- Automation & ControlView all 2,483 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- CCTV & Security
- Encoders
- Motor Soft Starters
- Safety Switches & Guard Locking
- HMI Displays
- Pneumatic Cylinders
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Eaton
Eaton PKE32/XTU-32 Electronic Motor-Protective Breaker 8-32 A
Description
Eaton PKE32/XTU-32 electronic motor-protective circuit-breaker, 8–32 A
The Eaton PKE32/XTU-32 (catalog number 121734) is the highest-current complete device of the PKE electronic motor-protective circuit-breaker range. A PKE32 basic device with standard knob carries an XTU-32 electronic trip block, giving three poles, a setting range of 8 to 32 A and a rated operational power of 15 kW at 380/400 V, 50 Hz. It covers motors that are too large for the PKE12 frame, such as 7.5 to 15 kW pumps, compressors and fans, while keeping the compact 45 mm width. Seven Star LLC supplies the PKE32/XTU-32 in Oman and the GCC for contractors, OEMs and maintenance teams.
Reading the PKE32/XTU-32 code
PKE32 names the larger basic device frame, rated for up to 32 A, and XTU-32 the electronic trip block with a 32 A upper limit; the setting range of the complete device is 8 to 32 A according to the sheet title. Catalog number 121734 identifies this assembly with standard knob. The PKE12 devices, such as the PKE12/XTU-12, use the smaller frame, and the trip block alone is sold separately.
PKE32/XTU-32 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Eaton PKE32/XTU-32 (catalog number 121734) |
| Series | Eaton Moeller PKE |
| Product category | Motor-protective circuit-breaker, electronic, three-pole |
| Rated operational voltage Ue | 690 V, 50/60 Hz |
| Rated impulse withstand voltage Uimp | 6000 V AC |
| Overvoltage category / pollution degree | III / 3 |
| Actuator | Turn button |
| Functions | Motor protection, overload release, protection for heavy starting duty, phase-failure sensitive |
| Short-circuit release | Basic device fixed at 15.5 × Iu; trip block fixed at 15.5 × Ir, delayed approx. 60 ms (±20 %) |
| Setting range (overload release) | 8 – 32 A |
| Rated operational current Ie / Iu | 32 A / 32 A |
| Rated operational power AC-3e, 230 V / 400 V / 440 V, 50 Hz | 7.5 kW / 15 kW / 15 kW |
| Rated operational power AC-3e, 500 V / 690 V, 50 Hz | 18.5 kW / 30 kW |
| Heat dissipation, total / per pole | 11.4 W / 3.8 W |
| Resistance per pole | 2.5 mΩ |
| Dimensions (depth x height x width) | 101 x 102.5 x 45 mm |
| Weight | 0.436 kg |
| Mechanical / electrical lifespan | 50,000 operations each (electrical at 400 V, AC-3) |
| Operating frequency | 60 operations per hour |
| Ambient operating temperature | −25 to 55 °C open; −25 to 40 °C enclosed |
| Ambient storage temperature | −40 to 80 °C |
| Temperature compensation | −5 to 40 °C to IEC/EN 60947, operating range −25 to 55 °C |
| Degree of protection | IP20; terminals IP00 |
| Connection | Screw terminals, 1 or 2 × 1–6 mm² with ferrule, AWG 14–10, 10 mm stripping, 1.7 Nm main / 1 Nm control |
| Mounting | 35 mm top-hat rail |
The sheet also lists assigned motor power for North American ratings at 60 Hz: 1.5 HP at 115/120 V and 3 HP at 230/240 V single-phase; 5 HP at 200/208 V, 7.5 HP at 230/240 V, 15 HP at 460/480 V and 20 HP at 575/600 V three-phase.
What the PKE32/XTU-32 adds over the PKE12 devices
The PKE32/XTU-32 keeps the electronic protection concept of the PKE family but raises the current to 32 A. Overload and phase-failure protection to IEC/EN 60947-4-1 and VDE 0660 part 102 are provided, with protection for heavy starting duty and minimum current flow times listed for classes 5, 10, 15 and 20. Switching capacity is 32 A in AC-3 up to 690 V and 32 A general use under UL/CSA.
