Brand:

Eaton PKZM0-10 Motor-Protective Circuit-Breaker 6.3-10 A

Description

Eaton PKZM0-10 motor-protective circuit-breaker, 6.3–10 A

The Eaton PKZM0-10 (catalog number 072739) is a three-pole motor-protective circuit-breaker from the Moeller PKZM0 range. A single compact device gives thermal overload protection, short-circuit protection and a hand-operated on/off switch for a three-phase motor. The overload release is adjustable from 6.3 to 10 A and the rated operational power at 380/400 V, 50 Hz is 4 kW, so the PKZM0-10 is a typical choice for pumps, fans and conveyors in the 3 to 4 kW class. Seven Star LLC supplies the PKZM0-10 in Oman and the GCC for panel builders, contractors and maintenance teams.

Reading the PKZM0-10 model code

PKZM0 names the frame: a 45 mm wide, three-pole breaker with a turn-button actuator and screw terminals. The figure after the dash is the upper limit of the current dial in amperes, so the PKZM0-10 covers 6.3 to 10 A and carries a rated uninterrupted current of 10 A. The same frame continues upward with the PKZM0-16 (10 to 16 A) and, in the lower ratings, with 6.3 A and smaller devices. Catalog number 072739 identifies this exact version, and its EAN is 4015080727392.

PKZM0-10 technical specifications

Parameter Specification
Manufacturer / part number Eaton PKZM0-10 (catalog number 072739)
Series Eaton Moeller PKZM0
Product category Motor-protective circuit-breaker, three-pole
Rated operational voltage Ue 690 V, 50/60 Hz
Rated impulse withstand voltage Uimp 6000 V AC
Overvoltage category / pollution degree III / 3
Actuator Turn button
Tripping class 10 A
Short-circuit release Fixed at 15.5 × Iu (±20 %)
Setting range (overload release) 6.3 – 10 A
Rated uninterrupted current Iu 10 A
Rated operational power AC-3e, 230 V, 50 Hz 2.2 kW
Rated operational power AC-3e, 380/400 V, 50 Hz 4 kW
Rated operational power AC-3e, 440 V and 500 V, 50 Hz 4 kW
Rated operational power AC-3e, 690 V, 50 Hz 7.5 kW
Breaking capacity Icu / Ics at 400 V AC 150 kA / 150 kA
Breaking capacity Icu / Ics at 440 V AC 50 kA / 50 kA
Breaking capacity Icu / Ics at 500 V AC 42 kA / 11 kA
Breaking capacity Icu / Ics at 690 V AC 3 kA / 2 kA
Short-circuit release value 155 A (15.5 × 10 A)
Switching capacity 10 A, AC-3 up to 690 V
Heat dissipation, total / per pole 6.48 W / 2.16 W
Degree of protection IP20; terminals IP00
Connection Screw terminals, 1 or 2 × 1–6 mm²
Dimensions (depth x height x width) 76 x 93 x 45 mm
Weight 0.295 kg
Mechanical / electrical lifespan 100,000 operations each
Operating frequency 40 operations per hour
Ambient operating temperature −25 to 55 °C open; −25 to 40 °C enclosed
Ambient storage temperature −40 to 80 °C
Maximum altitude 2000 m
Mounting 35 mm top-hat rail to IEC/EN 60715, 7.5 or 15 mm height

The figures follow the manufacturer specification sheet for catalog number 072739. For North American ratings the same sheet lists assigned motor power of 0.5 HP at 115/120 V single-phase, 1.5 HP at 230/240 V single-phase, 3 HP at 200/208 V and 230/240 V three-phase, 7.5 HP at 460/480 V and 10 HP at 575/600 V, all at 60 Hz.

How the PKZM0-10 protects the motor circuit

Each pole holds a thermal element and a magnetic element. The thermal element follows the motor current over time and opens the breaker when the current stays above the dial setting, which covers a jammed pump, a blocked fan or a worn bearing. The magnetic element reacts without delay to a short circuit, at a fixed trip value of 155 A for this rating, and opens all three poles together. Trip class 10 A suits normal starting duty. The device is phase-failure sensitive to IEC/EN 60947-4-1 and VDE 0660 part 102, so it trips when one phase is lost and the motor would otherwise run single-phase.

