Brand:

Eaton PKZM0-16 Motor-Protective Circuit-Breaker 10-16 A

Description

Eaton PKZM0-16 motor-protective circuit-breaker, 10–16 A

The Eaton PKZM0-16 (catalog number 046938) is the top rating of the compact PKZM0 motor-protective circuit-breaker frame. It is three-pole, adjustable from 10 to 16 A, and rated for 7.5 kW at 380/400 V, 50 Hz. One device combines overload release, short-circuit release and a manual switch, so it can protect and isolate a motor feeder without a separate fuse and thermal relay. Seven Star LLC supplies the PKZM0-16 in Oman and the GCC for contractors, OEMs and plant maintenance teams who need a reliable starter protection device on a rail.

What the PKZM0-16 designation tells you

PKZM0 is the frame family, 45 mm wide with a turn-button actuator. The number after the dash gives the maximum current of the setting range, so the PKZM0-16 is set between 10 and 16 A and has a rated uninterrupted current of 16 A. Several variants of the same rating exist with different connection systems or built-in accessories, such as the push-in version PKZM0-16-PI and the version with auxiliary switch PKZM0-16/NHI11. This page describes the plain screw-terminal device, catalog number 046938, EAN 4015080469384.

PKZM0-16 technical specifications

Parameter Specification
Manufacturer / part number Eaton PKZM0-16 (catalog number 046938)
Series Eaton Moeller PKZM0
Product category Motor-protective circuit-breaker, three-pole
Rated operational voltage Ue 690 V, 50/60 Hz
Rated impulse withstand voltage Uimp 6000 V AC
Overvoltage category / pollution degree III / 3
Actuator Turn button
Tripping class 10 A
Short-circuit release Fixed at 15.5 × Iu (±20 %)
Setting range (overload release) 10 – 16 A
Rated uninterrupted current Iu 16 A
Rated operational power AC-3e, 230 V, 50 Hz 4 kW
Rated operational power AC-3e, 380/400 V, 50 Hz 7.5 kW
Rated operational power AC-3e, 440 V and 500 V, 50 Hz 9 kW
Rated operational power AC-3e, 690 V, 50 Hz 12.5 kW
Breaking capacity Icu / Ics at 400 V AC 50 kA / 38 kA
Breaking capacity Icu / Ics at 440 V AC 15 kA / 12 kA
Breaking capacity Icu / Ics at 500 V AC 15 kA / 4 kA
Breaking capacity Icu / Ics at 690 V AC 3 kA / 2 kA
Short-circuit release value 248 A (15.5 × 16 A)
Switching capacity 16 A, AC-3 up to 690 V; DC-5 to 250 V with three contacts in series
Heat dissipation, total / per pole 6.43 W / 2.14 W
Degree of protection IP20; terminals IP00
Connection Screw terminals, 1 or 2 × 1–6 mm², stripping length 10 mm, 1.7 Nm
Dimensions (depth x height x width) 76 x 93 x 45 mm
Weight 0.292 kg
Mechanical / electrical lifespan 100,000 operations each
Operating frequency 40 operations per hour
Ambient operating temperature −25 to 55 °C open; −25 to 40 °C enclosed
Ambient storage temperature −40 to 80 °C
Maximum altitude 2000 m
Mounting 35 mm top-hat rail to IEC/EN 60715, 7.5 or 15 mm height

Listed approvals on the sheet include IEC/EN 60947-4-1, VDE 0660, UL 60947-4-1, CSA and CE marking. For North America the sheet gives assigned motor power of 1 HP at 115/120 V single-phase, 2 HP at 230/240 V single-phase, 3 HP at 200/208 V, 5 HP at 230/240 V, 10 HP at 460/480 V and 10 HP at 575/600 V three-phase at 60 Hz.

How the PKZM0-16 responds to faults

Thermal elements in all three poles integrate the motor current and open the breaker on sustained overload, with trip class 10 A for normal starting. A fixed magnetic release at 15.5 times the rated current, 248 A for this rating, clears short circuits without delay. Phase-failure sensitivity to IEC/EN 60947-4-1 means a lost phase also leads to a trip. The sheet states that the device is also suitable for motors of efficiency class IE3.

