Brand: Eaton
Eaton PKZM0-16/NHI11 Motor-Protective Breaker with Aux Contact
Description
Eaton PKZM0-16/NHI11 motor-protective circuit-breaker with auxiliary switch
The Eaton PKZM0-16/NHI11 (catalog number 039423) is a 16 A PKZM0 motor-protective circuit-breaker supplied with an auxiliary switch already fitted. The switch provides one normally open and one normally closed contact, so the breaker can report its state to a PLC, an indicator lamp or an interlock circuit without any additional part to order. Protective data is the same as for the PKZM0-16: setting range 10 to 16 A and 7.5 kW at 380/400 V, 50 Hz. Seven Star LLC supplies the PKZM0-16/NHI11 in Oman and the GCC for control panel builders and maintenance teams.
What the PKZM0-16/NHI11 suffix means
PKZM0-16 is the frame and the 16 A dial limit. The suffix /NHI11 denotes the fitted auxiliary switch with one N/O and one N/C contact. The sheet lists the device as a three-pole breaker with one normally open and one normally closed auxiliary contact. Because the module is fitted, the device is 54 mm wide instead of 45 mm and weighs 0.329 kg.
PKZM0-16/NHI11 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Eaton PKZM0-16/NHI11 (catalog number 039423) |
| Series | Eaton Moeller PKZM0 |
| Product category | Motor-protective circuit-breaker, three-pole |
| Rated operational voltage Ue | 690 V, 50/60 Hz |
| Rated impulse withstand voltage Uimp | 6000 V AC |
| Overvoltage category / pollution degree | III / 3 |
| Actuator | Turn button |
| Tripping class | 10 A |
| Short-circuit release | Fixed at 15.5 × Iu (±20 %) |
| Setting range (overload release) | 10 – 16 A |
| Rated uninterrupted current Iu | 16 A |
| Rated operational power AC-3e, 230 V, 50 Hz | 4 kW |
| Rated operational power AC-3e, 380/400 V, 50 Hz | 7.5 kW |
| Rated operational power AC-3e, 440 V and 500 V, 50 Hz | 9 kW |
| Rated operational power AC-3e, 690 V, 50 Hz | 12.5 kW |
| Breaking capacity Icu / Ics at 400 V AC | 50 kA / 38 kA |
| Breaking capacity Icu / Ics at 690 V AC | 3 kA / 2 kA |
| Auxiliary contacts | 1 N/O + 1 N/C (fitted) |
| Fitted with | Auxiliary switch |
| Tightening torque, control circuit terminals | 1 Nm |
| Tightening torque, main terminals | 1.7 Nm |
| Connection | Screw terminals |
| Degree of protection | IP20; terminals IP00 |
| Dimensions (depth x height x width) | 76 x 93 x 54 mm |
| Weight | 0.329 kg |
| Mechanical / electrical lifespan | 100,000 operations each |
| Ambient operating temperature | −25 to 55 °C open; −25 to 40 °C enclosed |
| Ambient storage temperature | −40 to 80 °C |
| Maximum altitude | 2000 m |
| Mounting | 35 mm top-hat rail to IEC/EN 60715, 7.5 or 15 mm height |
How the auxiliary switch on the PKZM0-16/NHI11 is used
The auxiliary contacts follow the position of the breaker. They are typically wired to a PLC input to signal that the motor feeder is switched on, to a lamp showing the state locally, or to a contactor coil circuit as an interlock so that the contactor cannot energise when the breaker is open. The protective side of the device is unchanged: thermal overload release, fixed magnetic short-circuit release at 15.5 times the rated current and trip class 10 A, with phase-failure sensitivity to IEC/EN 60947-4-1.
Control wiring on the auxiliary switch uses its own screw terminals, which are tightened to a lower torque of 1 Nm than the 1.7 Nm used for the main terminals. Keep control and power conductors separated in the panel in the usual way, and check the contact ratings in the instruction leaflet before connecting loads directly.
