Eaton PKE12/XTU-1,2 electronic motor-protective circuit-breaker, 0.3–1.2 A

The Eaton PKE12/XTU-1,2 (catalog number 121731) is the lowest-current complete device in the PKE12 electronic motor-protective circuit-breaker range. A PKE12 basic device with standard knob carries an XTU-1,2 trip block, giving three poles, a setting range of 0.3 to 1.2 A and a rated operational power of 0.25 kW at 380/400 V, 50 Hz. It is designed for very small motors and for fractional-kilowatt loads where an ordinary motor breaker would have its smallest setting far above the actual current. Seven Star LLC supplies the PKE12/XTU-1,2 in Oman and the GCC for OEMs and panel builders.

Decoding PKE12/XTU-1,2

The code mixes two parts. PKE12 is the basic device frame, 45 mm wide. XTU-1,2 is the electronic trip block, with the decimal comma indicating a 1.2 A upper limit; its lower limit is 0.3 A. When the sheet is read in the UK or US style the same device may appear as 1.2 A. Catalog number 121731 is the complete assembly. The neighbouring devices are the PKE12/XTU-4 for 1 to 4 A and the PKE12/XTU-12 for 3 to 12 A, and they differ from this one only in the trip block range.

PKE12/XTU-1,2 technical specifications

Parameter Specification
Manufacturer / part number Eaton PKE12/XTU-1,2 (catalog number 121731)
Series Eaton Moeller PKE
Product category Motor-protective circuit-breaker, electronic, three-pole
Rated operational voltage Ue 690 V, 50/60 Hz
Rated impulse withstand voltage Uimp 6000 V AC
Overvoltage category / pollution degree III / 3
Actuator Turn button
Functions Motor protection, overload release, protection for heavy starting duty, phase-failure sensitive
Short-circuit release Basic device fixed at 15.5 × Iu; trip block fixed at 15.5 × Ir, delayed approx. 60 ms (±20 %)
Setting range (overload release) 0.3 – 1.2 A
Rated operational current Ie / Iu 1.2 A / 1.2 A
Rated operational power AC-3e, 230 V / 400 V / 440 V, 50 Hz 0.12 kW / 0.25 kW / 0.37 kW
Rated operational power AC-3e, 500 V / 690 V, 50 Hz 0.37 kW / 0.75 kW
Heat dissipation, total / per pole 0.3 W / 0.1 W
Resistance per pole 121 mΩ
Dimensions (depth x height x width) 101 x 102.5 x 45 mm
Weight 0.42 kg
Mechanical / electrical lifespan 50,000 operations each (electrical at 400 V, AC-3)
Operating frequency 60 operations per hour
Ambient operating temperature −25 to 55 °C open; −25 to 40 °C enclosed
Ambient storage temperature −40 to 80 °C
Temperature compensation −5 to 40 °C to IEC/EN 60947, operating range −25 to 55 °C
Degree of protection IP20; terminals IP00
Connection Screw terminals, 1 or 2 × 1–6 mm² with ferrule, AWG 14–10, 10 mm stripping, 1.7 Nm main / 1 Nm control
Mounting 35 mm top-hat rail

The sheet also lists assigned motor power for North American ratings at 60 Hz: 1 HP at 115/120 V and 1.5 HP at 230/240 V single-phase; 3 HP at 200/208 V and 230/240 V, 0.5 HP at 460/480 V and 0.5 HP at 575/600 V three-phase.

Protecting very small motors with the PKE12/XTU-1,2

Fractional-kilowatt motors draw a few hundred milliamps at 400 V. A 0.18 kW motor takes under half an ampere, and a 0.37 kW motor just under one ampere. A thermal breaker with a 1 A minimum setting cannot protect them properly, because the dial would sit at or below the bottom of its range. The PKE12/XTU-1,2 solves this with a 0.3 to 1.2 A window, which allows the setting to follow the nameplate current closely.

