Brand: Eaton
Eaton PKZM0-16-PI Push-In Motor-Protective Circuit-Breaker
Description
Eaton PKZM0-16-PI motor-protective circuit-breaker with push-in terminals
The Eaton PKZM0-16-PI (catalog number 199159) is the push-in terminal version of the 16 A PKZM0 motor-protective circuit-breaker. Electrically it matches the screw-terminal PKZM0-16: three poles, an overload release adjustable from 10 to 16 A, and a rated operational power of 7.5 kW at 380/400 V, 50 Hz. What changes is the wiring: the power terminals are push-in spring terminals, so conductors are pushed in without tightening a screw. Seven Star LLC supplies the PKZM0-16-PI in Oman and the GCC for panel builders who want faster, maintenance-free wiring.
Reading the PKZM0-16-PI model code
PKZM0-16 gives the frame and the 16 A upper limit of the dial. The suffix -PI stands for push-in terminals. The device is catalog number 199159. Other connection variants of the same 16 A breaker exist, namely the screw version PKZM0-16, the mixed version PKZM0-16-SPI16 with screw feed side and push-in output side, and a version with built-in auxiliary switch, so the suffix matters when ordering.
PKZM0-16-PI technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Eaton PKZM0-16-PI (catalog number 199159) |
| Series | Eaton Moeller PKZM0 |
| Product category | Motor-protective circuit-breaker, three-pole |
| Rated operational voltage Ue | 690 V, 50/60 Hz |
| Rated impulse withstand voltage Uimp | 6000 V AC |
| Overvoltage category / pollution degree | III / 3 |
| Actuator | Turn button |
| Tripping class | 10 A |
| Short-circuit release | Fixed at 15.5 × Iu (±20 %) |
| Setting range (overload release) | 10 – 16 A |
| Rated uninterrupted current Iu | 16 A |
| Rated operational power AC-3e, 230 V, 50 Hz | 4 kW |
| Rated operational power AC-3e, 380/400 V, 50 Hz | 7.5 kW |
| Rated operational power AC-3e, 440 V and 500 V, 50 Hz | 9 kW |
| Rated operational power AC-3e, 690 V, 50 Hz | 12.5 kW |
| Breaking capacity Icu / Ics at 400 V AC | 50 kA / 38 kA |
| Breaking capacity Icu / Ics at 690 V AC | 3 kA / 2 kA |
| Connection | Push-in terminals |
| Stripping length (main cable) | 12 mm |
| Terminal capacity, flexible with ferrule | 1 or 2 × 1–6 mm² (DIN 46228-1); 1 × 1–6 mm² or 2 × 1–4 mm² (DIN 46228-4) |
| Terminal capacity, solid | 1 or 2 × 1–6 mm² |
| AWG range | 18 – 8 |
| Degree of protection | IP20 |
| Mounting | 35 mm top-hat rail, rail mounting optional |
| Dimensions (depth x height x width) | 75 x 109 x 45 mm |
| Weight | 0.345 kg |
| Mechanical / electrical lifespan | 100,000 operations each |
| Ambient operating temperature | −25 to 55 °C open; −25 to 40 °C enclosed |
| Ambient storage temperature | −40 to 80 °C |
| Maximum altitude | 2000 m |
| Mounting | 35 mm top-hat rail to IEC/EN 60715, 7.5 or 15 mm height |
How push-in connection changes the PKZM0-16-PI
The protective function of the PKZM0-16-PI is the same as that of the screw version: thermal overload release, fixed magnetic short-circuit release at 15.5 times the rated current, trip class 10 A and phase-failure sensitivity to IEC/EN 60947-4-1. The difference lies in the contact system. A push-in terminal clamps a ferruled or solid conductor with a spring as it is inserted, so the clamping force does not depend on how hard a screw was tightened and does not relax through vibration or thermal cycling in the way a loosened screw can.
Releasing a conductor needs only a small screwdriver on the release lever. This makes retrofits and replacements quicker, and it removes the periodic re-tightening that screw terminals call for in panels subject to vibration. The trade-off is that conductors should be fitted with suitable ferrules, and that the stripping length is 12 mm instead of the 10 mm used for the screw version. Dimensions also differ slightly: the PKZM0-16-PI is 75 mm deep and 109 mm high, and weighs 0.345 kg.
