- Automation & ControlView all 2,610 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Motor Soft Starters
- CCTV & Security
- Encoders
- HMI Displays
- Pneumatic Cylinders
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: ABB
ABB S203M-C25 3P MCB 25 A C Curve, S200M
Description
ABB S203M-C25 3P miniature circuit breaker, 25 A C curve
The ABB S203M-C25 is a 3P miniature circuit breaker rated 25 A with a C tripping characteristic, from the System pro M compact S200M series, which ABB describes as suitable for residential, commercial and industrial use, with breaking capacities up to 10 kA. It protects cables and equipment against overload through a thermal release and against short circuit through an electromagnetic release, and it is current limiting. The order code is 2CDS273001R0254.
Its rated short-circuit capacity is 10 kA AC, its rated operational voltage is 400 V AC and its width on the DIN rail is 52.5 mm. The data lists energy limiting class 3, which reflects the let-through energy under fault.
The 25 A, three-pole rating suits mid-sized three-phase feeders such as ventilation units, pump sets of a few kilowatts, heating banks and sub-boards in plant buildings.
Reading the S203M-C25 type designation
The S200 family designation can be read like a short specification, which makes a comparison of options quick.
| Code group | Meaning |
|---|---|
| S203M | Series prefix; S200M family |
| 3 | Number of poles in the type code, 3P |
| C | Tripping characteristic C (general purpose) |
| 25 | Rated current 25 A |
The C characteristic trips the electromagnetic release in the range of five to ten times the rated current in line with IEC/EN 60898-1, which suits most mixed loads including lighting, sockets, small motors and control transformers. B and D characteristics exist in the family for other inrush conditions.
S203M-C25 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | ABB / S203M-C25 |
| Order code / EAN | 2CDS273001R0254 / 4016779550475 |
| Product type | Miniature circuit breaker, S200M – 3P – 25 A – C – (AC) 10 kA |
| Number of poles | 3P |
| Rated current In | 25 A |
| Tripping characteristic | C |
| Rated short-circuit capacity | 10 kA AC |
| Rated operational voltage | acc. to IEC 60898-1 400 V AC |
| Maximum operational voltage | Maximum (Incl. Tolerance) 440 V AC |
| Rated ultimate breaking capacity Icu (as listed) | (230 V AC) 25 kA |
| Rated service breaking capacity Ics (as listed) | (230 V AC) 7.5 kA |
| Energy limiting class | 3 |
| Rated impulse withstand voltage | 4 kV |
| Power loss | 9.6 W |
| Electrical / mechanical endurance | 20000 AC cycle / 20000 cycle |
| Ambient air temperature | Operation -25 to +55 °C |
| Terminal type | Failsafe Bi-directional Cylinder-lift Terminal |
| Connecting capacity | Busbar 10/10 mm² |
| Tightening torque | 2.8 N·m |
| Mounting | 35 mm DIN rail, TH35-15 acc. to IEC 60715 |
| Dimensions W x H x D | 52.5 mm x 88 mm x 69 mm |
| Net weight | 0.345 kg |
| Accessories available | Yes |
| Standards | IEC/EN 60898-1 |
Values come from the ABB product page for the S203M-C25. Short-circuit values depend on the voltage and the pole count, so use the line that matches your system voltage.
How the S203M-C25 trips
The thermal element in the S203M-C25 bends with sustained overcurrent and trips with a delay that grows shorter as the overload increases, which gives time for motor or transformer starting currents while protecting the cable. The electromagnetic release acts without delay on a short circuit and, together with the current-limiting design, keeps the let-through energy low.
The toggle carries a contact position indication (listed by ABB as Red ON / Green OFF), which helps an operator tell the state at a glance. The mechanical endurance listed by ABB is {g(a,’Mechanical Endurance’)} and the electrical endurance is {g(a,’Electrical Endurance’)} at the rated conditions, which is a useful basis for planning inspection intervals.