Where the PKZM0-16/NHI11 fits
Because the auxiliary switch is already fitted, this version saves an assembly step and a separate catalog line when many feeders need a status signal, for example in pump stations monitored by a SCADA system or in motor control centres where a tripped breaker must raise an alarm. It also avoids the risk of a loosely fitted add-on module in vibrating machinery.
If the status signal is not needed, the PKZM0-16 is the simpler and narrower choice at 45 mm. For lower currents the PKZM0-10 covers 6.3 to 10 A. Note that a single auxiliary switch follows the breaker position; whether a trip can be distinguished from a manual off depends on the contact module, so confirm in the leaflet if this distinction is required for alarming.
Selection checklist for the PKZM0-16/NHI11
- Confirm the motor nameplate current falls between 10 and 16 A at the operating voltage.
- Check that one N/O and one N/C auxiliary contact is enough for the control scheme.
- Allow for the 54 mm width when planning the rail layout.
- Compare short-circuit level with Icu 50 kA and Ics 38 kA at 400 V, 3 kA and 2 kA at 690 V.
- Confirm how the alarm logic will treat trip and manual switch-off.
Installation and maintenance of the PKZM0-16/NHI11
Mount the device on a 35 mm rail with space for 54 mm width. Wire the main conductors to the screw terminals at 1.7 Nm and the auxiliary circuit at 1 Nm. Set the dial to the motor nameplate current. During commissioning, operate the breaker and verify with a meter or PLC diagnostic that the N/O and N/C contacts change state as expected. At maintenance intervals, check terminal tightness on both power and auxiliary terminals.
Typical applications in Oman and the GCC
In Oman and the GCC, breakers with a built-in status contact are common in remotely monitored pump stations, desalination auxiliaries, utility buildings and oil and gas package units, where an operator needs to know from the control room that a motor feeder has been switched off or has tripped. The hot climate means the enclosed temperature rating of 40 °C should be checked, especially as the auxiliary module adds a little to the device size and heat in the enclosure.
Eaton PKZM0 family at a glance
| Model | Setting range | Distinguishing feature |
|---|---|---|
| PKZM0-10 | 6.3 – 10 A | 4 kW at 380/400 V, screw terminals |
| PKZM0-16 | 10 – 16 A | 7.5 kW at 380/400 V, screw terminals |
| PKZM0-16-PI | 10 – 16 A | Push-in terminals top and bottom |
| PKZM0-16-SPI16 | 10 – 16 A | Screw terminals on feed side, push-in on output side |
| PKZM0-16/NHI11 | 10 – 16 A | Built-in auxiliary switch, 1 N/O + 1 N/C |
Information to send with an RFQ for PKZM0-16/NHI11
- Exact model PKZM0-16/NHI11 (catalog number 039423) and the quantity, including spares.
- Motor nameplate data and desired current setting.
- Control voltage and the PLC or relay input the contacts will drive.
- Quantity of identical feeders, if this is for a series build.
- Delivery location (Muscat, Sohar, Salalah or elsewhere in the GCC) and the date you need the goods.
- Any documents you need with the quotation, such as an installation leaflet or declaration of conformity.
Documents and quotation
The manufacturer specification sheet for PKZM0-16/NHI11 is attached on this page, so you can check the ratings, dimensions and approvals against your project before you order. Installation leaflets and declarations of conformity can be requested separately.
Seven Star LLC supplies Eaton industrial control products in Oman and the GCC. To request a quotation, send model PKZM0-16/NHI11, the quantity and your delivery location, and we will confirm availability and lead time for your order.