Where the PKZM0-16-PI belongs in a starter
The PKZM0-16-PI is used wherever the screw version would be used, as the protective element ahead of a contactor in a direct-on-line or reversing starter, but it pays off most in series production and in sites where panels are rewired often. A feeder in a pump station, a series of identical machine drives or a skid assembled in a workshop all benefit from tool-light connection. Because the breaker is only one of several 16 A versions, check that the panel layout, busbar adapters and contactor combinations were drawn for push-in terminals before changing the connection type.
Related devices are the PKZM0-10 for motors of up to 4 kW at 400 V and the PKZM0-16/NHI11 where a status contact is required. A mixed-terminal alternative, the PKZM0-16-SPI16, keeps screw terminals on the supply side for heavy feeders and push-in on the motor side.
Selection checklist for the PKZM0-16-PI
- Confirm that the motor nameplate current at the operating voltage falls inside 10 to 16 A.
- Decide whether push-in connection suits the maintenance team; ferrules are needed for fine-stranded conductors.
- Check conductor sizes against the capacity: up to 6 mm² flexible with ferrule, AWG 18 to 8.
- Verify that upstream protection suits the breaking capacity: Icu 50 kA and Ics 38 kA at 400 V, 3 kA and 2 kA at 690 V.
- Make sure the contactor and busbar adapter combination is approved for the push-in version.
Installation and maintenance of the PKZM0-16-PI
Snap the PKZM0-16-PI onto a 35 mm rail, strip the conductors to 12 mm and push them into the terminal until they seat. Set the dial to the nameplate current of the motor and check by pulling lightly on each conductor. To release a conductor, press the spring lever with a small screwdriver. In service, inspect for heat marks and confirm the dial setting at routine checks; re-tightening is not needed, which saves time during shutdowns in plants with many starters.
Typical applications in Oman and the GCC
In Oman and the wider GCC the PKZM0-16-PI suits packaged equipment built for export, process skids, cooling-water pump sets and HVAC plant, where many identical motor feeders are installed and later serviced under time pressure. Vibration near compressors and large pumps is a typical reason to prefer spring-type connection. As always with enclosed panels in hot climates, check the 40 °C enclosed rating against the real panel temperature.
Eaton PKZM0 family at a glance
| Model | Setting range | Distinguishing feature |
|---|---|---|
| PKZM0-10 | 6.3 – 10 A | 4 kW at 380/400 V, screw terminals |
| PKZM0-16 | 10 – 16 A | 7.5 kW at 380/400 V, screw terminals |
| PKZM0-16-PI | 10 – 16 A | Push-in terminals top and bottom |
| PKZM0-16-SPI16 | 10 – 16 A | Screw terminals on feed side, push-in on output side |
| PKZM0-16/NHI11 | 10 – 16 A | Built-in auxiliary switch, 1 N/O + 1 N/C |
Information to send with an RFQ for PKZM0-16-PI
- Exact model PKZM0-16-PI (catalog number 199159) and the quantity, including spares.
- Motor nameplate current, voltage and power.
- Conductor type and size, and whether ferrules are used.
- Contactor type that will be combined with the breaker.
- Delivery location (Muscat, Sohar, Salalah or elsewhere in the GCC) and the date you need the goods.
- Any documents you need with the quotation, such as an installation leaflet or declaration of conformity.
Documents and quotation
The manufacturer specification sheet for PKZM0-16-PI is attached on this page, so you can check the ratings, dimensions and approvals against your project before you order. Installation leaflets and declarations of conformity can be requested separately.
Seven Star LLC supplies Eaton industrial control products in Oman and the GCC. To request a quotation, send model PKZM0-16-PI, the quantity and your delivery location, and we will confirm availability and lead time for your order.
