Brand:

Allen-Bradley 2080-OW4I 4-Channel Relay Output Plug-in

Description

Four isolated relay outputs for AC or DC loads on a Micro800

The Allen-Bradley 2080-OW4I adds four dry-contact relay outputs to a Micro800 controller. Rockwell describes the module as a 4-channel AC/DC relay output with isolation between the outputs and to the backplane, so it can switch loads that a transistor output cannot, such as 120 or 240V AC coils and small solenoids.

The relay contacts have an initial contact resistance of at most 30 milliohms and an output delay of 10 ms each way, according to the product page. A yellow indicator shows each channel state.

Technical specifications

Parameter Specification
Number of I/O 4-channel relay output
Type of digital output Relay
Resistive output current 2A @ 5…30V DC, 0.5A @ 48V DC, 0.22A @ 125V DC, 2A @ 125V AC, 2A @ 240V AC
Output power, resistive, max 250VA for 125V AC resistive loads, 480VA for 240V AC resistive loads, 60VA for 30V DC resistive loads, 24VA for 48V DC resistive loads, 27.5VA for 125V DC resistive loads
Relay contact, continuous 2.0A @ 120V AC maximum volts, 0.35 power factor
Relay contact, make 7.5A @ 240V AC maximum volts, 0.35 power factor
Relay contact, break 28VA @ 24V DC maximum volts, 0.35 power factor
Pilot duty rating C300, R150
Minimum load per point 10 mA
Initial contact resistance of relay, max 30 mohm
Output delay time, max OFF to ON: 10 ms, ON to OFF: 10 ms
Backplane power 3.3V DC @ 38mA
Inrush current under 120mA @ 3.3V, under 120mA @ 24V
Isolation voltage 240V (continuous), reinforce insulation type, between output channels and output channels to backplane type tested for 60 s @ 1480V AC Outputs to Outputs, Outputs to Backplane
Status indicator 4 yellow
Wire size 0.05…1.31 mm2 (30…16 AWG) solid copper wire rated @ 90 °C (194 °F ) insulation maximum
Operating temperature -20 to 65 °C

Reading the contact ratings

For resistive loads the table gives 2 A at 5 to 30V DC, 0.5 A at 48V DC, 0.22 A at 125V DC and 2 A at both 125V AC and 240V AC. The pilot duty rating is C300 and R150, and the minimum load per point is 10 mA, so very small signals should go through a different output type.

Inductive ratings are lower than resistive ones for DC: 1.0 A steady state at 5 to 28V DC, 0.93 A at 30V DC, 0.5 A at 48V DC and 0.22 A at 125V DC. Keep a margin when switching relay coils or valves, and add arc suppression where the load calls for it.

Isolation and installation

The isolation rating is 240V continuous with reinforced insulation between output channels, and between outputs and the backplane, type-tested for 60 seconds at 1480V AC. That allows one module to switch mixed voltages from separate circuits, provided the wiring practice for your site is followed.

Terminal screws take 0.19 Nm maximum, and wire is 0.05 to 1.31 mm2 solid copper. The manual lists plug-in slot counts of 2 for Micro820, 2, 3 or 5 for Micro830 (10/16, 24 and 48 point), 3 or 5 for Micro850 (24 and 48 point) and 3 for Micro870, while Micro810 has none.

Ordering and documents

Order 2080-OW4I exactly as printed. The hosted document is the 2080-UM004F plug-in modules user manual, and the photo is the official Rockwell product photograph of this module. See more automation parts in the PLC & I/O Cards category.

Seven Star LLC is an independent supplier in Muscat and quotes on request. Please confirm the catalog number, ratings and the current product status against the latest Rockwell Automation documents before ordering.

Datasheets & Documents
  • PDF User manual Micro800 Plug-in Modules User Manual (2080-UM004F-EN-E, February 2026) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Allen-Bradley is the brand of Rockwell Automation for industrial control: ControlLogix and CompactLogix controllers, I/O systems, PanelView operator terminals, PowerFlex drives, motor control and industrial network equipment. The company began in Milwaukee in 1903, when Lynde Bradley and Dr. Stanton Allen formed the Compression Rheostat Company to make the motor speed controller Bradley had invented in 1901. It took the name Allen-Bradley in 1909 and was bought by Rockwell International in 1985. Since 2001 its owner has been Rockwell Automation, which is still headquartered in Milwaukee, Wisconsin.