In desalination and water treatment plants it is a common rating for dosing-skid and blower feeders, where the upstream distribution already uses the same System pro M compact busbar system.
Where the S203M-C25 fits and which parts go with it
The S203M-C25 sits in a final-circuit or sub-distribution board, normally downstream of a main switch, an RCD or an incoming breaker. Because it is current limiting, it helps back-up protection and cascading with other devices; check the cascading tables of the manufacturer for the exact upstream device.
ABB notes that a bottom-fitting auxiliary contact can be mounted on this series to save space, and the data lists accessories as available for this type.
Other types in the same family include S201M-C16, S201M-C25, S203M-C10, S203M-C16, S203M-C32, S203M-C50, S203M-C63. This page covers the S203M-C25.
Selection checklist for the S203M-C25
- Rated current: confirm that 25 A matches the cable cross-section and the connected load, including ambient derating.
- Pole count: this is a 3P device, so check that the neutral and phase arrangement of the board matches.
- Short-circuit capacity: the rated short-circuit capacity is 10 kA AC; compare it with the prospective fault level at the board.
- Characteristic: C is suited to general loads; choose B for long cable runs with a low fault level and D for high inrush.
- Accessories: ABB lists accessories as available: Yes. Decide on auxiliary or signalling contacts before you order.
- Space: allow 52.5 mm of DIN rail width and the height of the board enclosure.
Installation, commissioning and maintenance of the S203M-C25
Clip the S203M-C25 onto a 35 mm DIN rail and, where used, a busbar; the connecting capacity listed by ABB is Busbar 10/10 mm². Use a Pozidriv 2 screwdriver and tighten terminals to 2.8 N·m.
At commissioning, close the breaker, check the voltage at the terminals and test the downstream device. Label every circuit with its load and cable size in the board schedule.
Maintain by inspecting terminals for tightness, discolouration and heating, and operate the toggle periodically to keep the mechanism free. Replace a breaker that has tripped on a heavy short circuit if there is any sign of damage to the housing or terminals.
Typical applications of the S203M-C25 in Oman and the GCC
The 25 A, three-pole rating suits mid-sized three-phase feeders such as ventilation units, pump sets of a few kilowatts, heating banks and sub-boards in plant buildings.
High enclosure temperatures are common in outdoor kiosks and rooftop boards. The ABB data lists an operating range of -25 to +55 °C, and breaker loading should be checked against the real board temperature, since thermal trips are sensitive to heat from neighbouring devices.
S203M-C25 and the neighbouring S200M breakers
| Type | Poles | Rated current | Rated short-circuit capacity | Width |
|---|---|---|---|---|
| S201M-C16 | 1P | 16 A | (AC) 10 kA | 17.5 mm |
| S201M-C25 | 1P | 25 A | (AC) 10 kA | 17.5 mm |
| S203M-C10 | 3P | 10 A | (AC) 10 kA | 52.5 mm |
| S203M-C16 | 3P | 16 A | (AC) 10 kA | 52.5 mm |
| S203M-C25 | 3P | 25 A | (AC) 10 kA | 52.5 mm |
| S203M-C32 | 3P | 32 A | (AC) 10 kA | 52.5 mm |
| S203M-C50 | 3P | 50 A | (AC) 10 kA | 52.5 mm |
| S203M-C63 | 3P | 63 A | (AC) 10 kA | 52.5 mm |
The S203M-C25 is highlighted here for 3P protection at 25 A. If the load grows, move to the next current rating rather than changing the characteristic.
Information to send with an RFQ for the S203M-C25
- Exact type S203M-C25 (order code 2CDS273001R0254), quantity and required delivery time.
- Load current, cable size and the type of load.
- Supply voltage, system earthing and prospective short-circuit current.
- Accessories required, if any.
- Board type and ambient temperature.
- Documents needed with the order, for example datasheets.