The breaking capacity is the notable strength of the PKZM0-10: 150 kA at 400 V is very high for a device 45 mm wide. The values fall to 42 kA (Icu) and 11 kA (Ics) at 500 V and to 3 kA and 2 kA at 690 V, so on higher-voltage supplies the upstream protection must be checked against these figures and not against the 400 V number.

Where the PKZM0-10 fits in a starter or feeder

The usual role of the PKZM0-10 is the protective element of a direct-on-line starter. It sits ahead of a contactor and carries the overload and short-circuit duty, while the contactor handles the repeated switching. With a rated operating frequency of 40 operations per hour the breaker itself is not meant to be the main switching device for motors that start and stop often. In the same family the PKZM0-16 extends the range to 16 A, and the PKZM0-16/NHI11 adds a built-in auxiliary switch where a status signal is needed. Panel builders also use the PKZM0 frame as a compact feeder disconnect in front of small drives.

Choosing the right PKZM0 rating

  • Take the full-load current from the motor nameplate at the actual supply voltage, not from the kW figure alone.
  • Select the range so the nameplate current sits in the middle of the 6.3 to 10 A dial rather than at its limit.
  • Compare the prospective short-circuit current with the Icu and Ics values at your voltage: 150 kA at 400 V but only 3 kA Icu at 690 V.
  • Check that the device matches the starting duty, since trip class 10 A is intended for normal starting.
  • Decide on accessories such as an auxiliary contact or a busbar adapter before the panel layout is fixed.
  • Check the panel temperature against the 40 °C enclosed rating of the breaker.

Installation and maintenance of the PKZM0-10

The PKZM0-10 snaps onto a 35 mm top-hat rail. Connect the supply to the upper terminals and the motor to the lower terminals, strip the conductors to 10 mm and tighten the screw terminals to the torque in the instruction leaflet, then set the dial to the nameplate current of the motor. Terminals accept one or two conductors of 1 to 6 mm² with ferrules. During maintenance, look for discoloured terminals, re-check the dial after any motor replacement, and operate the turn button occasionally in installations where it rarely moves. A breaker that trips again straight after reset points to a motor or cable fault that should be traced before the device is replaced.

Typical applications in Oman and the GCC

In Oman and the wider Gulf region the PKZM0-10 is found in water treatment skids, desalination auxiliaries, HVAC plant rooms, oil and gas utility buildings and light industry, where three-phase motors of up to about 4 kW need a robust local protective device. Panels in these places run hot and collect dust, so the enclosed rating of 40 °C should be checked against the real panel temperature, and ventilation or filtering should be planned accordingly. Typical loads are circulation pumps, dosing pumps, extraction fans and small compressors.

Eaton PKZM0 family at a glance

Model Setting range Distinguishing feature
PKZM0-10 6.3 – 10 A 4 kW at 380/400 V, screw terminals
PKZM0-16 10 – 16 A 7.5 kW at 380/400 V, screw terminals
PKZM0-16-PI 10 – 16 A Push-in terminals top and bottom
PKZM0-16-SPI16 10 – 16 A Screw terminals on feed side, push-in on output side
PKZM0-16/NHI11 10 – 16 A Built-in auxiliary switch, 1 N/O + 1 N/C

The table lists the PKZM0 models covered on our pages; confirm the full ratings of each device from its own specification sheet before use.

Information to send with an RFQ for PKZM0-10

  • Exact model PKZM0-10 (catalog number 072739) and the quantity, including spares.
  • Motor nameplate current, voltage, power and starting duty.
  • Prospective short-circuit current at the installation point.
  • Any accessory needed with the breaker, such as an auxiliary contact.
  • Delivery location (Muscat, Sohar, Salalah or elsewhere in the GCC) and the date you need the goods.
  • Any documents you need with the quotation, such as an installation leaflet or declaration of conformity.

Documents and quotation

The manufacturer specification sheet for PKZM0-10 is attached on this page, so you can check the ratings, dimensions and approvals against your project before you order. Installation leaflets and declarations of conformity can be requested separately.

Seven Star LLC supplies Eaton industrial control products in Oman and the GCC. To request a quotation, send model PKZM0-10, the quantity and your delivery location, and we will confirm availability and lead time for your order.