Allen-Bradley company profile

Founded 1903, Milwaukee, Wisconsin, USA, as the Compression Rheostat Company
Founders Lynde Bradley (inventor of the compression rheostat, 1901) and Dr. Stanton Allen (investor); Harry Bradley joined in 1904
Name Allen-Bradley Company from 1909
Ownership Acquired by Rockwell International in 1985 for about USD 1.65 billion; a brand of Rockwell Automation (NYSE: ROK) since 2001
Headquarters Milwaukee, Wisconsin, USA
Product families Logix programmable automation controllers (ControlLogix, CompactLogix), legacy SLC 500 and MicroLogix PLCs, Micro800 controllers, POINT, FLEX and Compact I/O, PanelView HMIs, PowerFlex AC drives, contactors, motor starters and soft starters, safety components, Stratix Ethernet switches

Milestones

  • 1901: Lynde Bradley invents the compression rheostat to control the speed of electric motors.
  • 1903: The Compression Rheostat Company is formed in Milwaukee with an initial investment of USD 1,000.
  • 1904: Harry Bradley joins; a crane controller is shown at the St. Louis World's Fair.
  • 1909: The company is renamed Allen-Bradley.
  • 1985: Rockwell International acquires Allen-Bradley.
  • 2001: Rockwell Automation becomes the company's name; the Allen-Bradley brand marks 100 years in 2003.

Reading Allen-Bradley catalogue numbers

The first digits of an Allen-Bradley catalogue number identify the platform, which tells you what is compatible with what. 1756 is ControlLogix (chassis-based, used for large process and plant control), 1769 is CompactLogix 5370 with Compact I/O, 5069 is CompactLogix 5380 with Compact 5000 I/O, 1734 is POINT I/O, 1794 and 5094 are FLEX and FLEX 5000 distributed I/O, 1746 and 1747 belong to the older SLC 500 family, 1766 is MicroLogix 1400 and 2080 is Micro800. For drives, 25B is PowerFlex 525 and 22B is PowerFlex 40; in a code such as 25B-D010N114, "D" means 380–480 V, "010" is the output current rating, and N114 instead of N104 means the drive has an integrated EMC filter. Many plants in the region still run SLC 500 and older MicroLogix systems, which Rockwell has discontinued, so exact spares and migration to CompactLogix are both common requests.

Where Allen-Bradley products are used

In Oman and the GCC, Allen-Bradley controllers and drives run on oil and gas facilities, water treatment and pumping stations, cement, food and beverage and packaging plants, and on machines supplied by American OEMs. ControlLogix is often the platform for plant control systems, while PowerFlex drives are used on pumps, fans and conveyors.

Allen-Bradley products we list

Family Examples
ControlLogix 1756-L85E, 1756-EN2T, 1756-EN2TR, 1756-IF16, 1756-IB32, 1756-PA75, 1756-A10
CompactLogix and Micro controllers 5069-L320ER, 5069-L340ERM, 1769-L33ER, 1769-L16ER, MicroLogix 1400, Micro820, SLC 500 (1746)
Distributed I/O 1734-AENTR, 1734-IB8, 1734-IE2C, 1734-IB8S safety, 1794-AENTR, 5094-AENTR, 5069-IF8
Operator terminals PanelView Plus 7 10-inch, PanelView Plus 7 15-inch, PanelView 800, PanelView 5310
Drives, motor control and networking PowerFlex 525, PowerFlex 755, PowerFlex 4, 150-A180NBD SMC, Stratix 2000, 1783-NATR

Ordering Allen-Bradley products: what we need

Send the full catalogue number and the series letter from the label (for example 1756-EN2T Series D), because firmware and compatibility can change between series. For drives, add the motor power, voltage and filter option. For a discontinued SLC 500 or MicroLogix part, tell us whether you need the exact spare or a migration proposal.

Facts checked against Rockwell Automation's published company history, October 2026.

FAQ

Questions about the Allen-Bradley 2080-OW4I 4-Channel Relay Output

Answers from our engineering team on installation, compatibility and integration.

01What kind of output is 2080-OW4I?
Four relay outputs with dry contacts, AC or DC.
02What is the resistive rating at 240V AC?
2 A per the product page; the module output power is limited to 480 VA at 240V AC resistive.
03What is the minimum load per point?
10 mA.
04How fast does it switch?
Output delay time is a maximum of 10 ms OFF to ON and 10 ms ON to OFF.
05Is the module isolated?
Yes, outputs are isolated from each other and from the backplane, rated 240V continuous.