The rated power figures are 7.5 kW at 230 V, 15 kW at 380/400 V and 440 V, 18.5 kW at 500 V and 30 kW at 690 V. At full current the three poles dissipate 11.4 W, about three times the PKE12/XTU-12, which matters for panel cooling when several are mounted side by side. The low resistance of 2.5 milliohm per pole reflects the heavier current path.
Where the PKE32/XTU-32 fits in a motor feeder
With a 32 A upper limit the device is used on feeders for motors of roughly 5.5 to 15 kW at 400 V, ahead of a DILM contactor of matching size. Typical examples are cooling-water pumps, compressors, large fans and conveyor drives. For smaller motors the PKE12 devices give a more accurate setting window, and the PKE12/XTU-12 should be used up to 5.5 kW. The sheet lists the lower end of the setting range as 8 A, so motors below that value should be assigned to a smaller device.
Selection checklist for the PKE32/XTU-32
- Confirm that the motor nameplate current falls inside 8 to 32 A at the supply voltage.
- Select the trip class for the starting duty, especially for large-inertia fans and pumps.
- Allow for 11.4 W of heat per breaker at full current when sizing panel cooling.
- Check short-circuit level against the manufacturer tables.
- Verify that the contactor chosen matches the 32 A rating of the breaker.
Installation and commissioning of the PKE32/XTU-32
Mount the PKE32/XTU-32 on a 35 mm rail with enough space for heat to leave the enclosure. Terminals take conductors of 1 to 6 mm² with ferrules, so check that this cross-section is adequate for the motor current and cable length. Tighten main terminals to 1.7 Nm, set the dial and trip class, and verify the motor current at full load. Because heat output is higher than on the smaller PKE devices, inspect terminals for discolouration at each service.
Typical applications in Oman and the GCC
The PKE32/XTU-32 is used on larger auxiliary motors in desalination, water treatment, oil and gas utilities and industrial HVAC, where 7.5 to 15 kW drives are common. High ambient temperatures and the heat dissipated by the breaker itself make panel ventilation and the 40 °C enclosed rating important design checks.
Eaton PKE family at a glance
| Model | Setting range | Notes |
|---|---|---|
| PKE12/XTU-1,2 | 0.3 – 1.2 A | Very small motors, 0.25 kW at 400 V |
| PKE12/XTU-4 | 1 – 4 A | Up to 1.5 kW at 400 V |
| PKE12/XTU-12 | 3 – 12 A | Up to 5.5 kW at 400 V |
| PKE12/AK/XTU-12 | 3 – 12 A | AK lockable rotary handle |
| PKE32/XTU-32 | 8 – 32 A | Up to 15 kW at 400 V |
| PKE-XTU-12 | 3 – 12 A | Trip block only, for PKE12 and PKE32 basic devices |
The table lists the PKE models covered on our pages. Basic device, trip block and handle options combine into the complete devices shown; confirm each combination from its own sheet.
Information to send with an RFQ for PKE32/XTU-32
- Exact model PKE32/XTU-32 (catalog number 121734) and the quantity, including spares.
- Motor nameplate current, voltage, power and starting duty.
- Trip class needed and contactor type to be combined.
- Panel cooling arrangement and ambient temperature.
- Delivery location (Muscat, Sohar, Salalah or elsewhere in the GCC) and the date you need the goods.
- Any documents you need with the quotation, such as an installation leaflet or declaration of conformity.
Documents and quotation
The manufacturer specification sheet for PKE32/XTU-32 is attached on this page, so you can check the ratings, dimensions and approvals against your project before you order. Installation leaflets and declarations of conformity can be requested separately.
Seven Star LLC supplies Eaton industrial control products in Oman and the GCC. To request a quotation, send model PKE32/XTU-32, the quantity and your delivery location, and we will confirm availability and lead time for your order.
