Brand: Eaton
Eaton PKE12/XTU-12 Electronic Motor-Protective Breaker 3-12 A
Description
Eaton PKE12/XTU-12 electronic motor-protective circuit-breaker, 3–12 A
The Eaton PKE12/XTU-12 (catalog number 121733) is a complete electronic motor-protective circuit-breaker: a PKE12 basic device with a standard turn knob and an XTU-12 electronic trip block fitted. It is three-pole, adjustable from 3 to 12 A and rated for 5.5 kW at 380/400 V, 50 Hz. Unlike a purely thermal breaker, the electronic trip block monitors the current in all three phases and offers protection for heavy starting duty, which makes the PKE12/XTU-12 suitable for motors with demanding starts. Seven Star LLC supplies the PKE12/XTU-12 in Oman and the GCC for panel builders and plant maintenance teams.
Reading the PKE12/XTU-12 model code
PKE12 names the basic device, a 45 mm wide breaker body for currents up to 12 A. XTU-12 names the electronic trip block with a 12 A upper limit that is mounted on it, giving the complete device with a 3 to 12 A range. The PKE32 basic device takes trip blocks up to 32 A, and the trip block alone is listed as PKE-XTU-12. Catalog number 121733 is the complete assembly with standard knob; the sibling 158243 carries a lockable AK rotary handle instead.
PKE12/XTU-12 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Eaton PKE12/XTU-12 (catalog number 121733) |
| Series | Eaton Moeller PKE |
| Product category | Motor-protective circuit-breaker, electronic, three-pole |
| Rated operational voltage Ue | 690 V, 50/60 Hz |
| Rated impulse withstand voltage Uimp | 6000 V AC |
| Overvoltage category / pollution degree | III / 3 |
| Actuator | Turn button |
| Functions | Motor protection, overload release, protection for heavy starting duty, phase-failure sensitive |
| Short-circuit release | Basic device fixed at 15.5 × Iu; trip block fixed at 15.5 × Ir, delayed approx. 60 ms (±20 %) |
| Setting range (overload release) | 3 – 12 A |
| Rated operational current Ie / Iu | 12 A / 12 A |
| Rated operational power AC-3e, 230 V / 400 V / 440 V, 50 Hz | 3 kW / 5.5 kW / 5.5 kW |
| Rated operational power AC-3e, 500 V / 690 V, 50 Hz | 5.5 kW / 7.5 kW |
| Heat dissipation, total / per pole | 3.6 W / 1.2 W |
| Resistance per pole | 7.7 mΩ |
| Dimensions (depth x height x width) | 101 x 102.5 x 45 mm |
| Weight | 0.42 kg |
| Mechanical / electrical lifespan | 50,000 operations each (electrical at 400 V, AC-3) |
| Operating frequency | 60 operations per hour |
| Ambient operating temperature | −25 to 55 °C open; −25 to 40 °C enclosed |
| Ambient storage temperature | −40 to 80 °C |
| Temperature compensation | −5 to 40 °C to IEC/EN 60947, operating range −25 to 55 °C |
| Degree of protection | IP20; terminals IP00 |
| Connection | Screw terminals, 1 or 2 × 1–6 mm² with ferrule, AWG 14–10, 10 mm stripping, 1.7 Nm main / 1 Nm control |
| Mounting | 35 mm top-hat rail |
The sheet also lists assigned motor power for North American ratings at 60 Hz: 1 HP at 115/120 V and 1.5 HP at 230/240 V single-phase; 3 HP at 200/208 V and 230/240 V, 7.5 HP at 460/480 V and 10 HP at 575/600 V three-phase.
How the PKE12/XTU-12 differs from a thermal breaker
A thermal-magnetic breaker uses a bimetal strip that heats up with the current, so its response depends on ambient temperature and on how long the strip has had to cool. The PKE12/XTU-12 replaces it with an electronic trip block. Overload and phase-failure protection to IEC/EN 60947-4-1 is built in, and the sheet lists protection for heavy starting duty, with minimum current flow times for trip classes 5, 10, 15 and 20.
