Brand:

Allen-Bradley 1766-L32BXBA MicroLogix 1400 Controller

Description

A 24V DC MicroLogix 1400 with analog I/O

The Allen-Bradley 1766-L32BXBA is a MicroLogix 1400 programmable controller with a 24V DC power supply. It combines 32 base digital I/O points with four analog voltage inputs and two analog voltage outputs, relay and transistor outputs on the same base, a built-in EtherNet/IP port and an isolated RS-232/RS-485 serial port. It is a compact controller for machines and small process skids that need fast counting and positioning as well as network connectivity.

The digital side offers twelve high-speed 24V DC inputs that respond up to 100 kHz, eight standard 24V DC inputs, six relay outputs and six FET outputs, of which three are designed for high-speed pulse train and pulse width modulation operation.

Technical specifications

Parameter Specification
Catalog number 1766-L32BXBA (analog version of the 1766-L32BXB)
Controller MicroLogix 1400 programmable controller, 32 base I/O
Power supply 24V DC Class 2 SELV
Power consumption 50 W; 7.5 W with no 1762 expansion I/O
Power supply inrush current 24V DC: 15 A for 20 ms
Total I/O 24 inputs (20 digital and 4 analog) and 14 outputs (12 digital and 2 analog)
Digital inputs 12 high-speed 24V DC inputs (0…100 kHz) and 8 standard 24V DC inputs (0 Hz…1 kHz), sink/source
Analog inputs 4 voltage inputs, 0…10V DC, 12-bit, 0…4,095 counts; ±1.0% of full scale
Digital outputs 6 relay outputs, 3 fast FET DC outputs and 3 normal FET DC outputs
Analog outputs 2 single-ended voltage outputs, 0…10V DC, 12-bit, 1 kΩ load minimum, 3 ms settling
Relay contact rating 2.5 A continuous per channel; 1080 VA maximum controlled load for the BXB group
FET output 24V DC; surge 4.0 A for 10 ms; fast outputs 2, 3 and 4 support PTO and PWM
Communications EtherNet/IP port and an isolated RS-232/RS-485 combo port
Expansion Up to seven 1762 modules; 5V and 24V expansion bus limits of 1500 mA (1300 mA for series C)
Dimensions (H x W x D) 90 x 180 x 87 mm (3.5 x 7.087 x 3.43 in.)
Shipping weight 0.9 kg (2.0 lb)
Wire size 0.25…2.5 mm² (22…14 AWG) copper rated 90 °C; terminal screw torque 0.79 N•m (7.0 lb•in)
Enclosure type rating None (open-style)
North American temperature code T3C

Inputs, outputs and power

The power supply is 24V DC Class 2 SELV and the controller takes up to 50 W, or 7.5 W with no expansion I/O attached. The analog inputs are 0 to 10V with 12-bit resolution and an overall accuracy of ±1.0% of full scale, and the analog outputs are 0 to 10V with a 3 ms setting time and a 30 m shielded cable limit. The relay outputs are rated 2.5 A per channel, and the FET outputs allow 4.0 A surge for 10 ms.

The expansion bus supports up to seven 1762 modules, within the 5V and 24V current limits printed in the data sheet. Terminals accept 0.25 to 2.5 mm² (22 to 14 AWG) copper wire and are tightened to 0.79 N•m.

Model naming and variants

The MicroLogix 1400 family covers the 1766-L32AWA and 1766-L32AWAA with 120V AC inputs, the 1766-L32BWA and 1766-L32BWAA with 24V DC inputs and relay outputs, and the 1766-L32BXB and 1766-L32BXBA with a 24V DC supply and mixed relay and FET outputs. The trailing letter A in the catalog number marks the versions with built-in analog I/O.

Panel installation and wiring practice

The 1766-L32BXBA is an open-style controller, so it has to sit inside an enclosure that gives the protection the site needs. Mount it as described in the attached installation instructions, with clear space for air to move around the housing and room for 1762 expansion modules to be added later. Keep heat-producing devices such as power supplies and contactors away from it, and feed the 24V DC Class 2 supply from a dedicated source. Separate the analog cables from relay and motor wiring, use shielded cable for the 0 to 10V signals within the 30 m limit given in the data sheet, and tighten each terminal screw to 0.79 N•m with copper wire in the size range listed above.