Other Models in the Eaton Pke Range
Seven Star LLC supplies models from the Eaton Pke range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Eaton PKE12/XTU-12 Electronic Motor-Protective Breaker 3-12 A | Circuit Breakers | View details |
| Eaton PKE12/XTU-4 Electronic Motor-Protective Breaker 1-4 A | Circuit Breakers | View details |
| Eaton PKE12/XTU-1,2 Motor-Protective Breaker 0.3-1.2 A | Circuit Breakers | View details |
| Eaton PKE32/XTU-32 Electronic Motor-Protective Breaker 8-32 A | Circuit Breakers | You are viewing this model |
Datasheets & Documents
- Datasheet Eaton PKE32/XTU-32 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Eaton is a power management company that began in 1911, when Joseph O. Eaton started a truck axle business in New York and moved it to Cleveland, Ohio, in 1914. It grew from vehicle components into electrical equipment, hydraulics and aerospace systems. Since buying Cooper Industries in 2012, Eaton has been incorporated in Ireland with its head office in Dublin, and it is listed on the New York Stock Exchange.
Seven Star LLC lists Eaton NZM molded case circuit breakers, PKZM0 motor-protective circuit breakers and Bussmann series Class J fuses, and supplies them to panel builders and maintenance teams in Oman and the GCC.
Eaton company profile
| Founded | 1911, New York, USA, by Joseph O. Eaton |
|---|---|
| Early move | Cleveland, Ohio, 1914 |
| Headquarters | Dublin, Ireland, since the 2012 Cooper Industries acquisition |
| Listing | New York Stock Exchange (ETN) |
| Brands | Eaton, Moeller, Bussmann, Crouse-Hinds, MTL and MEDC |
| Product families | FAZ and PL miniature circuit breakers, NZM moulded-case breakers, DILM contactors, PowerXL variable frequency drives, 9PX and 93PM UPS, Bussmann fuses, hazardous-area enclosures and signalling |
Milestones
- 1911: Joseph O. Eaton starts an axle business in New York.
- 1914: The business moves to Cleveland.
- 2012: Eaton acquires Cooper Industries and redomiciles in Ireland.
Eaton circuit protection listed here
The NZMN1-A80 is a frame size 1 molded case circuit breaker rated 80 A with a thermomagnetic release for cable and system protection. The PKZM0-1,6 is a motor-protective circuit breaker whose overload release is adjustable from 1 to 1.6 A, used as a manual motor starter. The LPJ-35SP is a Bussmann series Low-Peak Class J time-delay fuse rated 35 A at 600 V AC. Older NZM and PKZ devices carry the Moeller name on the nameplate, and the type designations are the same.
Where Eaton breakers and fuses are used
Motor control centers, feeder panels, machine control cabinets and UL-style fused disconnects.
Eaton products we list
Ordering Eaton parts: what we need
Send the full type and article number, the number of poles, the current rating or setting range, and any accessories such as auxiliary contacts, trip releases or rotary handles.
Facts checked against Eaton's corporate history and investor materials, October 2026.
Browse Eaton products by category: Circuit Breaker.
FAQ
Questions about the Eaton PKE32/XTU-32 Electronic Motor-Protective
Answers from our engineering team on installation, compatibility and integration.
01What is the setting range of the PKE32/XTU-32?
The electronic trip block of the complete device is adjustable from 8 A to 32 A, with a rated operational current of 32 A, according to the specification sheet.
02What motor power does the PKE32/XTU-32 cover?
In AC-3e the rated operational power is 7.5 kW at 230 V, 15 kW at 380/400 V and 440 V, 18.5 kW at 500 V and 30 kW at 690 V.
03How much heat does the PKE32/XTU-32 dissipate?
The sheet gives 11.4 W for the complete device at rated current, or 3.8 W per pole, with a resistance of 2.5 milliohm per pole.
04What is the switching capacity of the PKE32/XTU-32?
The sheet lists 32 A in AC-3 up to 690 V and 32 A for general use under UL/CSA ratings.
05What are the size and weight of the PKE32/XTU-32?
It is 101 mm deep, 102.5 mm high and 45 mm wide and weighs 0.436 kg. It mounts on a 35 mm top-hat rail.


















Reviews
There are no reviews yet.