The short-circuit release is fixed at 15.5 times the rated current. On a trip block it is delayed by approximately 60 ms with a tolerance of 20 percent. Temperature compensation covers −5 to 40 °C in the IEC range, and the operating range is −25 to 55 °C.
Where the PKE12/XTU-12 fits in a motor starter
The PKE12/XTU-12 is the middle rating of the PKE12 range: its 3 to 12 A window covers motors from about 1.1 kW up to 5.5 kW at 400 V. It is typically mounted ahead of a DILM contactor in a direct-on-line starter. Where a lockable handle is required, the PKE12/AK/XTU-12 should be used, and for smaller motors the PKE12/XTU-4 offers a 1 to 4 A window with finer setting resolution at the bottom of the range. For loads above 12 A the PKE32/XTU-32 continues the series.
Selection checklist for the PKE12/XTU-12
- Verify that the motor nameplate current falls inside 3 to 12 A at the supply voltage and sits comfortably inside the dial.
- Select the trip class that matches the load: lighter classes for pumps and fans, heavier ones for high-inertia loads.
- Check the short-circuit capability of the installation against the breaker data in the manufacturer tables for the voltage in use.
- Note the 60 operations per hour limit of the breaker as a switching device.
- Decide between the standard knob (121733) and the AK lockable handle (158243).
Installation and commissioning of the PKE12/XTU-12
The PKE12/XTU-12 snaps onto a 35 mm top-hat rail. Connect conductors of 1 to 6 mm² with ferrules to the screw terminals at 1.7 Nm, strip length 10 mm, and set the current dial and trip class on the trip block to the motor values. For control circuit terminals the sheet gives 1 Nm. After commissioning, check the motor current under load and confirm that the dial matches the nameplate. During service inspect terminals and operate the knob occasionally.
Typical applications in Oman and the GCC
In Oman and the Gulf the PKE12/XTU-12 serves pumps, blowers, conveyor drives and compressors up to 5.5 kW in water, oil and gas and light industrial plants. Electronic trip blocks are appreciated where panels run warm, because the trip behaviour is less tied to heat build-up in a bimetal element, although the enclosure temperature should still stay within the 40 °C enclosed rating of the breaker. Dust and humidity call for a clean, sealed panel.
Eaton PKE family at a glance
| Model | Setting range | Notes |
|---|---|---|
| PKE12/XTU-1,2 | 0.3 – 1.2 A | Very small motors, 0.25 kW at 400 V |
| PKE12/XTU-4 | 1 – 4 A | Up to 1.5 kW at 400 V |
| PKE12/XTU-12 | 3 – 12 A | Up to 5.5 kW at 400 V |
| PKE12/AK/XTU-12 | 3 – 12 A | AK lockable rotary handle |
| PKE32/XTU-32 | 8 – 32 A | Up to 15 kW at 400 V |
| PKE-XTU-12 | 3 – 12 A | Trip block only, for PKE12 and PKE32 basic devices |
The table lists the PKE models covered on our pages. Basic device, trip block and handle options combine into the complete devices shown; confirm each combination from its own sheet.
Information to send with an RFQ for PKE12/XTU-12
- Exact model PKE12/XTU-12 (catalog number 121733) and the quantity, including spares.
- Motor nameplate current, voltage, power and starting duty.
- Preferred trip class and handle type (standard knob or AK handle).
- Prospective short-circuit current at the panel.
- Delivery location (Muscat, Sohar, Salalah or elsewhere in the GCC) and the date you need the goods.
- Any documents you need with the quotation, such as an installation leaflet or declaration of conformity.
Documents and quotation
The manufacturer specification sheet for PKE12/XTU-12 is attached on this page, so you can check the ratings, dimensions and approvals against your project before you order. Installation leaflets and declarations of conformity can be requested separately.