Commissioning the controller

Before downloading a program, assign the controller an IP address that fits the plant addressing plan and confirm that the EtherNet/IP port is reachable from the engineering workstation. Verify each digital input from its field device, then switch each output with the machine in a safe state to prove the relay and FET wiring. Apply known voltages from a calibrator to the analog inputs and compare the counts with the 0 to 4,095 scale, then drive the analog outputs and measure the result at the field device. Where the fast outputs generate pulse trains for an axis, test at low frequency first and confirm direction and stopping before running at full speed.

Heat, dust and power quality on Omani sites

Small machines and skids in Oman are often installed in workshops, pump houses or containerised plant rooms where summer heat builds up quickly. An open-style controller depends entirely on its enclosure, so specify filtered ventilation or cooling sized for the total heat of the panel, and check that the internal temperature stays within the limits in the installation instructions. Fine dust can bridge terminals and block filters, so gland every cable entry and clean filters on a schedule. Where large motor starts disturb the plant supply, a well-regulated 24V DC power supply for the controller, separate from the supply for field devices, helps keep it stable.

Maintenance and backup routine

Keep a current copy of the program, the network settings and a record of any forced or temporary changes, stored away from the machine. Include terminal tightness, enclosure cleanliness and the condition of the relay outputs in planned maintenance, since relay contacts wear with switching load. When a controller is replaced, match the catalog number and series letter on the label so the program and expansion I/O carry over without surprises.

Documents and quotation

The Rockwell Automation MicroLogix 1400 installation instructions are attached. See our PLC and I/O cards catalogue for related controllers and I/O. Confirm the exact catalog number, series letter and firmware or hardware revision on the product label, and the compatibility with your existing system, before ordering. Stock and lead time are confirmed at quotation.

Datasheets & Documents
  • PDF Installation instructions Rockwell Automation MicroLogix 1400 Programmable Controllers Installation Instructions 1766-IN001 (English) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Catalog numbers beginning 1756, 1734, 1746 or 5069 are read at a glance by anyone who maintains Allen-Bradley control panels. The brand, the control hardware name of Rockwell Automation, dates back to 1903 in Milwaukee, USA. Seven Star LLC sources and supplies Allen-Bradley PLC and I/O modules, communication adapters and PowerFlex drives for plants in Oman, matching catalog number, series letter and firmware against the manufacturer's documentation.

Allen-Bradley product families listed here

Current controller platforms on this page are ControlLogix, with the 1756-L85E ControlLogix 5580 controller and the 1756-PA72 chassis power supply, and CompactLogix 5380, with the 5069-L320ER and 5069-L340ERM. Distributed I/O is represented by POINT I/O: the 1734-AENTR dual-port EtherNet/IP adapter and the 1734-IB8 digital input module. Allen-Bradley drives listed include the PowerFlex 525 and PowerFlex 755. For installed systems there are SLC 500 parts: the 1746-A10 chassis, 1746-NI16I analog input module, 1747-ASB remote I/O adapter, 1747-KE interface and 1747-M13 memory module.

Where Allen-Bradley hardware is used

ControlLogix and CompactLogix controllers run packaged equipment and plant utilities: compressor and pump skids, water and wastewater plants, power distribution, material handling and packaging lines. PowerFlex drives control pumps, fans and conveyors. Many SLC 500 racks are still in service.

Ordering Allen-Bradley modules and drives: what we need

Send the full catalog number, the series letter and, for controllers and communication modules, the firmware revision printed on the side label. Compatibility with an existing project depends on these. For PowerFlex drives, give the complete catalog string, which encodes voltage, current rating, enclosure and options, plus the motor nameplate data. For SLC 500 parts, tell us the rack size and processor so that we can check slot and power supply loading in the manufacturer's manuals. A label photo avoids most mistakes.

Frequently Asked Questions

What power supply does the 1766-L32BXBA use?
24V DC Class 2 SELV, with up to 50 W consumption.
How many I/O does it have?
24 inputs (20 digital and 4 analog) and 14 outputs (12 digital and 2 analog).
What output types are fitted?
Six relay outputs and six FET DC outputs, three of which are high speed with PTO and PWM.
What communication ports are built in?
An EtherNet/IP port and an isolated RS-232/RS-485 combo port.
How many expansion modules can it support?
Up to seven 1762 expansion modules, within the bus current limits.