Other Models in the Eaton Pkzm0 Range

Seven Star LLC supplies models from the Eaton Pkzm0 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Eaton PKZM0-6,3 Motor-Protective Circuit-Breaker 4-6.3 ACircuit BreakersView details
Eaton PKZM0-10 Motor-Protective Circuit-Breaker 6.3-10 ACircuit BreakersYou are viewing this model
Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Eaton is a power management company that began in 1911, when Joseph O. Eaton started a truck axle business in New York and moved it to Cleveland, Ohio, in 1914. It grew from vehicle components into electrical equipment, hydraulics and aerospace systems. Since buying Cooper Industries in 2012, Eaton has been incorporated in Ireland with its head office in Dublin, and it is listed on the New York Stock Exchange.

Seven Star LLC lists Eaton NZM molded case circuit breakers, PKZM0 motor-protective circuit breakers and Bussmann series Class J fuses, and supplies them to panel builders and maintenance teams in Oman and the GCC.

Eaton company profile

Founded 1911, New York, USA, by Joseph O. Eaton
Early move Cleveland, Ohio, 1914
Headquarters Dublin, Ireland, since the 2012 Cooper Industries acquisition
Listing New York Stock Exchange (ETN)
Brands Eaton, Moeller, Bussmann, Crouse-Hinds, MTL and MEDC
Product families FAZ and PL miniature circuit breakers, NZM moulded-case breakers, DILM contactors, PowerXL variable frequency drives, 9PX and 93PM UPS, Bussmann fuses, hazardous-area enclosures and signalling

Milestones

  • 1911: Joseph O. Eaton starts an axle business in New York.
  • 1914: The business moves to Cleveland.
  • 2012: Eaton acquires Cooper Industries and redomiciles in Ireland.

Eaton circuit protection listed here

The NZMN1-A80 is a frame size 1 molded case circuit breaker rated 80 A with a thermomagnetic release for cable and system protection. The PKZM0-1,6 is a motor-protective circuit breaker whose overload release is adjustable from 1 to 1.6 A, used as a manual motor starter. The LPJ-35SP is a Bussmann series Low-Peak Class J time-delay fuse rated 35 A at 600 V AC. Older NZM and PKZ devices carry the Moeller name on the nameplate, and the type designations are the same.

Where Eaton breakers and fuses are used

Motor control centers, feeder panels, machine control cabinets and UL-style fused disconnects.

Eaton products we list

Family Examples
Circuit Breakers LPJ-35SP Class J Time-Delay Fuse, NZMN1-A80 Molded Case Circuit Breaker, NZMN2-A250 Molded Case Circuit Breaker, NZMN3-AE400 Molded Case Circuit Breaker, PKZM0-1
AC Drives DA1-342D2FB-A20C AC Drive, PowerXL DG1-34140FN-C21C Variable Freque…

Ordering Eaton parts: what we need

Send the full type and article number, the number of poles, the current rating or setting range, and any accessories such as auxiliary contacts, trip releases or rotary handles.

Facts checked against Eaton's corporate history and investor materials, October 2026.

FAQ

Questions about the Eaton PKZM0-10 Motor-Protective Circuit-Breaker

Answers from our engineering team on installation, compatibility and integration.

01What current range does the PKZM0-10 cover?
The overload release is adjustable from 6.3 A to 10 A and the rated uninterrupted current is 10 A. Set the dial to the motor nameplate current, ideally in the middle of the scale.
02What motor power can the PKZM0-10 protect?
At 380/400 V and 50 Hz the rated operational power in AC-3e is 4 kW. At 230 V it is 2.2 kW, at 440 V and 500 V it is 4 kW and at 690 V it is 7.5 kW.
03What is the short-circuit breaking capacity of the PKZM0-10?
Icu and Ics are both 150 kA at 400 V AC and 50 kA at 440 V AC. At 500 V Icu is 42 kA and Ics is 11 kA, and at 690 V they are 3 kA and 2 kA, so check upstream protection on higher voltages.
04Does the PKZM0-10 trip on phase failure?
Yes. The sheet lists phase-failure sensitivity to IEC/EN 60947-4-1 and VDE 0660 part 102, so the breaker opens when a phase is lost, in addition to overload and short-circuit protection.
05How is the PKZM0-10 mounted and what ambient range applies?
It snaps onto a 35 mm top-hat rail of 7.5 or 15 mm height. Operation is rated from -25 to 55 degrees C in open air or -25 to 40 degrees C when enclosed, with IP20 protection and IP00 terminals.