Compared with the smaller PKZM0 ratings, the short-circuit capacity of the PKZM0-16 is lower: Icu is 50 kA and Ics 38 kA at 400 V, against 150 kA for the 10 A device. At 500 V the service breaking capacity falls to 4 kA, so for any installation with high fault levels a back-up fuse or a current-limiting upstream device should be considered and the combination confirmed in the manufacturer tables.

Using the PKZM0-16 in a motor starter

The PKZM0-16 is normally paired with a DILM contactor to form a direct-on-line or reversing starter, with the breaker providing protection and isolation and the contactor doing the frequent switching. The breaker itself is rated for 40 operations per hour. For a 7.5 kW motor at 400 V the full-load current is close to the top of the dial, so the PKZM0-16 is usually chosen for motors of roughly 5.5 to 7.5 kW, while a 4 kW motor is better served by the PKZM0-10 so that the setting sits mid-scale. Where a signal to the PLC is needed, the PKZM0-16/NHI11 version carries a built-in auxiliary switch.

Selection checklist for the PKZM0-16

  • Confirm the motor nameplate current at the real supply voltage and verify that it falls inside 10 to 16 A.
  • Compare the prospective short-circuit current with Icu and Ics at 400 V, 500 V or 690 V, because the values differ by an order of magnitude.
  • Choose between screw, push-in and mixed terminals according to panel wiring practice and maintenance preference.
  • Check the ambient temperature inside the enclosure: 55 °C open, 40 °C enclosed.
  • Allow for 6.43 W of heat from the three poles at full current when sizing panel ventilation.

Installation and commissioning of the PKZM0-16

Mount the PKZM0-16 on a 35 mm rail with the turn button accessible from the front. Strip the cable by 10 mm, insert one or two conductors of 1 to 6 mm² and tighten the terminal screws to 1.7 Nm. After wiring, set the dial to the motor nameplate current, switch the breaker on and run the motor under load, then check the current with a clamp meter. Record the final setting in the panel documentation. At each service interval inspect terminals for heat marks and confirm the dial position.

Where the PKZM0-16 is used in Oman and the GCC

The PKZM0-16 appears in compressor rooms, cooling-water pump stations, fan coil and chiller auxiliaries, conveyor drives and workshop machines across Oman and the Gulf. These sites combine high ambient temperature with dust and humidity, so the enclosure temperature matters more than the room temperature. Where the panel is placed outdoors or in a poorly ventilated container, derating considerations and filtered cooling are usually required before the 40 °C enclosed limit can be met.

Eaton PKZM0 family at a glance

Model Setting range Distinguishing feature
PKZM0-10 6.3 – 10 A 4 kW at 380/400 V, screw terminals
PKZM0-16 10 – 16 A 7.5 kW at 380/400 V, screw terminals
PKZM0-16-PI 10 – 16 A Push-in terminals top and bottom
PKZM0-16-SPI16 10 – 16 A Screw terminals on feed side, push-in on output side
PKZM0-16/NHI11 10 – 16 A Built-in auxiliary switch, 1 N/O + 1 N/C

Information to send with an RFQ for PKZM0-16

  • Exact model PKZM0-16 (catalog number 046938) and the quantity, including spares.
  • Motor nameplate current, voltage, power and starting duty.
  • Preferred terminal type: screw, push-in or mixed.
  • Prospective short-circuit current at the panel.
  • Delivery location (Muscat, Sohar, Salalah or elsewhere in the GCC) and the date you need the goods.
  • Any documents you need with the quotation, such as an installation leaflet or declaration of conformity.

Documents and quotation

The manufacturer specification sheet for PKZM0-16 is attached on this page, so you can check the ratings, dimensions and approvals against your project before you order. Installation leaflets and declarations of conformity can be requested separately.

Seven Star LLC supplies Eaton industrial control products in Oman and the GCC. To request a quotation, send model PKZM0-16, the quantity and your delivery location, and we will confirm availability and lead time for your order.