Other Models in the Eaton Pkzm0 Range
Seven Star LLC supplies models from the Eaton Pkzm0 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Eaton PKZM0-6,3 Motor-Protective Circuit-Breaker 4-6.3 A | Circuit Breakers | View details |
| Eaton PKZM0-10 Motor-Protective Circuit-Breaker 6.3-10 A | Circuit Breakers | View details |
| Eaton PKZM0-16 Motor-Protective Circuit-Breaker 10-16 A | Circuit Breakers | View details |
| Eaton PKZM0-16-PI Push-In Motor-Protective Circuit-Breaker | Circuit Breakers | View details |
| Eaton PKZM0-16-SPI16 Motor-Protective Circuit-Breaker | Circuit Breakers | View details |
| Eaton PKZM0-16/NHI11 Motor-Protective Breaker with Aux Contact | Circuit Breakers | You are viewing this model |
Datasheets & Documents
- Datasheet Eaton PKZM0-16/NHI11 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Eaton is a power management company that began in 1911, when Joseph O. Eaton started a truck axle business in New York and moved it to Cleveland, Ohio, in 1914. It grew from vehicle components into electrical equipment, hydraulics and aerospace systems. Since buying Cooper Industries in 2012, Eaton has been incorporated in Ireland with its head office in Dublin, and it is listed on the New York Stock Exchange.
Seven Star LLC lists Eaton NZM molded case circuit breakers, PKZM0 motor-protective circuit breakers and Bussmann series Class J fuses, and supplies them to panel builders and maintenance teams in Oman and the GCC.
Eaton company profile
| Founded | 1911, New York, USA, by Joseph O. Eaton |
|---|---|
| Early move | Cleveland, Ohio, 1914 |
| Headquarters | Dublin, Ireland, since the 2012 Cooper Industries acquisition |
| Listing | New York Stock Exchange (ETN) |
| Brands | Eaton, Moeller, Bussmann, Crouse-Hinds, MTL and MEDC |
| Product families | FAZ and PL miniature circuit breakers, NZM moulded-case breakers, DILM contactors, PowerXL variable frequency drives, 9PX and 93PM UPS, Bussmann fuses, hazardous-area enclosures and signalling |
Milestones
- 1911: Joseph O. Eaton starts an axle business in New York.
- 1914: The business moves to Cleveland.
- 2012: Eaton acquires Cooper Industries and redomiciles in Ireland.
Eaton circuit protection listed here
The NZMN1-A80 is a frame size 1 molded case circuit breaker rated 80 A with a thermomagnetic release for cable and system protection. The PKZM0-1,6 is a motor-protective circuit breaker whose overload release is adjustable from 1 to 1.6 A, used as a manual motor starter. The LPJ-35SP is a Bussmann series Low-Peak Class J time-delay fuse rated 35 A at 600 V AC. Older NZM and PKZ devices carry the Moeller name on the nameplate, and the type designations are the same.
Where Eaton breakers and fuses are used
Motor control centers, feeder panels, machine control cabinets and UL-style fused disconnects.
Eaton products we list
Ordering Eaton parts: what we need
Send the full type and article number, the number of poles, the current rating or setting range, and any accessories such as auxiliary contacts, trip releases or rotary handles.
Facts checked against Eaton's corporate history and investor materials, October 2026.
Browse Eaton products by category: Circuit Breaker.
FAQ
Questions about the Eaton PKZM0-16/NHI11 Motor-Protective Breaker with
Answers from our engineering team on installation, compatibility and integration.
01What auxiliary contacts does the PKZM0-16/NHI11 include?
One normally open and one normally closed contact, built into the device as an auxiliary switch. The sheet lists a fitted auxiliary switch and the 3p+1N/O+1N/C configuration.
02How wide is the PKZM0-16/NHI11?
The device is 54 mm wide, 76 mm deep and 93 mm high according to the sheet, and weighs 0.329 kg. The extra width compared with the 45 mm PKZM0-16 comes from the auxiliary module.
03What is the current range of the PKZM0-16/NHI11?
The overload release is set between 10 and 16 A with a rated uninterrupted current of 16 A. At 380/400 V and 50 Hz the rated operational power in AC-3e is 7.5 kW.
04What torque applies to the terminals of the PKZM0-16/NHI11?
The sheet gives 1.7 Nm for the screw terminals of the main cable and 1 Nm for the control circuit cables of the auxiliary switch.
05Does the PKZM0-16/NHI11 have the same breaking capacity as the PKZM0-16?
The sheet lists Icu of 50 kA and Ics of 38 kA at 400 V AC and 3 kA and 2 kA at 690 V AC, matching the PKZM0-16 values. Check the sheet for other voltages.


















Reviews