Seven Star LLC supplies Eaton industrial control products in Oman and the GCC. To request a quotation, send model PKE12/XTU-12, the quantity and your delivery location, and we will confirm availability and lead time for your order.
Datasheets & Documents
- Datasheet Eaton PKE12/XTU-12 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Eaton is a power management company that began in 1911, when Joseph O. Eaton started a truck axle business in New York and moved it to Cleveland, Ohio, in 1914. It grew from vehicle components into electrical equipment, hydraulics and aerospace systems. Since buying Cooper Industries in 2012, Eaton has been incorporated in Ireland with its head office in Dublin, and it is listed on the New York Stock Exchange.
Seven Star LLC lists Eaton NZM molded case circuit breakers, PKZM0 motor-protective circuit breakers and Bussmann series Class J fuses, and supplies them to panel builders and maintenance teams in Oman and the GCC.
Eaton company profile
| Founded | 1911, New York, USA, by Joseph O. Eaton |
|---|---|
| Early move | Cleveland, Ohio, 1914 |
| Headquarters | Dublin, Ireland, since the 2012 Cooper Industries acquisition |
| Listing | New York Stock Exchange (ETN) |
| Brands | Eaton, Moeller, Bussmann, Crouse-Hinds, MTL and MEDC |
| Product families | FAZ and PL miniature circuit breakers, NZM moulded-case breakers, DILM contactors, PowerXL variable frequency drives, 9PX and 93PM UPS, Bussmann fuses, hazardous-area enclosures and signalling |
Milestones
- 1911: Joseph O. Eaton starts an axle business in New York.
- 1914: The business moves to Cleveland.
- 2012: Eaton acquires Cooper Industries and redomiciles in Ireland.
Eaton circuit protection listed here
The NZMN1-A80 is a frame size 1 molded case circuit breaker rated 80 A with a thermomagnetic release for cable and system protection. The PKZM0-1,6 is a motor-protective circuit breaker whose overload release is adjustable from 1 to 1.6 A, used as a manual motor starter. The LPJ-35SP is a Bussmann series Low-Peak Class J time-delay fuse rated 35 A at 600 V AC. Older NZM and PKZ devices carry the Moeller name on the nameplate, and the type designations are the same.
Where Eaton breakers and fuses are used
Motor control centers, feeder panels, machine control cabinets and UL-style fused disconnects.
Eaton products we list
Ordering Eaton parts: what we need
Send the full type and article number, the number of poles, the current rating or setting range, and any accessories such as auxiliary contacts, trip releases or rotary handles.
Facts checked against Eaton's corporate history and investor materials, October 2026.
Browse Eaton products by category: Circuit Breaker.
FAQ
Questions about the Eaton PKE12/XTU-12 Electronic Motor-Protective
Answers from our engineering team on installation, compatibility and integration.
01What current range does the PKE12/XTU-12 cover?
The electronic trip block is adjustable from 3 A to 12 A and the rated operational current is 12 A. At 380/400 V and 50 Hz the rated operational power in AC-3e is 5.5 kW.
02What is the difference between the PKE12/XTU-12 and the PKE12/AK/XTU-12?
Both have a 3 to 12 A electronic trip block. The PKE12/XTU-12 has a standard knob, while the PKE12/AK/XTU-12 has an AK lockable rotary handle and is 120 mm high instead of 102.5 mm.
03Does the PKE12/XTU-12 protect against phase failure?
Yes. The sheet lists phase-failure sensitivity to IEC/EN 60947-4-1 and VDE 0660 part 102, as well as overload release and protection for heavy starting duty.
04How is the short-circuit release of the PKE12/XTU-12 set?
It is fixed at 15.5 times the rated current. The trip block release is delayed by about 60 ms with a tolerance of 20 percent, according to the specification sheet.
05What are the dimensions and weight of the PKE12/XTU-12?
The sheet gives 101 mm depth, 102.5 mm height and 45 mm width, and a weight of 0.42 kg. It mounts on a 35 mm top-hat rail.