Other Models in the Eaton Pkzm0 Range

Seven Star LLC supplies models from the Eaton Pkzm0 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Eaton PKZM0-6,3 Motor-Protective Circuit-Breaker 4-6.3 ACircuit BreakersView details
Eaton PKZM0-10 Motor-Protective Circuit-Breaker 6.3-10 ACircuit BreakersView details
Eaton PKZM0-16 Motor-Protective Circuit-Breaker 10-16 ACircuit BreakersYou are viewing this model
Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Eaton is a power management company that began in 1911, when Joseph O. Eaton started a truck axle business in New York and moved it to Cleveland, Ohio, in 1914. It grew from vehicle components into electrical equipment, hydraulics and aerospace systems. Since buying Cooper Industries in 2012, Eaton has been incorporated in Ireland with its head office in Dublin, and it is listed on the New York Stock Exchange.

Seven Star LLC lists Eaton NZM molded case circuit breakers, PKZM0 motor-protective circuit breakers and Bussmann series Class J fuses, and supplies them to panel builders and maintenance teams in Oman and the GCC.

Eaton company profile

Founded 1911, New York, USA, by Joseph O. Eaton
Early move Cleveland, Ohio, 1914
Headquarters Dublin, Ireland, since the 2012 Cooper Industries acquisition
Listing New York Stock Exchange (ETN)
Brands Eaton, Moeller, Bussmann, Crouse-Hinds, MTL and MEDC
Product families FAZ and PL miniature circuit breakers, NZM moulded-case breakers, DILM contactors, PowerXL variable frequency drives, 9PX and 93PM UPS, Bussmann fuses, hazardous-area enclosures and signalling

Milestones

  • 1911: Joseph O. Eaton starts an axle business in New York.
  • 1914: The business moves to Cleveland.
  • 2012: Eaton acquires Cooper Industries and redomiciles in Ireland.

Eaton circuit protection listed here

The NZMN1-A80 is a frame size 1 molded case circuit breaker rated 80 A with a thermomagnetic release for cable and system protection. The PKZM0-1,6 is a motor-protective circuit breaker whose overload release is adjustable from 1 to 1.6 A, used as a manual motor starter. The LPJ-35SP is a Bussmann series Low-Peak Class J time-delay fuse rated 35 A at 600 V AC. Older NZM and PKZ devices carry the Moeller name on the nameplate, and the type designations are the same.

Where Eaton breakers and fuses are used

Motor control centers, feeder panels, machine control cabinets and UL-style fused disconnects.

Eaton products we list

Family Examples
Circuit Breakers LPJ-35SP Class J Time-Delay Fuse, NZMN1-A80 Molded Case Circuit Breaker, NZMN2-A250 Molded Case Circuit Breaker, NZMN3-AE400 Molded Case Circuit Breaker, PKZM0-1
AC Drives DA1-342D2FB-A20C AC Drive, PowerXL DG1-34140FN-C21C Variable Freque…

Ordering Eaton parts: what we need

Send the full type and article number, the number of poles, the current rating or setting range, and any accessories such as auxiliary contacts, trip releases or rotary handles.

Facts checked against Eaton's corporate history and investor materials, October 2026.

FAQ

Questions about the Eaton PKZM0-16 Motor-Protective Circuit-Breaker

Answers from our engineering team on installation, compatibility and integration.

01What setting range does the PKZM0-16 offer?
The overload release is adjustable from 10 A to 16 A and the rated uninterrupted current is 16 A. The dial should be set to the motor nameplate current at the actual supply voltage.
02What motor power is the PKZM0-16 rated for?
In AC-3e at 380/400 V and 50 Hz the rating is 7.5 kW. At 230 V it is 4 kW, at 440 V and 500 V it is 9 kW and at 690 V it is 12.5 kW.
03What are the breaking capacities of the PKZM0-16?
At 400 V AC Icu is 50 kA and Ics 38 kA. At 440 V they are 15 kA and 12 kA, at 500 V 15 kA and 4 kA, and at 690 V 3 kA and 2 kA, as listed on the specification sheet.
04What is the short-circuit release setting of the PKZM0-16?
The short-circuit release is fixed at 15.5 times the rated current with a tolerance of plus or minus 20 percent, which is 248 A for this 16 A rating. It is not adjustable.
05What conductors fit the PKZM0-16 terminals?
The screw terminals accept one or two conductors of 1 to 6 square millimetres with ferrules, AWG 18 to 10, with a stripping length of 10 mm and a tightening torque of 1.7 Nm.