The electronic trip block monitors the three phase currents. Overload and phase-failure protection are provided to IEC/EN 60947-4-1, with the sheet listing minimum current flow times for trip classes 5, 10, 15 and 20. The short-circuit release is fixed at 15.5 times the rated current and delayed by about 60 ms on the trip block, tolerance 20 percent. The high resistance per pole, 121 milliohm, and the heat dissipation of only 0.3 W reflect the small current.

Typical uses of the PKE12/XTU-1,2

The device is intended for small fans, pumps with fractional motors, valve and damper actuators, small gearmotors and laboratory or instrument equipment. In a motor starter it is combined with a small contactor. Because its ratings are low, the breaking capacity and switching limits should be checked in the manufacturer tables for the system voltage; it is not meant for motors above 1.2 A, for which the PKE12/XTU-4 or PKE12/XTU-12 are the right choices.

Selection checklist for the PKE12/XTU-1,2

  • Check that the motor nameplate current at the supply voltage lies between 0.3 and 1.2 A.
  • Choose the trip class for the starting duty.
  • Remember that rated power is 0.25 kW at 400 V and only 0.12 kW at 230 V.
  • Confirm short-circuit level at the installation point against the manufacturer data.
  • Check that the next higher device is not needed to leave headroom for future motor replacements.

Installation and service of the PKE12/XTU-1,2

Fix the PKE12/XTU-1,2 on a 35 mm rail. Use ferrules on fine conductors, strip 10 mm and tighten the main terminals to 1.7 Nm. Set the dial to the nameplate current and select the trip class. Because current is small, take care to measure the motor current under load to confirm that the setting is sensible; clamp meters can be inaccurate at very low current, so use a meter with a suitable range. Terminals should be checked at each service.

Typical applications in Oman and the GCC

Gulf installations contain many small motors in ventilation, instrumentation cabinets, dosing skids and building services. For these loads the PKE12/XTU-1,2 offers accurate protection in a 45 mm device that fits the same rail layouts as the larger PKE frames, which keeps panel design uniform. As elsewhere, hot rooms require checking the 40 °C enclosed rating.

Eaton PKE family at a glance

Model Setting range Notes
PKE12/XTU-1,2 0.3 – 1.2 A Very small motors, 0.25 kW at 400 V
PKE12/XTU-4 1 – 4 A Up to 1.5 kW at 400 V
PKE12/XTU-12 3 – 12 A Up to 5.5 kW at 400 V
PKE12/AK/XTU-12 3 – 12 A AK lockable rotary handle
PKE32/XTU-32 8 – 32 A Up to 15 kW at 400 V
PKE-XTU-12 3 – 12 A Trip block only, for PKE12 and PKE32 basic devices

The table lists the PKE models covered on our pages. Basic device, trip block and handle options combine into the complete devices shown; confirm each combination from its own sheet.

Information to send with an RFQ for PKE12/XTU-1,2

  • Exact model PKE12/XTU-1,2 (catalog number 121731) and the quantity, including spares.
  • Motor nameplate current and voltage.
  • Number of feeders and trip class needed.
  • Panel layout constraints such as available rail width.
  • Delivery location (Muscat, Sohar, Salalah or elsewhere in the GCC) and the date you need the goods.
  • Any documents you need with the quotation, such as an installation leaflet or declaration of conformity.

Documents and quotation

The manufacturer specification sheet for PKE12/XTU-1,2 is attached on this page, so you can check the ratings, dimensions and approvals against your project before you order. Installation leaflets and declarations of conformity can be requested separately.

Seven Star LLC supplies Eaton industrial control products in Oman and the GCC. To request a quotation, send model PKE12/XTU-1,2, the quantity and your delivery location, and we will confirm availability and lead time for your order.