Other Models in the Eaton Pkzm0 Range
Seven Star LLC supplies models from the Eaton Pkzm0 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Eaton PKZM0-6,3 Motor-Protective Circuit-Breaker 4-6.3 A | Circuit Breakers | View details |
| Eaton PKZM0-10 Motor-Protective Circuit-Breaker 6.3-10 A | Circuit Breakers | View details |
| Eaton PKZM0-16 Motor-Protective Circuit-Breaker 10-16 A | Circuit Breakers | View details |
| Eaton PKZM0-16-PI Push-In Motor-Protective Circuit-Breaker | Circuit Breakers | You are viewing this model |
Datasheets & Documents
- Datasheet Eaton PKZM0-16-PI Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Eaton is a power management company that began in 1911, when Joseph O. Eaton started a truck axle business in New York and moved it to Cleveland, Ohio, in 1914. It grew from vehicle components into electrical equipment, hydraulics and aerospace systems. Since buying Cooper Industries in 2012, Eaton has been incorporated in Ireland with its head office in Dublin, and it is listed on the New York Stock Exchange.
Seven Star LLC lists Eaton NZM molded case circuit breakers, PKZM0 motor-protective circuit breakers and Bussmann series Class J fuses, and supplies them to panel builders and maintenance teams in Oman and the GCC.
Eaton company profile
| Founded | 1911, New York, USA, by Joseph O. Eaton |
|---|---|
| Early move | Cleveland, Ohio, 1914 |
| Headquarters | Dublin, Ireland, since the 2012 Cooper Industries acquisition |
| Listing | New York Stock Exchange (ETN) |
| Brands | Eaton, Moeller, Bussmann, Crouse-Hinds, MTL and MEDC |
| Product families | FAZ and PL miniature circuit breakers, NZM moulded-case breakers, DILM contactors, PowerXL variable frequency drives, 9PX and 93PM UPS, Bussmann fuses, hazardous-area enclosures and signalling |
Milestones
- 1911: Joseph O. Eaton starts an axle business in New York.
- 1914: The business moves to Cleveland.
- 2012: Eaton acquires Cooper Industries and redomiciles in Ireland.
Eaton circuit protection listed here
The NZMN1-A80 is a frame size 1 molded case circuit breaker rated 80 A with a thermomagnetic release for cable and system protection. The PKZM0-1,6 is a motor-protective circuit breaker whose overload release is adjustable from 1 to 1.6 A, used as a manual motor starter. The LPJ-35SP is a Bussmann series Low-Peak Class J time-delay fuse rated 35 A at 600 V AC. Older NZM and PKZ devices carry the Moeller name on the nameplate, and the type designations are the same.
Where Eaton breakers and fuses are used
Motor control centers, feeder panels, machine control cabinets and UL-style fused disconnects.
Eaton products we list
Ordering Eaton parts: what we need
Send the full type and article number, the number of poles, the current rating or setting range, and any accessories such as auxiliary contacts, trip releases or rotary handles.
Facts checked against Eaton's corporate history and investor materials, October 2026.
Browse Eaton products by category: Circuit Breaker.
FAQ
Questions about the Eaton PKZM0-16-PI Push-In Motor-Protective
Answers from our engineering team on installation, compatibility and integration.
01What makes the PKZM0-16-PI different from the PKZM0-16?
The protective data is the same, but the PKZM0-16-PI has push-in terminals instead of screw terminals. It uses a 12 mm stripping length, is 109 mm high and 0.345 kg in weight, according to the specification sheet.
02What setting range does the PKZM0-16-PI have?
The overload release covers 10 to 16 A, with a rated uninterrupted current of 16 A. At 380/400 V and 50 Hz the rated operational power in AC-3e is 7.5 kW.
03What conductors can be used in the PKZM0-16-PI?
Flexible conductors with ferrule of 1 to 6 square millimetres, single or double, plus solid conductors of 1 to 6 square millimetres. The sheet lists AWG 18 to 8 and a stripping length of 12 mm.
04What is the breaking capacity of the PKZM0-16-PI?
The sheet gives Icu of 50 kA and Ics of 38 kA at 400 V AC, and 3 kA and 2 kA at 690 V AC, the same ratings as the screw-terminal PKZM0-16.
05Is the PKZM0-16-PI phase-failure sensitive?
Yes, phase-failure sensitivity to IEC/EN 60947-4-1 and VDE 0660 part 102 is listed. The breaker has thermal and magnetic releases and trip class 10 A for normal starting.