Documents and quotation
The official ABB data sheet for the S 200 M series (document 2CDC002157D0202, English) is attached on this page as a PDF and applies to the ABB S203M-C25. It covers the full System pro M compact S 200 and S 200 M range: tripping characteristics B, C, D, K and Z, rated currents from 0.5 to 63 A, breaking capacity to IEC/EN 60898-1 and IEC/EN 60947-2, UL 1077 data, terminal capacity, accessories and dimension drawings. Check the rating and the characteristic against your circuit before ordering, then send us the quantity and the delivery location for a quotation.
Seven Star LLC supplies ABB low-voltage protection devices in Oman and the GCC. Share your board schedule and we will match the breakers, the accessories and the busbars.
Other Models in the Abb S200m Mcb Range
Seven Star LLC supplies models from the Abb S200m Mcb range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| ABB S203M-C16 3P MCB 16 A C Curve, S200M | Circuit Breakers | View details |
| ABB S203M-C25 3P MCB 25 A C Curve, S200M | Circuit Breakers | You are viewing this model |
| ABB S203M-C32 3P MCB 32 A C Curve, S200M | Circuit Breakers | View details |
| ABB S203M-C50 3P MCB 50 A C Curve, S200M | Circuit Breakers | View details |
| ABB S203M-C63 3P MCB 63 A C Curve, S200M | Circuit Breakers | View details |
| ABB S201M-C16 1P MCB 16 A C Curve, S200M | Circuit Breakers | View details |
| ABB S201M-C25 1P MCB 25 A C Curve, S200M | Circuit Breakers | View details |
| ABB S203M-C10 3P MCB 10 A C Curve, S200M | Circuit Breakers | View details |
Datasheets & Documents
- Datasheet ABB S 200 / S 200 M Miniature Circuit Breaker Data Sheet (PDF) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.
ABB company profile
| Formed | 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50% |
|---|---|
| ASEA | Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators |
| Brown, Boveri & Cie | Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri |
| Headquarters | Zurich, Switzerland; ABB Ltd became the group holding company in 1999 |
| Ownership | Public company listed on SIX Swiss Exchange and Nasdaq Stockholm |
| Brands in the group | Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers |
| Product families | Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots |
Milestones
- 1883: ASEA is founded in Västerås, Sweden.
- 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
- 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
- 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
- 2011 and 2017: Baldor Electric and B&R join ABB.
- 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.
Choosing an ABB drive
ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.
Where ABB products are used
In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.
ABB products we list
| Family | Examples |
|---|---|
| AC drives | ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module |
| Breakers, motor control and protection | SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay |
| Flow measurement | ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500 |
| Pressure, temperature and level | 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge |
| Analysers | Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210 |
| Control systems and actuators | AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000 |
Ordering ABB products: what we need
Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.
Frequently requested ABB models: ABB FENA-21 Two-Port Ethernet Adapter Module, ABB AHM550.
Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.
FAQ
Questions about the ABB S203M-C25 3P MCB 25 A C Curve, S200M
Answers from our engineering team on installation, compatibility and integration.
01What is the rated current of the S203M-C25?
The S203M-C25 is rated 25 A with a C tripping characteristic. It is a 3P miniature circuit breaker, so the pole count must match the circuit it protects.
02What is the short-circuit capacity of the S203M-C25?
The ABB data lists a rated short-circuit capacity of 10 kA AC. Compare this with the prospective short-circuit current at the board before you rely on the device.
03Can I fit accessories to the S203M-C25?
Yes. ABB lists accessories as available for this type, and a bottom-fitting auxiliary contact can be mounted on the series to save space.
04What DIN rail width does the S203M-C25 need?
The ABB data lists a width of 52.5 mm, a height of 88 mm and a depth of 69 mm. It clips on a 35 mm DIN rail.
05What does the C characteristic of the S203M-C25 mean?
The C characteristic is a general-purpose curve in which the electromagnetic release acts at five to ten times the rated current in line with IEC/EN 60898-1. It suits lighting, sockets and small motor loads.


















Reviews