Other Models in the Eaton Pke Range

Seven Star LLC supplies models from the Eaton Pke range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Eaton PKE12/XTU-12 Electronic Motor-Protective Breaker 3-12 ACircuit BreakersView details
Eaton PKE12/XTU-4 Electronic Motor-Protective Breaker 1-4 ACircuit BreakersView details
Eaton PKE12/XTU-1,2 Motor-Protective Breaker 0.3-1.2 ACircuit BreakersYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Eaton PKE12/XTU-1,2 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Eaton is a power management company that began in 1911, when Joseph O. Eaton started a truck axle business in New York and moved it to Cleveland, Ohio, in 1914. It grew from vehicle components into electrical equipment, hydraulics and aerospace systems. Since buying Cooper Industries in 2012, Eaton has been incorporated in Ireland with its head office in Dublin, and it is listed on the New York Stock Exchange.

Seven Star LLC lists Eaton NZM molded case circuit breakers, PKZM0 motor-protective circuit breakers and Bussmann series Class J fuses, and supplies them to panel builders and maintenance teams in Oman and the GCC.

Eaton company profile

Founded 1911, New York, USA, by Joseph O. Eaton
Early move Cleveland, Ohio, 1914
Headquarters Dublin, Ireland, since the 2012 Cooper Industries acquisition
Listing New York Stock Exchange (ETN)
Brands Eaton, Moeller, Bussmann, Crouse-Hinds, MTL and MEDC
Product families FAZ and PL miniature circuit breakers, NZM moulded-case breakers, DILM contactors, PowerXL variable frequency drives, 9PX and 93PM UPS, Bussmann fuses, hazardous-area enclosures and signalling

Milestones

  • 1911: Joseph O. Eaton starts an axle business in New York.
  • 1914: The business moves to Cleveland.
  • 2012: Eaton acquires Cooper Industries and redomiciles in Ireland.

Eaton circuit protection listed here

The NZMN1-A80 is a frame size 1 molded case circuit breaker rated 80 A with a thermomagnetic release for cable and system protection. The PKZM0-1,6 is a motor-protective circuit breaker whose overload release is adjustable from 1 to 1.6 A, used as a manual motor starter. The LPJ-35SP is a Bussmann series Low-Peak Class J time-delay fuse rated 35 A at 600 V AC. Older NZM and PKZ devices carry the Moeller name on the nameplate, and the type designations are the same.

Where Eaton breakers and fuses are used

Motor control centers, feeder panels, machine control cabinets and UL-style fused disconnects.

Eaton products we list

Family Examples
Circuit Breakers LPJ-35SP Class J Time-Delay Fuse, NZMN1-A80 Molded Case Circuit Breaker, NZMN2-A250 Molded Case Circuit Breaker, NZMN3-AE400 Molded Case Circuit Breaker, PKZM0-1
AC Drives DA1-342D2FB-A20C AC Drive, PowerXL DG1-34140FN-C21C Variable Freque…

Ordering Eaton parts: what we need

Send the full type and article number, the number of poles, the current rating or setting range, and any accessories such as auxiliary contacts, trip releases or rotary handles.

Facts checked against Eaton's corporate history and investor materials, October 2026.

FAQ

Questions about the Eaton PKE12/XTU-1,2 Motor-Protective Breaker

Answers from our engineering team on installation, compatibility and integration.

01What is the setting range of the PKE12/XTU-1,2?
The electronic trip block is adjustable from 0.3 A to 1.2 A and the rated operational current is 1.2 A, which suits fractional-kilowatt motors.
02What motor power can the PKE12/XTU-1,2 protect?
In AC-3e the rated operational power is 0.12 kW at 230 V, 0.25 kW at 380/400 V, 0.37 kW at 440 V and 500 V and 0.75 kW at 690 V.
03Why does the PKE12/XTU-1,2 show a comma in its name?
The comma is a decimal comma used in the European model code. XTU-1,2 means a trip block with an upper setting of 1.2 A, not a pair of values.
04What is the heat dissipation of the PKE12/XTU-1,2?
The sheet gives 0.3 W for the complete device at rated current and 0.1 W per pole, with a resistance of 121 milliohm per pole.
05How is the short-circuit release of the PKE12/XTU-1,2 set?
It is fixed at 15.5 times the rated current. The trip block release is delayed by approximately 60 ms with a tolerance of 20 percent.