. At 230 V it is 1.1 kW, at 440 V and 500 V it is 3 kW and at 690 V it is 4 kW.
03What is the short-circuit breaking capacity of the PKZM0-6,3?
Icu and Ics are both 150 kA at 400 V AC. Ics is 42 kA at 500 V AC and 2 kA at 690 V AC, so the upstream protection should be checked on higher-voltage supplies.
04Does the PKZM0-6,3 protect against phase failure?
Yes. The sheet lists phase-failure sensitivity according to IEC/EN 60947-4-1 and VDE 0660 part 102, so the breaker trips when a phase is lost, in addition to overload and short-circuit protection.
05How is the PKZM0-6,3 mounted and what ambient range applies?
It snaps onto a 35 mm top-hat rail with 7.5 or 15 mm height. The operating range is -25 to 55 degrees C, or -25 to 40 degrees C inside an enclosure, with IP20 protection and IP00 terminals.